www.welbilt.com 800-225-9916 1
Kolpak/RDI
Refrigeration System
Installation & Operation
Manual
Welbilt
2915 Tennessee Avenue North
Parsons, TN 38363
Phone: 800 9916- -225
www.welbilt.com
550001058- 10
April 7 201

www.welbilt.com 800-225-9916 2
Table of Contents
Safety Information ...................................................................................................................... 3
Receiving Inspection ................................................................................................................... 4
Locating and Mounting Condensing Units ...............................................................................4-6
Locating and Mounting Evaporator Coils .................................................................................6-7
Wiring 8 .........................................................................................................................................
Piping ..................................................................................................................................... 8-13
Leak Test ............................................................................................................................. 14-15
Evacuation ........................................................................................................................... 15-16
Refrigerant Charging ................................................................................................................. 16
Suction/Liquid Line Sizing Chart ...............................................................................................17
Operational Start- Up ........................................................................................................... 18-20
Compressor Superheat ............................................................................................................. 21
Evaporator Superheat ......................................................................................................... 22-23
Thermostat ........................................................................................................................... 24-28
Electric Defrost Timer ................................................................................................................ 29
Maintenance ............................................................................................................................ 30
Troubleshooting Charts ........................................................................................................ 31 33-
ArcticFox Local Area Dashboard & Alarms (LDA): .................................................................... 34
ArcticFox LDA Kit...................................................................................................................... 34
ArcticFox LDA Back Label ........................................................................................................35
ArcticFox LDA Side View .......................................................................................................... 35
ModBus Configuration .......................................................................................................... 36 38-
Installing The ArcticFox LDA: Option 1 ...................................................................................... 39
Installing The ArcticFox LDA: Option 2 ...................................................................................... 39
Installing The ArcticFox LDA: Option 3 ...................................................................................... 40
Using the ArcticFox Flash Drive For Data Logging The ArcticFox LDA ..................................... 40
Accessing The Local Dashboard .......................................................................................... 41 58-
Evaporator Troubleshooting ...................................................................................................... 59
Condensing Unit Troubleshooting ........................................................................................ 60 61-
Wiring Diagrams .................................................................................................................. 62 76-
Condensing Unit 208-230/1/60 .............................................................................................. 62
Condensing Unit 208-230/3/60 .............................................................................................. 63
Condensing Unit 460/3/60 ..................................................................................................... 64
Condensing Unit Medium Temp (MZ) Scroll 208-230/1/60 .................................................... 65
Condensing Unit Medium Temp (MZ) Scroll 208-230/3/60 .................................................... 66
Condensing Unit Low Temp (LZ) Scroll 208-230/1/60 ........................................................... 67
Refrigeration System Low Temp (LZ) Scroll 208-230/1/60 .................................................... 68
Condensing Unit Low Temp (LZ) Scroll 208-230/3/60 ........................................................... 69
Refrigeration System Low Temp (LZ) Scroll 208-230/3/60 .................................................... 70
Air Defrost Evaporator 115/1/ ................................................................................................ 71
Air Defrost Evaporator 208 230/60/1- ..................................................................................... 72
Air Defrost with 2 Evaporators 115/1/60 ............................................................................... 73
Air Defrost with 2 Evaporators 208-230/60/1 ......................................................................... 74
Electric Defrost Evaporator 208-230/1/60 .............................................................................. 75
Electric Defrost with 2 Evaporators 208-230/1/60 .................................................................. 76
System Start-Up Data Sheet ................................................................................................ 77 80-
Warranty Information................................................................................................................. 81

www.welbilt.com 800-225-9916 3
General Safety Information
Read this manual carefully before beginning the installation and operation of the
refrigeration system. Special attention is required to all sections identified with the
following warning and caution notices provided in both English and French languages :
WARNING
Text in a Warning box alerts you to a potential personal injury situation. Read each
Warning statement before proceeding and work carefully.
AVERTISSEMENT
Le texte qui figure dans les encadrés d’avertissement vous alerte d’une
situation pouvant potentiellement causer des blessures. Lire chaque
déclaration d’avertissement avant de procéder et travailler prudemment.
CAUTION
Text in a Caution box alerts you to a situation in which you could damage the
refrigeration system. Read each Caution statement before proceeding and work
carefully.
MISE EN GARDE
Le texte qui figure dans les encadrés de mise en garde vous alerte d’une
situation dans laquelle le système de réfrigération pourrait subir des
dommages. Lire chaque déclaration de mise en garde avant de procéder et
travailler prudemment.
Disregarding these special notices may result in personal injury and/or damage to the
refrigeration system.
Safety Notices:
Installation and maintenance/servicing to be performed only by trained and are
qualified personnel familiar with commercial refrigeration systems.
Ensure that all field wiring conforms to the equipment requirements and all
applicable local and national codes.
Disconnect all power sources before servicing the refrigeration equipment.
Sheet metal and coil surfaces have sharp edges. Use appropriate protective
gloves to prevent injury.
Use appropriate eye protection during installation and servicing.

