1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
%HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUHDVWKH\LQFOXGHLPSRUWDQWLWHPVUHODWHGWRVDIHW\
• After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
1-2. SELECTING THE INSTALLATION LOCATION
1-3. SPECIFICATIONS
CAUTION
&RXOGOHDGWRVHULRXVLQMXU\LQSDUWLFXODUHQYLURQPHQWVZKHQRSHUDWHGLQFRUUHFWO\
Required Tools for Installation
Phillips screwdriver
Level
Scale
8WLOLW\NQLIHRUVFLVVRUV
65 mm hole saw
Torque wrench
Wrench (or spanner)
PPKH[DJRQDOZUHQFK
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer
N
Do not install the unit by yourself (user).
,QFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHRUHOHFWULFVKRFNLQMXU\
due to the unit falling, or leakage of water. Consult the dealer
IURPZKRP\RXSXUFKDVHGWKHXQLWRUDTXDOL¿HGLQVWDOOHU
N
Perform the installation securely referring to the installa-
tion manual.
,QFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHRUHOHFWULFVKRFNLQMXU\
due to the unit falling, or leakage of water.
N
Install the unit securely in a place which can bear the
weight of the unit.
If the installation location cannot bear the weight of the unit,
WKHXQLWFRXOGIDOOFDXVLQJLQMXU\
N
Perform electrical work according to the installation
manual and be sure to use an exclusive circuit. Do not
connect other electrical appliances to the circuit.
,I WKH FDSDFLW\ RI WKH SRZHU FLUFXLW LV LQVXI¿FLHQW RU WKHUH LV
LQFRPSOHWHHOHFWULFDOZRUNLWFRXOGUHVXOWLQD¿UHRUDQHOHFWULF
shock.
N
Earth the unit correctly.
Do not connect the earth to a gas pipe, water pipe, lightning
rod or telephone earth. Defective earthing could cause electric
shock.
N
Do not damage the wires by applying excessive pressure
with parts or screws.
'DPDJHGZLUHVFRXOGFDXVH¿UH
N
Be sure to cut off the main power in case of setting up the
indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
N
8VHWKHVSHFL¿HGZLUHVWRFRQQHFWWKHLQGRRUDQGRXWGRRU
XQLWVVHFXUHO\DQGDWWDFKWKHZLUHV¿UPO\WRWKHWHUPLQDO
block connecting sections so the stress of the wires is
not applied to the sections.
,QFRPSOHWHFRQQHFWLQJDQGVHFXULQJFRXOGFDXVH¿UH
N
'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHLQÀDPPDEOHJDV
may leak.
If gas leaks and accumulates in the area around the unit, it
FRXOGFDXVHDQH[SORVLRQ
N
Do not use intermediate connection of the power cord or
the extension cord and do not connect many devices to
one AC outlet.
,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFNGXHWRGHIHFWLYHFRQ-
WDFW GHIHFWLYH LQVXODWLRQ H[FHHGLQJ WKH SHUPLVVLEOH FXUUHQW
etc.
N
%HVXUHWRXVHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWVIRU
the installation work.
7KHXVHRIGHIHFWLYHSDUWVFRXOGFDXVHDQLQMXU\RUOHDNDJHRI
ZDWHUGXHWRD¿UHDQHOHFWULFVKRFNWKHXQLWIDOOLQJHWF
N
When plugging the power supply plug into the outlet,
make sure that there is no dust, clogging, or loose parts
in both the outlet and the plug. Make sure that the power
supply plug is pushed completely into the outlet.
,I WKHUHLV GXVWFORJJLQJRUORRVHSDUWVRQWKHSRZHUVXSSO\
SOXJRUWKHRXWOHWLWFRXOGFDXVHHOHFWULFVKRFNRU¿UH,IORRVH
SDUWVDUHIRXQGRQWKHSRZHUVXSSO\SOXJUHSODFHLW
N
Attach the electrical cover to the indoor unit and the
service panel to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service
SDQHORI WKH RXWGRRU XQLW DUH QRW DWWDFKHG VHFXUHO\ LW FRXOG
UHVXOWLQD¿UHRUDQHOHFWULFVKRFNGXHWRGXVWZDWHUHWF
N
When installing or relocating the unit, make sure that no
VXEVWDQFHRWKHUWKDQWKHVSHFL¿HGUHIULJHUDQW5$
enters the refrigerant circuit.
