You can use this Quick Start for an overview of the AY1020 installation. For complete
installation and con guration information, download the device manual from the ifm.com
website.
Installation and connection
The device must be installed in a suitable housing protected against re and electrical or
mechanical in uences.
Connect the power and Ethernet cables according to the following table
Terminals Description Voltage Range Remarks
V+, V-
24VDC
PWR IN
Power supply for modules and
sensors (A-ports via PWR Out
connectors)
18…30 V DC,
max. 4 A
Only use PWR connectors on one
side top OR bottom. Do not use
both at the same time.
L+, L-
PWR OUT
Port 1…8
Power supply (A-ports) for sen-
sors or actuators. Be aware of
the current limitations.
24 V DC,
max. 200 mA
If more current is needed for B-
port devices, take it directly from
the power supply.
Con guration
Con gure IP address
You can use the following procedure with the IO-Link master embedded web interface to
con gure the AY1020 network settings (administrative rights required).
Note: The AY1020 is shipped from the factory with the Admin account enabled without a
password.
Open browser and enter IP address of the AY1020.
Note: The AY1020 default IP address is 192.168.1.250. You may need to change your
laptop or PC network address to the same network segment to access the web interface.
Click on [Con guration] [NETWORK].
Click on the button [EDIT].
Make any necessary network setting changes and click on [SAVE].
Connect and con gure devices
Connect the IO-Link and digital I/O devices
Use the web interface to con gure IO-Link, Ethernet/IP, and Modbus/TCP settings
If necessary, con gure the dedicated digital I/O ports.
If desired, upload the appropriate IODD les for the IO-Link devices.
Operating instructions
IO-Link Master Ethernet/IP AY1020
If desired, con gure the IO-Link device parameters using the web interface.
If desired, implement AY1020 features or options, such as: data storage mode, de-
vice validation mode, and data validation mode.
Use the Diagnostics pages to monitor or troubleshoot the devices.
If desired, connect to a PLC or HMI/SCADA (depending on the protocol).
Electrical connection
A quali ed electrician must connect the unit. The national and international regulations for
the installation of electrical equipment must be adhered to.
Voltage supply to EN 50178, SELV, PELV or UL. The module must be supplied from only
one common voltage source.
The inputs and outputs are not electrically isolated.
Disconnect power.
Connect the device as follows; only one terminal block on the top or the bottom may be
connected.
Terminal connection top
1
LEDs
2
1: Terminal connection ext. voltage supply and IO-
Link ports 1,2,5,6
2: terminal connection and IO-Link ports 3,4,7,8
Ext. voltage supply
1: V_ext. voltage GND DC
2: V_ext. voltage GND DC
3: V_ext. voltage +24 V DC
4: V_ext. voltage +24 V DC
Terminal connection bottom
Internal voltage, inputs/outputs
1: L+ sensor supply +24 V DC
2: L- sensor supply GND DC
3: DI digital input DI
4: DO digital output DO
Terminal connection IO-Link ports
Ports 1…8
1: L+ sensor supply +24 V DC
2: L- sensor supply GND DC
3: DI digital input
4: C/Q IO-Link / DI / DO
IP address set at the factory: 192.168.1.250
7391053/00 02/2016 ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen • Germany • http://www.ifm.com

Especificaciones del producto

Marca: IFM
Categoría: No categorizado
Modelo: AY1020
Peso.: 380 g
Manual de usuario: Ja
Indicadores LED: Stroom
Número de puertos Ethernet LAN (RJ-45): 2
Certificación: EN 55024, \r\nEN 61000-4-2 (ESD) Level 3, \r\nEN 61000-4-3 (RS) Level 3, \r\nEN 61000-4-4 (EFT) Level 4, \r\nEN 61000-4-5 (Surge) Level 3, \r\nEN 61000-4-6 (CS) Level 3, \r\nEN 61000-4-8, \r\nEN 61000-4-11
Interfaz: RS-232, RS-422, Ethernet, IPs
Temperatura de almacenamiento: -40 - 85 °C
Sistemas operativos compatibles: Windows 2000, Windows XP/2003/Vista/200/8/7 x86/x64
Seguridad: UL 508, EN 60950-1
Protocolos soportados: CIP (PCCC) on EtherNet/IP, DF1
Duplex completo: Ja
Ratio de transferencia: 0.1 Gbit/s
Temperatura de funcionamiento (TT): -40 - 75 °C
Humedad relativa de funcionamiento (VV): 5 - 95 procent