www.welbilt.com 800-225-9916 4
Receiving Inspection
Check the shipment carefully and compare to the bill of lading. Account for all items
listed and inspect each container for damage. Carefully inspect for any concealed
damage. Report any shortages or damages to the carrier, note on the bill of lading, and
file a freight claim.
Damaged material cannot be returned to the manufacturer without prior approval. A
Return Material Authorization (RMA) must be obtained. Contact a sales representative
at 800- -826 7036.
Locating and Mounting Condensing Unit
General Guidelines:
Check the selected installation location to ensure that racks, braces, flooring,
foundations, etc. are adequate to support the condensing unit weight.
The installation location is clean, dry, and level.
Locate away from corrosive and noise sensitive atmospheres.
Use the condensing unit skid and base when moving the unit. Do not remove
unit from skid until the unit is moved to the mounting location.
Mount the condensing unit base to pads or structural rails using properly sized
bolts through the unit base. Center of condensing unit needs to be properly
supported.

www.welbilt.com 800-225-9916 5
General Guidelines - Condensing Unit Locating and Mounting (continued):
WARNING
Do not lift the condensing unit by the refrigerant tubing or components. These features
will not support the condensing unit weight. Injury and unit damage may occur!
AVERTISSEMENT
Ne pas soulever le groupe compresseur condenseur par les tubes ou les -
composants du réfrigérant. Ces éléments ne supporteront pas le poids du
groupe compresseur-condenseur. Cela pourrait entraîner des blessures et
des dommages à l’appareil!
Clearance Requirements:
Locate where there is a sufficient and unrestricted supply of clean ambient air.
Locate where this is adequate space for the removal of the heated discharged air
from the condensing unit area.
Do not position multiple units so that discharge air from one unit is blowing into
the condenser inlet air of the other unit.
All sides of the unit should be positioned a minimum distance equal to the total
width of the condensing unit away from any other unit, wall, or obstruction.

www.welbilt.com 800-225-9916 6
Clearance Requirements (continued):
Example of Multiple Units with Horizontal Airflow
CAUTION
Failure to observe clearance and air flow requirements will result in poor system
performance and premature equipment failure!
MISE EN GARDE
Le non-respect des exigences de dégagement et de circulation d’air aura
pour résultat un rendement médiocre du système et une défaillance
prématurée de l’équipement!
Locating and Mounting Evaporator Coil
General Guidelines:
Do not place the evaporator above or close to door openings. This will help
prevent potential icing problems.
Allow a minimum clearance equal to or greater than the coil height on all sides of
the coil for proper air flow and service access.
Use the evaporator coil for a template to locate and drill the mounting holes (1/2”
diameter).
Place a 1” and a 1 5/8” washer on each nylon bolt and insert through the drilled -
mounting holes in the ceiling from the exterior of the walk in ceiling panel - .
BUILDING WALL
(VIEWED FROM ABOVE)
AIR
FLOW
AIR
FLOW
MINIMUM
DISTANCE
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”

www.welbilt.com 800-225-9916 7
General Guidelines - Locating and Mounting Evaporator Coil (continued):
NOTE: Nylon bolts are supplied to prevent thermal transfer between the exterior
of the walk- - in and the interior of the walk in. Do not use metal bolts.
Lift the evaporator coil until the nylon bolts extend through the mounting
brackets.
Install washers and secure with nuts. Tighten until the coil is firm against the
ceiling. The evaporator coil must be level.
Additional information is available in the installation manual supplied with the
evaporator.
CAUTION
Failure to observe clearance and air flow requirements will result in poor system
performance and premature equipment failure!
MISE EN GARDE
Le non-respect des exigences de dégagement et de circulation d’air aura
pour résultat un rendement médiocre du système et une défaillance
prématurée de l’équipement!
Evaporator Coil Mounting Diagram

www.welbilt.com 800-225-9916 8
Wiring
All electrical connections and routing must comply with local and national codes. Do not
modify the factory installed wiring without written factory approval. The field wiring must
enter through the knockouts provided. Refer to the nameplate on the condensing or
evaporator coil to determine the proper electrical power supply. Wire type should be of
copper conductor only and properly sized to handle the electrical load. The unit and coil
must be properly grounded. Condensing unit wiring diagrams are cated inside this lo
installation manual and attached inside the electrical box cover. Evaporator coil wiring
diagrams are located inside this installation manual and inside the evaporator cover.
WARNING
All wiring must comply with local and national codes. Wiring must be performed only by
a refrigeration technician or certified electrician Failure to follow these guidelines may .
result in injury!
AVERTISSEMENT
Tout le câblage doit être conforme aux codes locaux et nationaux. Le
câblage ne doit être effectué que par un technicien en réfrigération ou un
électricien agréé. Le non-respect de ces consignes peut entraîner des
blessures!
CAUTION
Check all wiring connections, including factory terminals, before operation. Connections
can become loose during shipment and installation.
MISE EN GARDE
Vérifier toutes les connexions de câblage, y compris les bornes installées en
usine, avant de faire fonctionner l’appareil. Les connexions peuvent devenir
lâches pendant l’expédition et l’installation.
Piping
General Requirements:
All refrigeration piping and components are to be installed in accordance with applicable
local and national codes and in conformance with industry refrigeration guidelines to
ensure proper operation of the refrigeration system. Only refrigeration grade copper
tubing should be used. Long radius elbows should be used. Short radius elbows have
points of excessive stress concentration and are subject to breaking at these points, do
not use short radius elbows. Suction lines must be insulated with a minimum ¾” thick
insulation tubing to reduce heat pick -up.

