Type 1 + Type 2 / Class I Surge Protection Devices
SPN8***
SPN801 / SPN801R SPN802 / SPN802R
Tested to EN 61643-11
(VDE0675-6-11) 2002-12
EN 61643-11
(VDE0675-6-11) 2002-12
L1/L2/L3/N => PE L1/L2/L3 => N N => PE
SPD type / class Type 1 + Type 2 / I / B
Type of connexion Parallel connection
Type of power supply system TN-S - System TT - System
Type of protection Common modes Common and differential modes
Nominal voltage UN230V / 400V ac
Rated voltage Uc255V ac
Voltage protection level Up 1.5kV 255V ac
TOV-voltage UT440V / 5s 1200V / 200ms
Rated load current I(L) 315A
I(L-L) 125A
Follow current interrupting rating I
50 kA 100kA
Nominal discharge current (8/20) I
n100kA 25kA 100kA
Impulse current (10/350) I
imp 100kA 25kA 100kA
Residual current IPE 100mA
Max. rating of overcurrent
protection
fuse 125A gL / gG serial or 315A parallel
MCCB 125A serial or 160A parallel
Short-circuit withstand capability
with max. overcurrent protection
fuse 50kA ac 25kA ac
MCCB 50kA ac 25kA ac
Response time tA< 100ns
Operating temperature range - 40°C ….+ 60°C
Indication of SPD disconnector Green - red on L1, L2, L3, N
Cross sectional area min 10mm
2 solid / exible
L1, L2, L3, PE max 50mm
2 multi-stranded / 35mm
2 exible
Tightening torque for terminals 7.0 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width 6 8
Weight 1260 g 1272 g
Approval marking VDE
Protection
Devices
4.56 General Catalogue • Protection Devices • Technical
Type 1 & 2 Surge Protection Devices
SPA215*, SPA400*, SPA401*
SPA201 SPA401
Tested to EN 61643-11 2002-12
SPD type / class Type 1 + Type 2 / Class I
Energy-coordinated
protection effect on terminal
equipment
Type 1 + Type 2
Energy-coordinated
protection effect on
terminalequipment 5 m
Type 1 + Type 2 + Type 3
Type of connexion Parallel connection
Type of power supply
system
TT / TN system
Type of protection common and differential modes
Nominal voltage UN230V/400V ac
Rated voltage Uc255V ac
Voltage protection level Up 1.5kV
TOV Voltage UT440V / 5s
1200V / 200ms
Rated load current I(L) n/a
I(L-L) n/a
Follow current interrupting
rating
I25kA rms
100A rms
Nominal discharge current
(8/20)
In12.5kA
25kA
12.5kA
50kA
Impulse current (10/350) Iimp 12.5kA
25kA
12.5kA
50kA
Max. rating of overcurrent
protection
fuse 160A gL / gG
MCCB n/a 160A
Short-circuit withstand
capability with max.
overcurrent protection
fuse 25kA rms
MCB n/a
Response time tA 100ns
Operating temperature
range
- 40°C ….+ 80°C
Indication of SPD
disconnector
Green/Red ag on L and N Green/Red ag on L1, L2, L3 and N 
Cross sectional area min 1,5mm2 solid / exible
max 35mm2 stranded / 25mm2 exible
Tightening torque for
terminals
4 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width 2 4
Weight 275 g 480 g
Approval marking KEMA
4.57
Sales Service Centre • 01952 675612 Technical Support Helpline • 01952 675689
Type 2 / Class II Surge Protection Devices
SPN215*, SPN415* & SPN440*
SPN215D/R SPN415D/R SPN440D/R
Tested to EN 61643-11 (VDE0675-6-11) 2002-12
SPD type Type 2 according to EN 61643-11
SPD class Class II according to IEC 61643-1
Type of connexion Parallel connection
Maximum continuous operationg voltage U
cLine / Neutal 255V
Neutral/ PE 275V
Voltage protection level Up≤≤≤ 1kV 1kV 1.2kV
Nominal discharge current (8/20 µs)
[(DC+/DC-) --> PE]
In5kA 5kA 15kA
Max. discharge current (8/20 µs) [(DC+/DC-) -->
PE]
Imax 15kA 15kA 40kA
Short-circuit withstand capability with max.
overcurrent protection
10kA - 32A 10kA - 32A 20kA - 32A
Operating temperature range - 40°C ….+ 80°C
Indication of SPD disconnector Green - Yellow - Red
Cross sectional area min 1,5mm2 solid / exible
max 35mm2 multi-stranded / 25mm2 exible
Tightening torque for terminals 4.0 Nm
Mounting on 35mm DIN rail in accordance with EN 60715
Enclosure material grey thermoplastic, UL 94V-0
Degree of protection IP20
Modular width (DIN 43880) 2 2 4
Auiliary contact. Voltage/ nominal current
(only applicable on the R suf x products)
230V/ 0.5A
12Vdc
10mA
Protection
Devices

Especificaciones del producto

Marca: Hager
Categoría: No categorizado
Modelo: SPN215R

¿Necesitas ayuda?

Si necesitas ayuda con Hager SPN215R haz una pregunta a continuación y otros usuarios te responderán




No categorizado Hager Manuales

No categorizado Manuales

Últimos No categorizado Manuales