Installation Instructions
Airflow monitor analogue
SL520x
80259971 / 00 07 / 2017
UK
2
1 Safety instructions
Read this document before setting up the product and keep it during the entire
service life.
The product must be suitable for the corresponding applications and environ-
mental conditions without any restrictions.
Only use the product for its intended purpose .(→ 2 Function and features)
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
Installation, electrical connection, set-up, operation and maintenance of the unit
must be carried out by qualified personnel authorised by the machine operator.
Protect units and cables against damage.
2 Function and features
The airflow monitor monitors the flow velocity of airflows.
Contents
1 Safety instructions 2 ...............................................................................................
2 Function and features ..........................................................................................2
3 Function ...............................................................................................................3
4 Mounting ..............................................................................................................4
4.1 Insertion depth 4 ...............................................................................................
4.2 Alignment .......................................................................................................4
4.3 Installation distances 5 .....................................................................................
5 Electrical connection 5 ............................................................................................
6 Operation .............................................................................................................5
3
UK
3 Function
The unit provides an analogue signal that is proportional to the flow velocity.
Within the measuring range the analogue signal is 1...10 V.
10
9
8
7
6
5
4
3
2
1
00 2 4 6 8 10 12 14 16 18 20
Ua [V]
v [m/s]
Figure 1: Characteristics of the analogue output of SL5201, SL5202
Ua [V]
v [m/s]
1
0
2
3
4
5
6
7
8
9
10
2 4 6 80 10 12 14 16 18 20 22 24 26 28 30
Figure 2: Characteristics of the analogue output of SL5204
Reference conditions:
4" pipe, 1.5 m inlet pipe length, 20 °C medium temperature, insertion depth → 4.1.