www.welbilt.com 800-225-9916 9
Cleanliness:
Condensing units and evaporator coils are cleaned and dehydrated at the factory. The
condensing unit must remain closed and pressurized until the piping is complete and
final connections are ready to be made.
CAUTION
The maximum air exposure for dehydrated condensing units is 15 minutes. Systems
exposed longer than 15 minutes must have the compressor oil and drier filter replaced.
Leaving a system exposed to the atmosphere for more than 15 minutes can result in
premature system failure.
MISE EN GARDE
L’exposition maximale à l’air des groupes compresseurs-condenseurs
déshydratés est de 15 minutes. L’huile du compresseur et le filtre du
dessiccateur doivent être remplacés sur les systèmes qui ont été exposés à
l’air pendant plus de 15 minutes. L’exposition d’un système à l’atmosphère
pendant plus de 15 minutes peut avoir pour résultat une défaillance
prématurée du système.
Do not base mount vremove alve covers until work is ready to be performed. Ensure
that all refrigeration tubing is clean and dry prior to installation. Use only tubing cutters
when trimming tubing to the proper length. Do not use saws to cut tubing.
CAUTION
The use of saws to cut tubing can contaminate the system with copper chips causing
premature system failure.
MISE EN GARDE
L’utilisation de scies pour couper le tubage peut contaminer le système par
des copeaux de cuivre et causer une défaillance prématurée du système.
Brazing joints require a dry inert gas, typically nitrogen, be passed through the lines at a
low pressure to prevent scaling and oxidation. Use only silver solder brazing alloys.
Minimize the amount of flux to prevent internal contamination. Flux only the male
portion of the joint. Thoroughly clean fluxed joints after brazing.
CAUTION
Dry inert gas must be passed through the system while brazing to prevent scaling and
oxidation. Scaling and oxides can clog refrigeration components resulting in system
failure.

www.welbilt.com 800-225-9916 10
MISE EN GARDE
Le gaz sec inerte doit passer par le système pendant le brasage afin de
prévenir l’entartrage et l’oxydation. Le tartre et les oxydes peuvent bloquer
les éléments de réfrigération et causer une défaillance du système.
Pipe Supports:
All tubing should be supported in a least two locations (near the end of each tubing run).
Long runs will require additional support. As a guide, support 3/8” to 7/8” pipe every five
feet, 1-1/8” to 1-3/8” every seven feet, and 1-5/8” to 2-1/8” every ten feet. Do not leave
a corner unsupported when changing directions. Place supports within 2 feet of each
direction change. Piping that is attached to a vibrating object (such as a compressor or
compressor base) must be supported in a manner that will not restrict the movement of
the vibrating object. Rigid mounting will fatigue the tubing causing refrigerant leaks.
Oil Traps:
To ensure proper oil return to the compre a P type oil trap should be installed at ssor, -
the base of each suction riser of four feet or more. The suction trap must be the same
size as the suction line. Additional traps are necessary for long vertical risers. Add a
trap for each length of pipe (approximately 20 feet) to insure proper oil return. Suction
lines must slope ¼” per 10 feet toward the compressor. Install a suction line trap at the
evaporator outlet if the suction line rises to a point higher than the connection on the
evaporator.
C AUTION
Failure to properly install oil traps can prevent sufficient oil return to the compressor
resulting in premature compressor failure.
MISE EN GARDE
L’installation incorrecte des siphons d’huile peut empêcher un retour d’huile
suffisant au compresseur, entraînant une défaillance prématurée du
compresseur.

www.welbilt.com 800-225-9916 11
Pressure Regulating-Relief Valves:
WARNING
Do not defeat, cap, add piping to the outlet of the valve, or, attempt to
change the relief setting.
AVERTISSEMENT
Ne pas annuler, mettre un capuchon, ajouter de la tuyauterie à la prise de la
valve ou tenter de modifier le réglage de décharge.
Drain Lines:
Evaporator coil drain lines should be pitched a minimum of per foot to allow proper 1/2”
drainage and exit the walk-in as quickly as possible. Insulate and seal the drain line
where it passes through the wall. Copper drain line is required Freezer compartment .
drain lines must have heat tape wrapped around the copper drain line and must have
¾” thick insulation tubing Do not locate. drain -line P traps within the freezer space. Do
not reduce the drain line size. Locate a drain line P-trap outside of the cooler space.
Any outdoor P-traps exposed to low ambient temperatures should be wrapped with a
drain line heater (provide 20 watts of heat per foot of drain line at 0°F, 30 watts per foot
at -20°F. Freezer/cooler combo boxes can have one common drain line. However,
there must be a P-trap located between the freezer evaporator and the cooler
evaporator located inside the cooler compartment. The cooler compartment P-trap
should be located between the cooler evaporator and the external drain location.

www.welbilt.com 800-225-9916 12
P - re Charged lines and Quick Connects:
Route the suction and liquid line sets between the condensing unit and evaporator coil
following the piping guidelines identified in this manual. Remove the dust caps from the
quick connect fittings and verify that the o rings are intact. Wipe the coupli- ng seals and
threaded surfaces with a clean cloth to prevent contamination. Lubricate the threads
and o-rings with Polyol Ester oil. Thread the coupling halves together by hand to
ensure proper thread mating. Tighten with a wrench until the coupling bodies “bottom”
or until there is definite resistance. Tighten an additional ¼ turn to ensure proper brass-
to-brass seating. Once the system is opened and pressurized, check each fitting for
refrigerant leaks. If a leak is detected, tighten until the leak stops.
WARNING
Do not loosen and disconnect the quick connect fittings before reclaiming the refrigerant
and depressurizing the system. Disconnecting a pressurized system can result in
injury!

