IFM SF6200 Manual de Usario

Lee a continuación 📖 el manual en español para IFM SF6200 (3 páginas) en la categoría No categorizado. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/3
Installation Instructions
Flow sensor
701816 / 01 03 / 2011
2
1 Function and features
In conjunction with the VS3000 control monitor the flow sensor monitors flows in
liquids and gases. The sensor / control monitor combination senses whether a
preset flow value has been reached (= medium flowing) or not (= medium not flow-
ing) and provides a switched signal.
2 Installation
The unit is adaptable for various process fittings (clamp adapters to be ordered
separately as accessories, order no. E4016, E40174).
In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
- When the unit is to be mounted at the bottom of the pipe, it should be free
from deposits.
- When the unit is to be mounted at the top of the pipe, it should be completely
filled with the medium to be monitored.
In the case of vertical pipes mount the unit in a place where the medium flows
upwards (fig. 2).
1 2
To avoid malfunction a minimum
distance between the flow sensor and
bends, valves, changes in cross-sec-
tion or such like must be observed:
Min. 5 x pipe diameter upstream
(A),
min. 3 x pipe diameter downstream
(B).
D
A
B
min.
5 x D
min.
3 x D
3
UK
124
3
Screw the clamp adapter (2) onto the process fitting (1).
Insert the flow sensor (4) into the adapter.
Set the requested installation length.
Tighten the nut (3) (follow the instructions included with the clamp adapter).
Recommended insertion depth of the sensor: 20 ... 30 mm in the pipe. Min.
12 mm, max. to mid pipe.
Note: The sensor tip must not touch the pipe wall.
3 Electrical connection
Connection to control monitor VS3000 or SR59xx; voltage supply to
EN50178, SELV, PELV.
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a sec-
ondary Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).
4 Scale drawing
7,7
45
15
M12x1
217
10
20
25 146

Especificaciones del producto

Marca: IFM
Categoría: No categorizado
Modelo: SF6200

¿Necesitas ayuda?

Si necesitas ayuda con IFM SF6200 haz una pregunta a continuación y otros usuarios te responderán




No categorizado IFM Manuales

No categorizado Manuales

Últimos No categorizado Manuales