Design 30
RCCB Incomer Consumer Unit
Consumer Unit
Design 30 RCCB Incomer
For the distribution of power in a residential
application, conforming to BS EN 61439-3
including Annex ZB (16kA rating).
Design 30 is the enhanced board for use in applications where the
consumer unit is located in a living area of the dwelling and allows
compliance with BS 7671:2018;
Regulation 421.1.201 within domestic (household) applications consumer
units and similar assemblies shall comply with BS EN 61439-3 and shall
have their enclosure manufactured from a non-combustible material.
Regulation 411.3.3 additional protection by means of a 30mA RCD
Regulation 522.6.202 protection of wiring concealed in walls or partitions
with RCD 30mA.
Regulation 531.3.3 Selection of appropriate RCD. Type A RCCBs can
detect and respond to both AC and pulsating DC components.
RCCB incomer boards are generally used as sub distribution boards in
residential applications where all outgoing circuits share the same 30mA
RCD protection.
Description Size Cat ref.
Cat ref.
with Knockouts
2 Way 40A 30mA Type A RCCB Incomer 2 VM402AH VM402AHK
Con.unit,D30,6w,63A,30mA Type A RCCB 3 VM406AH VM406AHK
Con.unit,D30,8w,63A,30mA, Type A RCCB 4 VM410AH VM410AHK
Con.unit,D30,6w,100A,30mA type A RCCB 3 VM306AH VM306AHK
10 Way 100A 30mA Type A RCCB Incomer 4 VM310AH VM310AHK
14 Way 100A 30mA Type A RCCB Incomer 5 VM314AH VM314AHK
VM306 HA
Features & Benets
- Type A RCCBs for general purpose circuits and circuits containing
equipment incorporating electronic components.
- Cable clampSecures supply cables on entry to main incoming
device preventing any movement being transmitted through metertails
to device.
- Square cable entry points top and bottom for use with cable trunking.
- Meter tail cable entry plate (VM04CE) provided
- Rear knockouts for ease of cable entry – Cable protector plate
(VM02CE) provided
- Rigid top wallEnhances rigidity to prevent distortion when removing
knockouts.
- Front cover retained screws – Prevents loss during installation
- Locate and hold cover allows use of both hands whilst tting cover.
- Full metal din rail – Secure and stable attachment of devices.
- Quick release clip on MCB/RCBO Allows tting and removal of
device with busbar in place.
- Optimised cabling space – Din rail positioned to provide maximum
space at top of board.
- Top mounted terminal rail makes the wiring of the neutral and earth
connections neat and simple.
- Health and safety lock allows the door to be secured with circuits
isolated during construction (via accessory see overleaf)
- Torque settings displayed inside front covereasily accessible to
electrician during installation and maintenance.
RCCB
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 2
Design 30
RCCB Incomer Consumer Unit
Technical Characteristics
Standards BS EN 61439-3
Classication Consumer Unit
Rated & Operational Voltage (Un/Ue) 230V a.c 50 Hz
Rated Insulation Voltage (Ui) 320V a.c. 50Hz
Rated Frequency (fn) 50 Hz
Rated impulse withstand voltage (Uimp) 4kV
Rated Current of the Assembly (Ina) 40A/63A/100A
Rated Current of an Outgoing Circuit I
nC MCB 6A-63A (Marked Rated Current on Device)
Rated Conditional Short Circuit of the Assembly (I
cc) Annex ZB: 16kA rms at 250V, power factor 0.6 with equipment and
arrangements specied in Hager's technical documentation/catalogue
Protection against electric shock Consumer Unit shall be installed in an electrical system conforming to IEC
60364 / BS 7671
Rated Diversity Factor (RDF) / Values of assumed loading 2 Way to 3 Way - 0.8, 4 Way to 5 Way - 0.7, 6 Way to 9 Way - 0.6, 10 Way and
above - 0.5
Note: RDF only applies to continuously and simultaneously loaded circuits.
In principle, this means adjacent circuit breakers having a load on time exceeding 30 minutes or where a load not exceeding 30 minutes has an 'off' time less than
the 'on' time will need to have the rated diversity factor applied as indicated.
Pollution Degree 2
Types of System Earthing for which the assembly is designed TNC-S and TN-S when installed in an electrical system conforming to BS 7671
Intended locations Indoor use only
Stationary assembly
Degree of protection IP2XC with door open / closed and full compliment of devices / blanks tted.
Note: Where cables are installed through the top wall of the enclosure, gaps of
IP4X to be maintained.
Intended use Intended for use in domestic (residential) or similar premises
Electromagnetic compatibility (EMC) classication EMC environment B
External design Wall mounted, surface type, enclosed assembly.
Mechanical impact protection IK05
Type of construction Fixed parts
Incoming Line/Neutral terminal (80 - 100A board) 50mm²
Incoming Line/Neutral terminal (63A board) 25mm²
Incoming Earth Terminal 16mm²
Warranty - Hager undertakes to replace or repair at its discretion products should they become inoperable within the time periods as stated. - 2 Years
Height
Width
Depth
Design 30 Dimensions (mm)
Enclosure Size
2 3 4 5
Height 240 240 240 240
Width 149 221 293 364
Depth 102.5 102.5 102.5 102.5
Number of Knockouts
*Top Face 30 x 25 (mm) 2 2 2 2
*Top Face 40 x 30 (mm) 0 2 4 4
Back 100 x 50 (mm) 1 1 1 3
*Bottom Face 30 x 25 (mm) 2 3 4 4
Accessories
Cable protector plate Provides protection for cables entering from the rear of the board VM02CE
Top wall cable entry plates Provide more options for cable entry, when used with 50x50mm trunking IP ratings can be
achieved
VM03CE
Blind cable entry plates A blank plate for drilling which allows the installation of cable glands etc VM04CB, VM03CB
Health and safety lock Provides the ability to lock the consumer unit during the installation process VMHBL
Design 30 door locking kit Allows the board to be lockable VMLOCK
Grommet strip For protecting cables against damage when entering the board VM05GS
Rear stand off plates To stand consumer unit off wall allowing surface mounted cables to enter through rear of unit. VM01SP
* References with a ‘K’ sufx feature top and bottom square knockouts.