www.welbilt.com 800-225-9916 13
Pre-Charged lines and Quick Connects (continued):
AVERTISSEMENT
Ne pas desserrer et désaccoupler les raccords rapides avant de récupérer
le réfrigérant et de dépressuriser le système. La déconnexion d’un système
sous pression peut entraîner des blessures!
CAUTION
Quick connects are for one time use only. Once disconnected, the coupling cannot be
re-used. Refrigerant leaks will occur if the couplings -are re used resulting in poor
system performance.
MISE EN GARDE
Les raccords rapides ne sont prévus que pour un seul usage. Une fois
désaccouplés, ils ne peuvent plus être utilisés de nouveau. Des pertes de
réfrigérant se produiront si les raccords sont réutilisés, ayant pour résultat
un rendement médiocre du système.
Excess line set length should never be allowed to coil in the vertical position. Excess
line length should be laid flat on its side.

www.welbilt.com 800-225-9916 14
Leak Testing
After all connections are complete the refrigeration system must be tested for leaks.
Failure to perform a leak test can result in unsatisfactory system performance,
additional servicing and service costs, and possible system failure. Leak test should be
performed using an electronic leak detector. All joints and components, both factory
and field installed, should be thoroughly inspected for leaks. The system installation
must be leak free!
Leak Testing “PR” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
Leak Testing “PC” model systems:
Leave the service valves closed, the condensing unit is charged with refrigerant.
Ensure the solenoid valve is energized and open.
Add 50 psi refrigerant, then pressurize with dry nitrogen to the low side test
pressure identified on the unit rating label.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
Leak Testing “PCL” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Allow thirty minutes for refrigerant to reach all parts of the system.
Check all joints and components with an electronic leak detector.
If a leak is detected, relieve the pressure and/or reclaim the refrigerant and repair the
leak. If additional brazing is required, pass a dry inert gas (nitrogen) through the system
to prevent contamination. Reference page 1 of this manual for leaks located at quick 2
connects couplings. Retest the system as outlined above until no leaks are detected.
NOTE: refrigerant R448 is a blend and when leaks occur, it is unknown which
refrigerant blend or how much of it has escaped. If R448 refrigerant is simply
“topped off”, the new blend mixture may affect proper performance of the
system.
CAUTION
If a braze joint is detected leaking, dry inert gas must be passed through the system
while repairing the joint to prevent scaling and oxidation. Scaling and oxides can clog
refrigeration components resulting in system failure.

www.welbilt.com 800-225-9916 15
MISE EN GARDE
Si une fuite d’un joint de brasage a été détectée, le gaz inerte doit passer
par le système lors de la réparation du joint afin de prévenir l’entartrage et
l’oxydation du système. Le tartre et les oxydes peuvent bloquer les éléments
de réfrigération et causer une défaillance du système.
CAUTION
Always use the system specified refrigerant when pressuring to perform a leak test.
MISE EN GARDE
Utiliser toujours le réfrigérant du système précisé lors de la mise sous
pression dans le but de réaliser un essai de fuite.
System Evacuation
Evacuation of the refrigeration system is necessary to remove all air and moisture from
the system. A reliable rotary vacuum pump with an accurate deep vacuum gauge is
recommended. Do not use the system compressor as a vacuum pump and do not
operate the compressor while the system is under vacuum.
Evacuation of “PR” model systems:
Open both the liquid and suction service valves.
Ensure the solenoid valve is energized and open.
Connect vacuum pump to the liquid and suction service located on the valves
condensing unit.
Evacuate the system to 250 microns and maintain for a minimum of 4 hours.
Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.
Evacuation of “PC” model systems:
Leave the service valves closed, the condensing unit has been evacuated and is
charged with refrigerant.
Ensure the solenoid valve is energized and open.
Connect vacuum pump to the liquid and suction service valves. located on the
condensing unit.
Evacuate the system to 250 microns and maintain for a minimum of 4 hours.
Perform a vacuum decay test for a minimum of ten minutes to ensure the system
is leak free and dry.

www.welbilt.com 800-225-9916 16
Evacuation of “PCL” model systems:
“PCL” systems do not require evacuation.
CAUTION
Do not use the system compressor to evacuate the system. Do not start the
compressor while the system is under vacuum. This may damage to the compressor
and cause premature system failure.
MISE EN GARDE
Ne pas utiliser le compresseur du système pour vidanger celui-ci Ne pas
démarrer le compresseur pendant que le système est sous vide. Cela peut
endommager le compresseur et causer une défaillance prématurée du
système.
Refrigerant Charging
The refrigerant charge should be added to the system through the liquid line
service valve located on the condensing unit. Do not charge liquid refrigerant
into the suction service valve! The initial charge should be determined by weight
and sight glass indication. Start the system. If the condensing temperature is
105° F or greater, charge the system until the sight glass clears. If the
condensing unit temperature is below 105° F, reduce the condenser face surface
area to raise the discharge pressures above 105° F and to charge to a clear sight
glass. Return to a full condenser face area when charging is complete.
NOTE: PC & PCL refrigerant charge amounts are based on average ambient
operating temperatures across the United States. Any refrigerant amount added
or removed based on ambient operating temperatures is considered part of
normal maintenance and is not covered under warranty.
CAUTION
Do not charge liquid refrigerant into the suction service located on the condensing valve
unit. Do not overcharge the system. These conditions can permit liquid refrigerant to
enter the compressor and cause damage to internal components resulting in premature
system failure.
MISE EN GARDE
Ne pas charger le réfrigérant liquide dans le robinet d’aspiration de service.
Ne pas surcharger le système. Ces conditions peuvent permettre au
réfrigérant d’entrer dans le compresseur et de causer des dommages aux
composants internes, entraînant une défaillance prématurée du système.

