Apc BE350G-CN Manual de Usario
Apc
Unión Postal Universal
BE350G-CN
Lee a continuación 📖 el manual en español para Apc BE350G-CN (2 páginas) en la categoría Unión Postal Universal. Esta guía fue útil para 8 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios
Página 1/2
Safety
Specifications
Connect the Battery
The Back-UPS is shipped with one battery cable disconnected. Remove the “Stop!
Connect the Battery” label that covers the outlets. Prior to connecting any equipment
to the unit, connect the battery cable to the unused battery terminal. It is normal for
small sparks to be seen when the battery cable is connected to the battery terminal.
Wall Mount Installation
• Horizontal installation, use 2 screws 5.0" (127 mm) apart.
• Vertical installation, use 2 screws 4.3" (110.4 mm) apart.
• Allow 5/16" (8 mm), of the screw to protrude from the wall.
Connect Equipment
Battery Backup + Surge Protection Outlets
Battery backup outlets provide protection to connected equipment when the
Back-UPS is turned on and connected to utility power.
Battery backup outlets receive power from the Back-UPS for a limited period of time
when a power outage, or brownout condition occurs.
Battery backup outlets provide protection from power surges or spikes.
Connect a computer, monitor and other peripheral devices to the outlets.
Surge Protection Outlets
Surge protection outlets provide protection to connected equipment when the
Back-UPS is connected to utility power, and is switched on or off.
Surge protection outlets provide protection from power surges or spikes.
Connect a printer, scanner or other peripheral devices that do not need to remain on
during power outages, or utility problems to the surge protection outlets.
Connect Network
The Back-UPS protects equipment connected to a 10/100 Base-T ethernet, from
power surges when connected through the Back-UPS coaxial connectors.
Turn On the Back-UPS
Press the POWER ON button located on the top of the Back-UPS. The Power On/
Replace Battery LED will illuminate and a single short beep will be audible to
indicate that the Back-UPS is providing protection for connected equipment.
The Back-UPS battery charges fully during the first 16 hours while connected to
utility power. The Back-UPS battery will charge while the Back-UPS is switched on
or off and is connected to utility power. Do not expect full battery run capability
during the initial charge time.
If the red Building Wiring Fault LED located on the side of the Back-UPS
illuminates, do not operate the Back-UPS. Have a qualified electrician correct the
building wiring fault.
Voltage Sensitivity Adjustment (optional)
The Back-UPS detects and reacts to line voltage distortions by transferring to battery
backup power to protect connected equipment. In situations where either the Back-
UPS or the connected equipment is too sens tage level it is itive for the input vol
necessary to adjust the transfer voltage.
1. Connect the Back-UPS to a wall outlet. The Back-UPS will be in Standby mode,
no indicators will be illuminated.
2. Press and hold the ON/OFF button for 10 seconds. The OnLine LED will
illuminate alternately green-amber-red, to indicate that the Back-UPS is in
Program mode.
3. The Power On/Replace Battery LED will flash either green, amber, or red to
indicate the current sensitivity level. Refer to the table for an explanation of the
transfer voltage sensitivity levels.
4. To select LOW sensitivity, press and hold the ON/OFF button until the LED
flashes green.
5. To select MEDIUM sensitivity, press and hold the ON/OFF button until the LED
flashes red.
6. To select HIGH sensitivity, press and hold the ON/OFF button until the LED
flashes amber.
7. To exit Program mode wait five seconds and all LED indicators will extinguish.
Program mode is no longer active.
This unit is intended for indoor use only.
Do not operate this unit in direct sunlight, in
contact with fluids, or where there is
excessive dust or humidity.
Connect the Back-UPS power cord directly to
a wall outlet. Do not use a surge protector or
an extension cord.
Input
Voltage 120 Vac Nominal
Frequency 60 Hz + 3
Brownout Transfers 92 Vac Typical
Over-voltage Transfer 139 Vac Typical
Output
UPS Capacity
(3 outlets) 350 VA, 200 W
Total Amperage
(6 outlets) 8 A (including UPS output)
Voltage - On Battery 115 Vac ± 8%
Frequency - On Battery 60 Hz + 1
Transfer Time 6 ms Typical, 10 ms maximum
Protection
and
Filtering
AC Surge Protection Full time, 340 Joules
EMI/RFI Filter Full time
AC Input Resettable circuit breaker
Battery
Type Sealed, maintenance-free, lead acid
Replacement battery cartridge RBC35
Average Life 3 - 5 years depending on the number
of discharge cycles and environmental
temperature
Physical
Net Weight 9 lb (4 kg)
Dimensions
Length x Width x Height 11 in x 6 in x 3 in
29 cm x 16 cm x 9 cm
Operating Temperature 32º F to 104º F (0º C to 40º C)
Storage Temperature 5º F to 113º F (–15º C to 45º C)
Operating Relative Humidity 0 to 95% non-condensing humidity
Operating Elevation 0 to 10,000 ft (0 to 3000 m)
EMC
Compliance
This device complies with part 68 and part 15 of the FCC rules.
Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) This device must accept
any interference received, including interference that may cause
undesired operation.
Press the battery compartment cover
release tab located on the rear side of the
unit. Slide the battery cover off.
Connect the battery cable securely to
the battery terminal.
Reinstall the battery compartment
cover. Be sure that the release tab locks
into place.
bu064a
bu065a
bu066a
LED
Flashes
Sensitivity
Setting
Input Voltage Range
(Utility Operation) Recommended Use
Green LOW 88 Vac to 142 Vac Use this setting with equipment that
is less sensitive to fluctuations in
voltage or waveform distortions.
Red MEDIUM 92 Vac to 139 Vac Factory default setting. Use this
setting under normal conditions.
Amber HIGH 96 Vac to 136 Vac Use this setting when connected
equipment is sensitive to voltage
and waveform fluctuations.
bu206a
Back-UPS
Battery Backup +
Surge Protection
Surge Protection
bu208a
CAUTION-Refer to bottom
of unit for safety markings.
Circuit
Breaker
Building
Wiring Fault
Network
Out
Push to
Reset
Network
In
User Manual Back-UPS® BE350G Series
990-3950B
7/2011
© 2011 APC by Schneider Electric. APC, the APC logo, Back-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion
Corporation, or their eir respective owners.affiliated companies. All other trademarks are property of th
Status Indicators
Troubleshooting Replace Battery
Use only approved APC replacement battery cartridges.
Deliver used batteries to a battery replacement facility in the packaging provided by
APC with the replacement battery cartridge.
To order replacement battery cartridges contact APC through the Web site
www.apc.com
Warranty
The standard warranty is 3 years in the USA and Canada, 2 years in all other regions
from the date of purchase. APC standard procedure is to replace the original unit with
a factory reconditioned unit. Customers who must have the original unit back due to
assigned asset tags and set depreciation schedules must declare such a need at first
contact with APC Technical Support. APC will ship the replacement unit once the
defective unit is received by the repair department or cross-ship upon the provision of
a valid credit card number. The customer pays for shipping to APC, and APC pays
ground freight transportation costs back to the customer.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common
problems.
2. If the problem persists, contact APC Customer Support.
a. Note the model number and serial number and the date of purchase. The
model and serial numbers are located on the rear panel of the unit and are
available through the LCD display on select models.
b. Call APC Customer Support and a technician will attempt to solve the
problem over the phone. If this is not possible, the technician will issue a
Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC
Web site for country specific instructions.
3. Pack the unit properly to avoid damage in transit. Never use foam beads for
packaging. Damage sustained in transit is not covered under warranty. Always
DISCONNECT THE UPS BATTERY before shipping in compliance with
U.S. Department of Transportation (DOT) and IATA regulations. The battery
may remain in the unit.
4. Write the RMA# provided by Customer Support on the outside of the package.
5. Return the unit by insured, pre-paid carrier to the address provided by Customer
Support.
Contact
APC Web site, www.apc.com
Status LED Indicator Audible Indicator On Audible Indicator Terminates
Power On
The Back-UPS is supplying utility power to connected
equipment.
The green LED illuminates. None N/A
On Battery
Back-UPS supplying battery power to battery backup outlets.
The green LED illuminates.The LED
is not illuminated during the beeps.
Back-UPS beeps 4 times
every 30 seconds.
Beeping stops when utility power is restored or
the Back-UPS is turned off.
Low Battery warning
The Back-UPS is supplying battery power to the battery backup
outlets and the battery is near a total discharge state.
The green LED illuminates with
rapid green flashes.
The Back-UPS emits rapid
beeping, every 1/2 second.
Beeping stops when utility power is restored or
the Back-UPS is turned off.
Replace Battery
• The battery is disconnected.
• The battery needs to be charged, or replaced.
•Replace Battery LED flashes.
• Replace Battery and Power On
LEDs flash alternately.
Constant tone
Constant tone Back-UPS is turned off.
Overload Shutdown
While on battery power an overload condition has occurred in
one or more of the battery backup outlets while the Back-UPS
is operating on battery power.
None Constant tone Back-UPS is turned off.
Sleep Mode
While on battery power the battery is completely discharged.
The Back-UPS will “awaken” once utility power is restored. None The Back-UPS beeps once
every four seconds.
The beeping stops when:
• Utility power is restored
• If utility power is not restored within 32 seconds
• The Back-UPS is turned off
Building Wiring Fault
The building wiring presents a shock hazard that must be
corrected by a qualified electrical.