$Q\SUHVHQFHRIIRUHLJQVXEVWDQFHVXFK DVDLUFDQFDXVHDE-
QRUPDOSUHVVXUHULVHRUDQH[SORVLRQ
N
Do not discharge the refrigerant into the atmosphere. If
refrigerant leaks during installation, ventilate the room.
,IUHIULJHUDQWFRPHVLQFRQWDFWZLWKD¿UHKDUPIXOJDVFRXOGEH
generated.
N
Check that the refrigerant gas does not leak after installa-
tion has been completed.
If refrigerant gas leaks indoors, and comes into contact with
WKHÀDPH RI D IDQ KHDWHUVSDFH KHDWHU VWRYH HWF KDUPIXO
substances will be generated.
N
Use appropriate tools and piping materials for installa-
tion.
The pressure of R410A is 1.6 times more than R22. Not us-
ing appropriate tools or materials and incomplete installation
FRXOGFDXVHWKHSLSHVWREXUVWRULQMXU\
N
When pumping down the refrigerant, stop the compressor
before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the compres-
sor is running and the stop valve is open, air could be drawn
LQ DQG WKH SUHVVXUH LQ WKH UHIULJHUDWLRQ F\FOH FRXOG EHFRPH
DEQRUPDOO\KLJK7KLVFRXOGFDXVHWKHSLSHVWREXUVWRULQMXU\
N
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
If the compressor is started before the refrigerant pipes are
connected and when the stop valve is open, air could be
GUDZQLQDQGWKHSUHVVXUHLQWKHUHIULJHUDWLRQF\FOHFRXOGEH-
FRPHDEQRUPDOO\KLJK7KLVFRXOGFDXVHWKHSLSHVWREXUVWRU
LQMXU\
N )DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQ
this manual.
,IIDVWHQHGWRRWLJKWDÀDUHQXWPD\ EUHDNDIWHUD ORQJSHULRG
and cause refrigerant leakage.
N
The unit shall be installed in accordance with national
wiring regulations.
N
Install an earth leakage breaker depending on the installa-
tion place.
If an earth leakage breaker is not installed, it could cause
electric shock.
N
Perform the drainage/piping work securely according to
the installation manual.
If there is defect in the drainage/piping work, water could drop
from the unit, soaking and damaging household goods.
N
'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKH
outdoor unit.
7KLVFRXOGFDXVHLQMXU\
N
Do not install the outdoor unit where small animals may
live.
If small animals enter and touch the electric parts inside the
unit, it could cause a malfunction, smoke emission, or fire.
Also, advise user to keep the area around the unit clean.
INDOOR UNIT
:KHUHDLUÀRZLVQRWEORFNHG
• Where cool air spreads over the entire room.
• Rigid wall without vibration.
:KHUHLWLVQRWH[SRVHGWRGLUHFWVXQVKLQH
:KHUHHDVLO\GUDLQHG
$WDGLVWDQFHPRUPRUHDZD\IURP\RXU79DQGUDGLR
2SHUDWLRQRIWKHDLUFRQGLWLRQHUPD\ LQWHUIHUHZLWKUDGLR
RU79UHFHSWLRQ$QDPSOL¿HUPD\ EHUHTXLUHGIRUWKHDI-
fected device.
,QDSODFHDVIDUDZD\DVSRVVLEOHIURPÀXRUHVFHQWDQG
incandescent lights (so the infrared remote control can
RSHUDWHWKHDLUFRQGLWLRQHUQRUPDOO\
:KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\
REMOTE CONTROLLER
:KHUHLWLVHDV\WRRSHUDWHDQGHDVLO\YLVLEOH
• Where children cannot touch it.
6HOHFWDSRVLWLRQDERXWPDERYHWKHÀRRUDQGFKHFN
WKDW VLJQDOV IURP WKH UHPRWH FRQWUROOHU DUH VXUHO\ UH-
FHLYHG E\ WKH LQGRRU XQLW IURP WKDW SRVLWLRQ µEHHS¶ RU
µEHHSEHHS¶UHFHLYLQJWRQHVRXQGV$IWHUWKDWDWWDFKUH-
mote controller holder to a pillar or wall and install wire-
less remote controller.
Note:
,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHG
WKHVLJQDOIURPWKHZLUHOHVVUHPRWHFRQWUROOHUPD\QRWEH
received.
OUTDOOR UNIT
:KHUHLWLVQRWH[SRVHGWRVWURQJZLQG
:KHUHDLUÀRZLVJRRGDQGGXVWOHVV
• Where rain or direct sunlight can be avoided as much as
possible.
:KHUHQHLJKERXUVDUHQRWDQQR\HGE\ RSHUDWLRQVRXQG
or hot air.