www.welbilt.com 800-225-9916 17

www.welbilt.com 800-225-9916 18
Operational Start-Up
The first 2 – 4 hours of operation after initial start up is a critical time. Do not just start -
the system and leave. Pressure values, compressor and evaporator superheat, and
inspecting for excessive vibrations and loose connections are some of checks that must
be performed prior to leaving the system.
Pre-Start Checks:
Verify that all service valves are fully open.
Ensure that all refrigerant and electrical connections are tight.
Verify that the wiring and piping is properly routed and secured.
The compressor mounting bolts are properly adjusted (see compressor mounts
on page 18 ).
All fan motors and mounting brackets are tight.
The condensing unit base and evaporator coil are properly secured.
Compressor Mounts:
Hermetic Compressors ic compressor springs are mounted internally; check – hermet
the compressor mounting bolts to ensure the nuts have not become loose during
shipment.
Semi-Hermetic Compressors – most semi-hermetic compressors have external spring
mounts and are factory assembled. The following actions are required once the
condensing unit is installed and before system start- up:
Loosen the upper mounting nuts.
Remove the spring steel clips from the mounting springs.
Retighten the upper mounting nuts until the compressor can float on the springs
approximately 1/16” between the mounting nut and rubber grommet.

www.welbilt.com 800-225-9916 20
Start-Up Procedure (continued):
Operate the system for a minimum of two hours and perform checks of the following:
Check the compressor discharge and suction pressures to ensure they are in the
normal operating range.
Check the liquid line sight glass for proper refrigerant charge (based off of 105ºF
condenser coil).
Monitor the compressor oil level (semi hermetic compressors), add oil as necessary to -
keep the level at ¾ sight glass when idle and ½ sight glass when running.
Check the voltage and amperage at the compressor terminals. Voltage must be
within +10% or 5% of the rating indicted on the condensing unit name plate. On -
three phase compressors, verify there is a balanced load.
Check all fans on the evaporator coil and condensing unit to be sure they are
operational and turning in the correct direction.
Check the piping and electrical connections for vibration. Add supports and
strapping if needed.
Check the crankcase heater operation (if equipped).
Set the defrost control time and verify the defrost initiation settings. See pages
28 30- for additional details.
Set temperature control to desired temperature range.
Check the compressor and evaporator superheat (reference pages 21 23- ).
After all system checks have been checked, properly adjusted, and verified, replace all
Schrader caps, service valve caps, electrical box covers, housings, etc. File a copy of
this manual for future reference.
CAUTION
Failure to check and properly adjust compressor superheat can result in premature
system failure.
MISE EN GARDE
La vérification et le réglage inadéquats de la surchauffe du compresseur peut
entraîner une défaillance prématurée du système.

www.welbilt.com 800-225-9916 22
Evaporator Superheat:
Check the evaporator superheat once the has reached the desired temperature. walk-in
Generally, systems with a design temperature drop of 10°F should have an evaporator
superheat value of 6°-10°F on freezers and 8°-12°F on coolers for maximum efficiency.
To determine the evaporator superheat:
1. Measure the suction pressure at the evaporator outlet.
2. Convert the pressure to saturation temperature referencing a temperature-pressure
chart.
3. Measure the temperature of the suction line at the expansion valve bulb. Ensure
the bulb is mounted at the correct location on the suction tube.
4. Subtract the saturation temperature reading (step 2) from the measured temperature
(step 3). The difference is the evaporator superheat.
CAUTION
Minimum compressor superheat of 20°F may override these recommendations on
systems with short line runs.
MISE EN GARDE
Une surchauffe minimale de 20 °F peut écraser ces recommandations sur les
systèmes ayant de courtes conduites.
CAUTION
The condensing unit must have the discharge pressure above the equivalent 105°F
condensing pressure (reference refrigerant charging on page 16).
Temperature minus
pressure converted
to temperature
equals superheat
T emperature
P ressure
Determining Evaporator Superheat

www.welbilt.com 800-225-9916 23
Evaporator Superheat (continued):
MISE EN GARDE
La pression de décharge du groupe compresseur-condenseur doit être
supérieure à la pression de condensation équivalente de 105 °F (40,5 °C)
(faire référence au chargement du réfrigérant à la page 16).
CAUTION
Correct location and full contact of the expansion valve bulb is extremely important for
proper system performance.
MISE EN GARDE
L’emplacement correct et le plein contact du bulbe du détendeur sont
extrêmement importants pour assurer un bon rendement du système.

