Installation Instructions
Electronic pressure sensor
for mobile applications
PT355x/PT3560/PT955x
706129 / 00 12 / 2011
UK
2
1 Safety instructions
• Please read this document prior to installing the unit. Ensure that the product is
suitable for your application without any restrictions.
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• Please check for all applications that the product materials (see Technical data)
are compatible with the media to be measured.
For the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).
Contents
1 Safety instructions 2 ................................................................................................
2 Function and features 3 ...........................................................................................
2.1 Applications ....................................................................................................3
3 Installation 3 ............................................................................................................
4 Electrical connection.............................................................................................4
5 Scale drawing 5 .......................................................................................................
6 Technical data .......................................................................................................6
3
UK
2 Function and features
The pressure sensor detects the system pressure and converts it into an analog
output signal.
• 4 ... 20 mA (PT355x/PT3560) / 0 ... 10 V (PT955x)
2.1 Applications
• The unit is suited for use in mobile vehicles.
• Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
bar PSI bar PSI bar PSI
PTx550 0...400 0...5 800 600 8 702 1 600 23 206
PTx551 0...250 0...3 625 400 5 800 1 000 14 504
PTx552 0...100 0...1 450 200 2 900 1 000 14 504
PTx553 0...25 0...362 0...60 870 600 8702
PTx554 0...10 0...145 0...25 362 300 4351
PT3560 0...600 0...8702 900 13053 2400 34809
MPa = bar ÷ 10 / kPa = bar × 100
Static and dynamic overpressures exceeding the indicated overload pres-
sure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the burst-
ing pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Insert the unit in a G¼ process connection.
Tighten firmly. Tightening torque: max. 25 Nm.