• Where rigid wall or support is available to prevent the
increase of operation sound or vibration.
• Where there is no risk of combustible gas leakage.
• When installing the unit at a high level, be sure to secure
the unit legs.
:KHUHLWLVDWOHDVWPDZD\IURPWKHDQWHQQDRI79VHW
RUUDGLR2SHUDWLRQRIWKHDLUFRQGLWLRQHUPD\LQWHUIHUHZLWK
radio or TV reception in areas where reception is weak.
$QDPSOL¿HUPD\EHUHTXLUHGIRUWKHDIIHFWHGGHYLFH
,QVWDOOWKHXQLWKRUL]RQWDOO\
3OHDVH LQVWDOO LW LQ DQ DUHD QRW DIIHFWHG E\ VQRZIDOO RU
EORZLQJVQRZ,QDUHDVZLWKKHDY\VQRZSOHDVHLQVWDOOD
FDQRS\DSHGHVWDODQGRUVRPHEDIÀHERDUGV
Note:
It is advisable to make a piping loop near outdoor unit so as
to reduce vibration transmitted from there.
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2
8VH ZLUHV LQ FRQIRUPLW\ ZLWK GHVLJQ ,(& 7KH XQLW
shall be installed in accordance with national wiring regulations.
*3 Never use pipes with thickness less than specified. The
SUHVVXUHUHVLVWDQFHZLOOEHLQVXI¿FLHQW
8VHDFRSSHUSLSHRUDFRSSHUDOOR\VHDPOHVVSLSH
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
,I SLSH OHQJWK H[FHHGV P DGGLWLRQDO UHIULJHUDQW 5$
charge is required. (No additional charge is required for
pipe length less than 7 m.)
Additional refrigerant = A × (pipe length (m) - 5)
*8 Insulation material : Heat resisting foam plastic 0.045
VSHFL¿FJUDYLW\
%HVXUHWRXVHWKHLQVXODWLRQRIVSHFL¿HGWKLFNQHVV([FHV-
VLYHWKLFNQHVVPD\FDXVHLQFRUUHFWLQVWDOODWLRQRIWKHLQGRRU
XQLWDQGLQVXI¿FLHQWWKLFNQHVVPD\FDXVHGHZGULSSDJH
Note:
When operating the air conditioner in low outside tempera-
ture, be sure to follow the instructions described below.
• Never install the outdoor unit in a place where its air
LQOHWRXWOHWVLGHPD\EHH[SRVHGGLUHFWO\WRZLQG
7R SUHYHQW H[SRVXUH WR ZLQG LQVWDOO WKH RXWGRRU XQLW
with its air inlet side facing the wall.
•
7RSUHYHQWH[SRVXUHWRZLQGLWLVUHFRPPHQGHGWRLQVWDOO
DEDIÀHERDUGRQWKHDLURXWOHWVLGHRIWKHRXWGRRUXQLW
Avoid the following places for installation where air condi-
tioner trouble is liable to occur.
:KHUHÀDPPDEOHJDVFRXOGOHDN
• Where there is much machine oil.
6DOW\SODFHVVXFKDVWKHVHDVLGH
:KHUHVXO¿GHJDVLVJHQHUDWHGVXFKDVDKRWVSULQJ
:KHUHWKHUHLVKLJKIUHTXHQF\RUZLUHOHVVHTXLSPHQW
WARNING &RXOGOHDGWRGHDWKVHULRXVLQMXU\HWF
SG79Y970H10
SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
ENGLISH
Model names are indicated in 1-3.
When installing multi units, refer to
the installation manual of the multi
unit for outdoor unit installation.