www.welbilt.com 800-225-9916 24
Thermostats
P/N 550005663 P/N 550005664
Air Defrost Evaporators Electric Defrost Evaporators
P/N 550005663 is used on all Air Defrost model evaporators and features a built in Air
Defrost time clock. default defrost settings are every 6 hours for 30 minutes. See The
pages 27-28 for default and custom defrost setting instructions.
P/N 550005664 is used on all Electric defrost model evaporators. See page 29 for
Electric Defroster Timer setting instructions.
NOTE: The 550005664 display will be blank during the electric defrost cycle.

www.welbilt.com 800-225-9916 25
Thermostats (continued)
• Access Setpoint mode by pressing and holding the button until
ts (Temperature setpoint) displays on the screen
• Use the up and down arrows to scroll through the available setpoints
• Press to view the current setting
• Use the up and down arrows to change the setpoint
• Press and hold the button to confirm each setpoint change
• Press the button to escape
Especificaciones del producto
Marca: | Kolpak |
Categoría: | Refrigerador |
Modelo: | Polar Pak QS6-066-CT |
¿Necesitas ayuda?
Si necesitas ayuda con Kolpak Polar Pak QS6-066-CT haz una pregunta a continuación y otros usuarios te responderán
Refrigerador Kolpak Manuales

27 Octubre 2024

27 Octubre 2024

1 Septiembre 2024

30 Agosto 2024

30 Agosto 2024

29 Agosto 2024

28 Agosto 2024

28 Agosto 2024

28 Agosto 2024

28 Agosto 2024
Refrigerador Manuales
- Refrigerador Candy
- Refrigerador Electrolux
- Refrigerador Samsung
- Refrigerador ATAG
- Refrigerador LG
- Refrigerador Bosch
- Refrigerador AEG
- Refrigerador IKEA
- Refrigerador Panasonic
- Refrigerador AEG Electrolux
- Refrigerador Bauknecht
- Refrigerador BEKO
- Refrigerador Delonghi
- Refrigerador Daewoo
- Refrigerador Etna
- Refrigerador Garmin
- Refrigerador Grundig
- Refrigerador Honeywell
- Refrigerador Indesit
- Refrigerador Inventum
- Refrigerador Kenwood
- Refrigerador Liebherr
- Refrigerador Miele
- Refrigerador Medion
- Refrigerador Siemens
- Refrigerador Toshiba
- Refrigerador Unold
- Refrigerador Whirlpool
- Refrigerador Yamaha
- Refrigerador Zanussi
- Refrigerador Zanker
- Refrigerador Adler
- Refrigerador Amica
- Refrigerador Airlux
- Refrigerador Aldi
- Refrigerador Amana
- Refrigerador Ardo
- Refrigerador Arcelik
- Refrigerador Asko
- Refrigerador Silverline
- Refrigerador Bartscher
- Refrigerador GE
- Refrigerador Orbegozo
- Refrigerador Salton
- Refrigerador Princess
- Refrigerador Sharp
- Refrigerador Techwood
- Refrigerador Fisher And Paykel
- Refrigerador Bertazzoni
- Refrigerador Lamona
- Refrigerador Klarstein
- Refrigerador Fagor
- Refrigerador Brandt
- Refrigerador Omega
- Refrigerador Severin
- Refrigerador Smeg
- Refrigerador Telefunken
- Refrigerador Gorenje
- Refrigerador Tricity Bendix
- Refrigerador Neff
- Refrigerador Palsonic
- Refrigerador Silvercrest
- Refrigerador Baumatic
- Refrigerador Hitachi
- Refrigerador Thomson
- Refrigerador Arthur Martin
- Refrigerador Hoover
- Refrigerador KitchenAid
- Refrigerador Tristar
- Refrigerador Domo
- Refrigerador Teka
- Refrigerador Trisa
- Refrigerador Nordland
- Refrigerador Progress
- Refrigerador Cata
- Refrigerador Pyle
- Refrigerador Gaggenau
- Refrigerador Hotpoint-Ariston
- Refrigerador Ignis
- Refrigerador Tomado
- Refrigerador Kernau
- Refrigerador Maytag
- Refrigerador Livoo
- Refrigerador Manta
- Refrigerador Thermador
- Refrigerador OK
- Refrigerador Hisense
- Refrigerador Hyundai
- Refrigerador Hanseatic
- Refrigerador Vox
- Refrigerador Cylinda
- Refrigerador Bellini
- Refrigerador Avanti
- Refrigerador Westinghouse
- Refrigerador Vestel
- Refrigerador ECG
- Refrigerador Moulinex
- Refrigerador Pelgrim
- Refrigerador Blomberg
- Refrigerador Melissa
- Refrigerador Magic Chef
- Refrigerador Swan
- Refrigerador Emerio
- Refrigerador RCA
- Refrigerador Russell Hobbs
- Refrigerador Elica
- Refrigerador Constructa
- Refrigerador BlueStar
- Refrigerador John Lewis
- Refrigerador Summit
- Refrigerador Hotpoint
- Refrigerador Midea
