GE ZV850SB Manual de Usario

Lee a continuación 📖 el manual en español para GE ZV850SB (16 páginas) en la categoría campana extractora. Esta guía fue útil para 9 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/16
GE Monogram®
Installation
Instructions
36" Island
Vent Hood
Model
ZV850
Before you begin – Read these instructions completely and carefully.
IMPORTANT – Save these instructions for local inspector’s use.
IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer – Be sure to leave these instructions with the Consumer.
Note to Consumer – Keep these instructions with your Owner’s Manual for future reference.
WARNING: This appliance must be properly grounded. See “Electrical Supply,” page 5.
2
If you have a question concerning the
installation of this product, call the GE Answer
Center® Consumer Information Service at
800.626.2000, 24 hours a day, 7 days a week.
If you received a damaged vent hood, you
should immediately contact your dealer or
builder.
For Monogram local service in your area,
1.800.444.1845.
For Monogram service in Canada, call
1.888.880.3030.
For Monogram Parts and Accessories, call
1.800.626.2002.
CAUTION!
Due to the weight and size of this vent hood
and to reduce the risk of personal injury or
damage to the product, TWO PEOPLE ARE
REQUIRED FOR PROPER INSTALLATION.
Proper installation is the responsibility of
the installer. Product failure due to improper
installation is not covered under the GE
Appliance Warranty. See the Owner’s
Manual for warranty information.
WARNING:
To reduce the risk of fire or electrical
shock, do not use this hood with any external
solid-state speed control device. Any such
alteration from original factory wiring could
result in damage to the unit and/or create
an electrical safety hazard.
To reduce the risk of fire and to properly
exhaust air, be sure to duct air outdoors. Do
not vent exhaust air into spaces within walls or
ceilings or into attics, crawl spaces or garages.
WARNING: TO REDUCE THE RISK OF FIRE,
USE ONLY METAL DUCTWORK.
TO REDUCE THE RISK OF FIRE,
ELECTRICAL SHOCK OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended
by the manufacturer. If you have any
questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch
power off at the service panel and lock service
panel to prevent power from being switched
on accidentally. If the service panel cannot be
locked, fasten a tag or prominent warning
label to the panel.
For general ventilating use only. Do not use
to exhaust hazardous or explosive materials
or vapors.
Structural framing, installation work and
electrical wiring must be done by qualified
person(s), in accordance with all applicable
codes and standards including fire-rated
construction.
Sufficient air is needed for proper combustion
and exhausting of gases through the flue
(chimney) of fuel burning equipment to
prevent back drafting. Follow the heating
equipment manufacturers guidelines and
safety standards such as those published by
the National Fire Protection Association
(NFPA), and the American Society for
Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE), and the local code
authorities.
Local codes vary. Installation electrical
connections and grounding must comply
with applicable codes. In the absence of
local codes, the vent should be installed in
accordance with National Electrical Code
ANSI/NFPA 70-1990 or latest edition.
Contents Model Available ............................................ 3
Required Accessory ...................................... 3
Recirculating Operation .............................. 3
Product Dimensions ..................................... 3
Using Duct Cover Accessories ..................... 4
Installation Preparation
Tools and Materials Required ..................... 5
Power Supply ................................................ 5
Duct Fittings ................................................. 6
Step 1, Advance Planning ........................ 7, 8
Installation
Step 2, Remove the Packaging .................... 9
Step 3, Check Installation Hardware .......... 9
Step 4, Mount Template ............................ 10
Step 5, Install Support Frame .................... 10
Step 6, Secure Wiring ................................ 11
Step 7, Size and Install Ductwork.............. 11
Step 8, Install Decorative Duct Covers ..... 12
Step 9, Install Hood ................................... 13
Step 10, Connect Electrical ....................... 13
Step 11, Slide Duct Cover Down,
Install Side Utility Bars ................ 14
Step 12, Install Filters ................................. 15
Step 13, Finalize Installation ..................... 15
3
Design Information
36" Island Vent Hood
Model
ZV850
Model
Available
Required
Accessory
This vent hood is designed to
be used in vented ceiling mounted
installations.
The vent hood must be installed 24" min. and
30" max. above the cooking surface. 25-1/2" is
recommended for best venting performance
and to insure that the duct cover meets the
ceiling. The cooking surface should be at least
36" above the floor. Installation will be easier if
the vent hood is installed before the cooktop
and countertop is installed.
Product
Dimensions
ZX858 – For 8 ft. ceiling height.
This kit includes decorative duct covers and
support frames to reach an 8 ft ceiling height.
ZX859 – For 9 ft. ceiling height.
This kit includes decorative duct covers and
support frames to reach an 9 ft ceiling height.
* The distance between the cooking surface and the bottom
of the hood must be at least 24” and up to 30”. The 25-1/2”
recommended installation height, above the standard 36”
countertop, will insure duct cover fit to the ceiling.
ZX8510 – For 10 ft. ceiling height.
This kit includes decorative duct covers and
support frames to reach a 10 ft. ceiling height.
Order the required accessory at the same time
as the vent hood and have on site before
installation.
*25-1/2" Recommended
36" Reference
*26-1/4" for 8 ft. Ceiling
Using ZX858 Accessory
38-1/8" for 9 ft. Ceiling
Using ZX859 Accessory
50-1/8" for 10 ft. Ceiling
Using ZX8510 Accessory
*Height
to Ceiling
8-1/4"
35-3/8"
27-1/2"
Recirculating
Operation
This hood may be installed for recirculating
operation. One of the following kits is
required and must be ordered with the hood.
ZXR858 – For 8 ft. ceiling height.
ZXR859 – For 9 ft. ceiling height.
ZXR8510 – For 10 ft. ceiling height.
NOTE: Accessories to meet proper
ceiling height are required to complete
the installation.
Both the hood and accessory must be
on site at the time of installation. Follow
the installation instructions packed with
the accessory to complete the installation.

Especificaciones del producto

Marca: GE
Categoría: campana extractora
Modelo: ZV850SB

¿Necesitas ayuda?

Si necesitas ayuda con GE ZV850SB haz una pregunta a continuación y otros usuarios te responderán




campana extractora GE Manuales

campana extractora Manuales

Últimos campana extractora Manuales