Mach Power UPS-TRI30K Manual de Usario

Lee a continuación 📖 el manual en español para Mach Power UPS-TRI30K (4 páginas) en la categoría No categorizado. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/4
UPS ONLINE THREE PHASE
10KVA ~ 30KVA
DATASHEET
MOELLO: UPS-TRI10K / UPS-TRI20K / UPS-TRI30K
FEATURES
High frequency and true online double-conversion
DSP digitai contrai technology
Input power factor correction (PFC)
Wide input voltage range (190V - 485V)
Output power factor 0.9
Excellent load-carrying capability, linear derating between 50% and 100% load at 190 - 277 Vac
Optimized battery configuration: 192V / 240V
Cold start
Auto sensing frequency
ECO mode operation for energy saving
50 / 60Hz frequency conversion mode
Selectable output voltage via LCD
Selectable battery shutdown voltage (EOD) via LCD
Power-on self test
Advanced battery management (ABM)
Short circuit and overload protection
Automatic charging in OFF mode
Auto control fan speed when loads varies
Dual input
Advanced quick charge technology, charging speed is increased double
Configurable transfer time from battery to mains power, reducing the impact on grid or generator
Automatic startup/shutdown function (optional), automatic transfer to bypass at light load, automatic
restart at acting load; energy-saving and enviranment-friendly
Standard USB communication port
Standard emergency power off (EPO)
Standard maintenance bypass
Optional extension battery bank
Optional RS465 I SNMP I AS400 communication port
Optional N+X redundancy parallel up to 6 units
Optional battery temperature compensation
| DATASHEET
MAINS INPUT
DC INPUT
OUTPUT
FAN
INTELLIGENT SLOT 2
(SNMP / AS400 / RS485 OPTIONAL)
INTELLIGENT SLOT 1
(SNMP / AS400 / RS485 OPTIONAL)
BYPASS INPUT
MAINTENANCE
BYPASS
MAINS INPUT
BYPASS
BYPASS INPUT
BREAKER
PARALLEL CARD
(OPTIONAL)
USB EPO
BATTERY
TEMPERATURE
COMPENSATION
SPECIFICATION
UPS-TRI10K
10KVA / 9KW
40 x 9Ah
MODEL
Capacity
INPUT
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Total harmonic distortion THDI
Bypass voltage range
OUTPUT
Voltage
Voltage regulation
Frequency
Waveform
Crest factor
Total harmonic distortion THDV
Transfer time
lnverter overload capability
Bypass overload capability
BATTERIES
DC voltage
lnbuilt battery space *
Typical recharge time
SYSTEM
Efficiency
Display
Alarm
UPS-TRI20K
20KVA / 18KW
360 V /380V /400 V/ 415 Vac
277 - 485 Vac (no derating)
190 - 277Vac (linear derating between 50% and 100% load)
50 / 60 Hz (auto-sense)
40 ~ 70 Hz
0.99
5%
-40% - + 15% (settable)
360 V/ 360 V/ 400 V/ 415 Vac (settable)
±1%
Synchronized with utility in mains mode; 50 / 60 ± 0.1Hz in battery mode
Sinusoidal
3:1
2% (linear load); 5% (non-linear load)
Mains mode to battery mode: 0ms; lnverter mode to bypass mode: 0ms
102% - 125%: transfer to bypass in 10 mins;
125% - 150%: transfer to bypass in 1 min;
> 150%: transfer to bypass in 0.5 s
240 Vdc; Long time model: 192 Vdc
40 x 7/9Ah
4 Hours
93%, ECO mode 96%
LCD+ LED
Battery mode, low battery, fans fault etc.
UPS-TRI30K
30KVA / 27KW
60 x 7/9Ah
* battery not included
| DATASHEET

Especificaciones del producto

Marca: Mach Power
Categoría: No categorizado
Modelo: UPS-TRI30K

¿Necesitas ayuda?

Si necesitas ayuda con Mach Power UPS-TRI30K haz una pregunta a continuación y otros usuarios te responderán




No categorizado Mach Power Manuales

No categorizado Manuales

Últimos No categorizado Manuales