- Refrigerador De Dietrich
- Refrigerador Junker
- Refrigerador Cuisinart
- Refrigerador Blaupunkt
- Refrigerador Mabe
- Refrigerador Concept
- Refrigerador Gram
- Refrigerador Monogram
- Refrigerador Frigidaire
- Refrigerador Iberna
- Refrigerador Worx
- Refrigerador Svan
- Refrigerador Logik
- Refrigerador Danby
- Refrigerador Balay
- Refrigerador Valberg
- Refrigerador Stirling
- Refrigerador PKM
- Refrigerador Daikin
- Refrigerador Accucold
- Refrigerador Frilec
- Refrigerador Rosieres
- Refrigerador Salora
- Refrigerador Scholtes
- Refrigerador Profilo
- Refrigerador Thetford
- Refrigerador Berg
- Refrigerador CDA
- Refrigerador Finlux
- Refrigerador Castor
- Refrigerador Heinner
- Refrigerador Schneider
- Refrigerador Sanyo
- Refrigerador Kenmore
- Refrigerador Philco
- Refrigerador TCL
- Refrigerador Juno
- Refrigerador Nabo
- Refrigerador Guzzanti
- Refrigerador Defy
- Refrigerador Infiniton
- Refrigerador Mitsubishi
- Refrigerador Dometic
- Refrigerador Igloo
- Refrigerador Aspes
- Refrigerador Schaub Lorenz
- Refrigerador Dimplex
- Refrigerador DCG
- Refrigerador White Knight
- Refrigerador Sunny
- Refrigerador Orima
- Refrigerador Luxor
- Refrigerador Nordmende
- Refrigerador Husqvarna
- Refrigerador Koenic
- Refrigerador CaterCool
- Refrigerador Haier
- Refrigerador Rangemaster
- Refrigerador H.Koenig
- Refrigerador Boretti
- Refrigerador Haeger
- Refrigerador Perel
- Refrigerador Ariston Thermo
- Refrigerador Viking
- Refrigerador GOTIE
- Refrigerador Wolkenstein
- Refrigerador Hansa
- Refrigerador Polar
- Refrigerador Thor
- Refrigerador Kubo
- Refrigerador Benavent
- Refrigerador Costway
- Refrigerador Exquisit
- Refrigerador Elba
- Refrigerador Proline
- Refrigerador Euromaid
- Refrigerador Corberó
- Refrigerador Crosley
- Refrigerador WLA
- Refrigerador New Pol
- Refrigerador True
- Refrigerador Ardes
- Refrigerador Kelvinator
- Refrigerador ETA
- Refrigerador Element
- Refrigerador Mora
- Refrigerador Everglades
- Refrigerador Steel Cucine
- Refrigerador Zephyr
- Refrigerador Bomann
- Refrigerador Novy
- Refrigerador Zerowatt
- Refrigerador Kuppersbusch
- Refrigerador Continental Edison
- Refrigerador Jenn-Air
- Refrigerador Limit
- Refrigerador Freggia
- Refrigerador Carpigiani
- Refrigerador Insignia
- Refrigerador Listo
- Refrigerador Edesa
- Refrigerador Milectric
- Refrigerador Mobicool
- Refrigerador Leonard
- Refrigerador Osprey
- Refrigerador Franke
- Refrigerador New World
- Refrigerador AYA
- Refrigerador Leisure
- Refrigerador Camry
- Refrigerador Fridgemaster
- Refrigerador Nodor
- Refrigerador WhiteLine
- Refrigerador Blaze
- Refrigerador Jocel
- Refrigerador Glem Gas
- Refrigerador Viva
- Refrigerador Bifinett
- Refrigerador Respekta
- Refrigerador U-Line
- Refrigerador M-System
- Refrigerador Changhong
- Refrigerador Electra
- Refrigerador Primo
- Refrigerador Rex
- Refrigerador Comfee
- Refrigerador Meireles
- Refrigerador Dacor
- Refrigerador Saro
- Refrigerador Scandomestic
- Refrigerador V-Zug
- Refrigerador Godrej
- Refrigerador Sauber
- Refrigerador Chiq
- Refrigerador MPM
- Refrigerador Matrix
- Refrigerador Zenith
- Refrigerador Becken
- Refrigerador Esatto
- Refrigerador Belling
- Refrigerador BeefEater
- Refrigerador Marvel
- Refrigerador Juno-electrolux
- Refrigerador Napoleon
- Refrigerador Waeco
- Refrigerador Essentiel B
- Refrigerador Mestic
- Refrigerador Privileg
- Refrigerador ProfiCook
- Refrigerador Vivax
- Refrigerador Stoves
- Refrigerador Edy
- Refrigerador Nevir
- Refrigerador Ilve
- Refrigerador Edgestar
- Refrigerador Coyote
- Refrigerador Gys
- Refrigerador Parmco
- Refrigerador G3 Ferrari
- Refrigerador Caple
- Refrigerador Eurotech
- Refrigerador Gourmetmaxx
- Refrigerador Avintage
- Refrigerador Equator
- Refrigerador Vestfrost
- Refrigerador Kunft
- Refrigerador Caso
- Refrigerador Upo
- Refrigerador Hestan
- Refrigerador Rommer
- Refrigerador Heller
- Refrigerador Lavorwash
- Refrigerador Climadiff
- Refrigerador SIBIR
- Refrigerador Scancool
- Refrigerador Veripart
- Refrigerador Brandy Best
