Installation Instructions
Flow sensor
SF57xx
SF5800
706075/00 08/2011
UK
2
1 Function and features
In conjunction with the VS3000 control monitor the flow sensor monitors flows in
liquids and gases, aggressive media.
The sensor / control monitor combination senses whether a preset flow value has
been reached (= medium flowing) or not (= medium not flowing) and provides a
switched signal.
2 Installation
The unit is adaptable for various process fittings. Adapters to be ordered sepa-
rately as accessories. The following titanium adapters are available:
mounting adapter G ½ order no. E40114
mounting adapter G ¼ order no. E40115
mounting adapter ½“ NPT order no. E40127
mounting adapter M12 x 1 order no. E40128
In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
When the unit is to be mounted at the bottom of the pipe, it should be free from
deposits.
When the unit is to be mounted at the top of the pipe, it should be completely
filled with the medium to be monitored.
In the case of vertical pipes mount the unit in a place where the medium flows
upwards (fig. 2).
1 2
Components integrated in the pipes, bends, valves, reductions, etc. lead to turbu-
lence of the medium. This affects the function of the unit.
3
UK
Recommendation: Adhere to the distances between sensor and sources of inter-
ference:
5...10 x D
S
3...5 x D
S
D = pipe diameter; S = sources of interference
Mounting operation
1 2 3
A
1. Lubricate the nut (3) and all threads with grease to ensure the nut can be loos-
ened and tightened several times.
Note: No grease must be applied to the sensor tip (A).
2. Screw the suitable adapter (2) onto the process fitting (1).
3. Insert the flow sensor into the adapter and tighten the nut (3); (max. tightening
torque 50 Nm).
Insertion depth of the sensor: min. 12 mm in the pipe. When the adapters are
used which are available as accessories the correct depth is ensured.
Note: The sensor tip must not touch the pipe wall.