Building Wiring Fault LED
illuminates red None The Back-UPS is unplugged from the wall outlet
or is plugged into an improperly wired outlet.
Problem and Possible Cause Solution
The Back-UPS will not turn on
The Back-UPS has not been turned
on. Press the POWER ON button.
The Back-UPS is not connected to
utility power, there is no utility
power available at the wall outlet, or
the utility power is experiencing a
brownout or over voltage condition.
Make sure the power cord is securely connected
to the wall outlet, and that there is utility power
available at the wall outlet.Where applicable,
check that the wall outlet is switched on.
The battery is not connected. Connect the battery. Refer to “Connect the
Battery” on page 1 of this manual.
In the event that the Back-UPS receives no utility
power and the battery is connected, a cold-start
can be initiated. Press and hold the Power On
button until the Back-UPS emits two beeps.
The Back-UPS is on, the Replace Battery LED flashes and the unit emits a
constant tone
The battery is disconnected. Refer to the “Connect the Battery” on page 1.
Connected equipment loses power
A Back-UPS overload condition has
occurred. Remove all nonessential equipment connected to
the outlets. One at a time reconnect equipment to
the Back-UPS.
The Back-UPS battery is completely
discharged.
Connect the Back-UPS to utility power and allow
the battery to recharge for eight hours.
PowerChute software has performed
a shutdown due to a power failure. This is normal Back-UPS operation.
Connected equipment does not
accept the step-approximated sine
waveform from the Back-UPS.
The output waveform is intended for computers
and peripheral devices. It is not intended for use
with motor driven equipment.
The Back-UPS may require service. Contact APC Technical Support for more in
depth troubleshooting.
The Power On LED is illuminated and the Back-UPS beeps 4 times every
30 seconds
The Back-UPS is operating on
battery power. The Back-UPS is operating normally on battery
power. At this point the user should save all open
files, and shutdown the computer. When utility
power is restored the battery will recharge.
The Power On LED flashes once every second while the Back-UPS beeps
once every second
The Back-UPS battery has
approximately two minutes of
remaining runtime.
The Back-UPS battery is near a total discharge
state. At this point the user should save all open
files, and shutdown the computer. When utility
power is restored the battery will recharge.
The Building Wiring Fault LED illuminates
The building wiring presents a shock
hazard that must be corrected by a
qualified electrical.
Do not operate the Back-UPS. Call a qualified
electrician to correct the building wiring fault.
The Back-UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful
life and should be replaced.
Leave the Back-UPS connected to utility power
for 16 hours while the battery charges to full
capacity.
As a battery ages, the runtime capability
decreases. Contact APC at the Web site
www.apc.com, to order replacement batteries.
The connection from the Back-UPS to the internet is lost during a power
outage
The modem has lost power. Connect the modem cable into one of the Battery
Backup + Surge Protection outlets.
Especificaciones del producto
Marca: | Apc |
Categoría: | Unión Postal Universal |
Modelo: | BE350G-CN |
¿Necesitas ayuda?
Si necesitas ayuda con Apc BE350G-CN haz una pregunta a continuación y otros usuarios te responderán
Unión Postal Universal Apc Manuales
18 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024
4 Octubre 2024
Unión Postal Universal Manuales
- Unión Postal Universal AEG
- Unión Postal Universal IKEA
- Unión Postal Universal HP
- Unión Postal Universal Lenovo
- Unión Postal Universal Tripp Lite
- Unión Postal Universal Energenie
- Unión Postal Universal Voltcraft
- Unión Postal Universal Adj
- Unión Postal Universal Digitus
- Unión Postal Universal LevelOne
- Unión Postal Universal Eaton
- Unión Postal Universal CyberPower
- Unión Postal Universal Block
- Unión Postal Universal Avocent
- Unión Postal Universal Minuteman
- Unión Postal Universal Maruson
- Unión Postal Universal V7
- Unión Postal Universal Phoenix Contact
- Unión Postal Universal Puls Dimension
- Unión Postal Universal Salicru
- Unión Postal Universal Equip
- Unión Postal Universal Murr Elektronik
- Unión Postal Universal Altronix
- Unión Postal Universal Ditek
- Unión Postal Universal Bxterra
- Unión Postal Universal Middle Atlantic
- Unión Postal Universal FSP
- Unión Postal Universal Atlantis Land
- Unión Postal Universal PowerWalker
- Unión Postal Universal FSP/Fortron
- Unión Postal Universal Online USV
Últimos Unión Postal Universal Manuales
24 Octubre 2024
22 Octubre 2024
22 Octubre 2024
22 Octubre 2024
20 Octubre 2024
18 Octubre 2024
11 Octubre 2024
9 Octubre 2024
9 Octubre 2024
6 Octubre 2024