- Refrigerador Sub-Zero
- Refrigerador Lynx
- Refrigerador Optimum
- Refrigerador Flavel
- Refrigerador Furrion
- Refrigerador Cecotec
- Refrigerador Bluesky
- Refrigerador Tecnolux
- Refrigerador Whynter
- Refrigerador Icecool
- Refrigerador Cobal
- Refrigerador Chefman
- Refrigerador Kalorik
- Refrigerador Mercury
- Refrigerador Marynen
- Refrigerador Gardenline
- Refrigerador La Germania
- Refrigerador Lec
- Refrigerador Oranier
- Refrigerador Galanz
- Refrigerador Tisira
- Refrigerador Turbo Air
- Refrigerador Orava
- Refrigerador CombiSteel
- Refrigerador Khind
- Refrigerador Husky
- Refrigerador Foster
- Refrigerador Gastro-Cool
- Refrigerador Hoshizaki
- Refrigerador Wells
- Refrigerador Paulmann
- Refrigerador NewAir
- Refrigerador Kucht
- Refrigerador Avantco
- Refrigerador Kogan
- Refrigerador Norlake
- Refrigerador Arctic Air
- Refrigerador Gamko
- Refrigerador Signature
- Refrigerador Snaigė
- Refrigerador Romo
- Refrigerador Merax
- Refrigerador Sam Cook
- Refrigerador Consul
- Refrigerador Blucher
- Refrigerador Silhouette
- Refrigerador ColdTech
- Refrigerador ONYX
- Refrigerador Magic Cool
- Refrigerador JennAir
- Refrigerador Rhino
- Refrigerador LERAN
- Refrigerador Le Chai
- Refrigerador IOMABE
- Refrigerador APW Wyott
- Refrigerador General Electric
- Refrigerador SPT
- Refrigerador Hatco
- Refrigerador Fulgor Milano
- Refrigerador High One
- Refrigerador Les Petits Champs
- Refrigerador Airflo
- Refrigerador Moa
- Refrigerador Master-Bilt
- Refrigerador Hydra Kool
- Refrigerador Linarie
- Refrigerador XO
- Refrigerador Dunavox
- Refrigerador Arktic
- Refrigerador Curtiss
- Refrigerador Nemco
- Refrigerador Beverage-Air
- Refrigerador Vedette
- Refrigerador Winia
- Refrigerador Delfield
- Refrigerador Traulsen
- Refrigerador Artusi
- Refrigerador Alto-Shaam
- Refrigerador Simfer
- Refrigerador Federal
- Refrigerador NEO Tools
- Refrigerador Structural Concepts
- Refrigerador Vinata
- Refrigerador LeCavist
- Refrigerador Sôlt
- Refrigerador Avallon
- Refrigerador Emperor's Select
- Refrigerador Ravanson
- Refrigerador Fisher Paykel
- Refrigerador Wine Klima
- Refrigerador Marbor
- Refrigerador Create
- Refrigerador Vintec
- Refrigerador Hiberg
- Refrigerador Engel
- Refrigerador Americana
- Refrigerador Koolatron
- Refrigerador Cosmo
- Refrigerador Adventure Kings
- Refrigerador Lemair
- Refrigerador EvaKool
- Refrigerador FAURE
- Refrigerador Coldtainer
- Refrigerador Orien
- Refrigerador Enofrigo
- Refrigerador BSK
- Refrigerador United
- Refrigerador Techfrost
- Refrigerador Irinox
- Refrigerador DCS
- Refrigerador Azure
- Refrigerador IFB
- Refrigerador Gecko
- Refrigerador Bromic
- Refrigerador Kuhla
- Refrigerador Adora
- Refrigerador Newpol
- Refrigerador Brastemp
- Refrigerador Royal Catering
- Refrigerador SEIKI
- Refrigerador Haden
- Refrigerador FrigeluX
- Refrigerador Cookology
- Refrigerador Perlick
- Refrigerador Sedona
- Refrigerador Atosa
- Refrigerador Cool Head
- Refrigerador MBM
- Refrigerador Gladiator
- Refrigerador Vinotemp
- Refrigerador Norpole
- Refrigerador Euro Appliances
- Refrigerador Fhiaba
- Refrigerador Gasmate
- Refrigerador Arthur Martin-Electrolux
- Refrigerador Triomph
- Refrigerador Schmick
- Refrigerador Dellware
- Refrigerador Elektra Bregenz
- Refrigerador InAlto
- Refrigerador HABAU
- Refrigerador Cooluli
- Refrigerador Electroline
- Refrigerador Tuscany
- Refrigerador Café
- Refrigerador TESLA Electronics
- Refrigerador Smart Brand
- Refrigerador Brass Monkey
- Refrigerador Premium Levella
- Refrigerador Wisberg
- Refrigerador Waltham
- Refrigerador DAYA
- Refrigerador Lec Medical
- Refrigerador Sangiorgio
- Refrigerador Kalamazoo
- Refrigerador Yolco
- Refrigerador Aconatic
- Refrigerador Kluge
- Refrigerador Hoover-Grepa
- Refrigerador Coca-Cola
- Refrigerador Acros
- Refrigerador HomeCraft
- Refrigerador Koldfront
- Refrigerador Eqtemp
- Refrigerador Landmark
- Refrigerador Pitsos
Últimos Refrigerador Manuales

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024

27 Octubre 2024