Model 3RZHUVXSSO\ :LUHVSHFL¿FDWLRQV Pipe size
(thickness *3, *4)
Indoor unit Outdoor unit Rated
Voltage )UHTXHQF\ Breaker
FDSDFLW\
3RZHUVXSSO\
3-core
Indoor/outdoor
connecting wire
Gas / Liquid
MSZ-FD25VA(S)
MUZ-FD25VAH-E1
230 V 50 Hz
12 A 1.5 mm2
4-core
1.0 mm2
ø9.52 / 6.35 mm
(0.8 mm)
MUZ-FD25VAH-E2 10 A 1.5 mm2
MUZ-FD25VABH
MUZ-FD25VA 10 A 1.0 mm2
MSZ-FD35VA(S) MUZ-FD35VA(B)H 12 A 1.5 mm2
MUZ-FD35VA 10 A 1.0 mm2
Pipe length and height difference
0D[SLSHOHQJWK 20 m
0D[KHLJKWGLIIHUHQFH 12 m
0D[QXPEHURIEHQGV 10
Refrigerant adjustment A *7 30 g/m
Insulation thickness *8, *9
8 mm
84 mm
or more
84 mm
or more
100 mm
or more
350 mm
or more
100 mm
or more
60 mm or more/
142.5 mm or more for
left and left back piping
(using spacer)
100 mm
or more
200 mm
or more
7 mm or more
1-4. INSTALLATION DIAGRAM
2-1. FIXING OF INSTALLATION PLATE
)LQGDVWUXFWXUDOPDWHULDOVXFKDVDVWXGLQWKHZDOODQG¿[LQVWDOODWLRQSODWHKRUL-
]RQWDOO\ZLWK¿[LQJVFUHZV
7R SUHYHQW LQVWDOODWLRQ SODWH IURP YLEUDWLQJ EH VXUH WR LQVWDOO WKH ¿[LQJ VFUHZV LQ
WKH KROHV LQGLFDWHG LQ WKH LOOXVWUDWLRQ )RU DGGHG VXSSRUW ¿[LQJ VFUHZV PD\ DOVR EH
installed in other holes.
• When bolts recessed in the concrete wall are to be utilized, secure installation plate (1)
using 11 × 20 · 11 × 26 oval hole (450 mm pitch).
• If the recessed bolt is too long, change it for a shorter one available in the market.
2-2. WALL HOLE DRILLING
1) Determine the wall hole position.
2) Drill a ø 65 mm hole. The outdoor side should be
5 to 7 mm lower than the indoor side.
3) Insert wall hole sleeve (C).
2-3. CONNECTING WIRES FOR INDOOR UNIT
You can connect indoor/outdoor lead wire without removing the front panel.
5HPRYHFRUQHUER[
2) Remove VA clamp.
3URFHVVWKHHQGRIHDUWKZLUHDQGFRQQHFWLWWRWKHHDUWKWHUPLQDORIHOHFWULFDOSDUWVER[
3URFHVVWKHHQGRILQGRRURXWGRRUXQLWFRQQHFWLQJZLUH$DQG¿[LWWR WHUPLQDOEORFN
%HFDUHIXOQRWWRPDNHPLVZLULQJ)L[WKHZLUHWRWKHWHUPLQDOEORFNVHFXUHO\VRWKDWQR
SDUWRILWV FRUHLV DSSHDUHGDQGQRH[WHUQDOIRUFH LVFRQYH\HG WRWKHFRQQHFWLQJVHF-
tion of the terminal block.
)LUPO\WLJKWHQWKHWHUPLQDOVFUHZVWRSUHYHQWWKHPIURPORRVHQLQJ$IWHUWLJKWHQLQJSXOO
WKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH
6) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA clamp.
1HYHUIDLOWRKRRNWKHULJKWFODZRIWKH9$FODPS$WWDFKWKH9$FODPSVHFXUHO\
5HLQVWDOOFRUQHUER[
2-4. PIPE FORMING AND DRAIN PIPING
Pipe Forming
• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not heaved or snaked.
'RQRWSXOOWKHKRVHZKHQDSSO\LQJWKHWDSH
• When the drain hose passes the room, be sure to wrap
insulation material (obtainable at a store) around it.
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate 1
(2) ,QVWDOODWLRQSODWH¿[LQJVFUHZ
4 × 25 mm 5
(3) Remote controller holder 1
(4) )L[LQJVFUHZIRU × 16 mm
(Black) 2
(5) 2%DWWHU\$$$IRU
(6) Wireless remote controller 1
(7) Felt tape
(For left or left-rear piping) 1
(8) 13ODVPDDQWLDOOHUJ\HQ]\PH¿OWHU
(9) 13ODVPDGHRGRUL]LQJ¿OWHU
<Outdoor unit>
(
10
)'UDLQVRFNHW9$W\SHRQO\ 1
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire* 1
(B) 1([WHQVLRQSLSH
(C) Wall hole sleeve 1
(D) Wall hole cover 1
(E) 2 to 53LSH¿[LQJEDQG
(F) 2 to 5)L[LQJVFUHZIRU(îPP
(G) Piping tape 1
(H) 13XWW\
(I)
Drain hose
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
1 or 2
(J) Refrigeration oil 1
(K) 13RZHUVXSSO\FRUG
Air inlet
Air outlet
Outdoor unit installation
8QLWVVKRXOGEHLQVWDOOHGE\OLFHQVHGFRQWUDFWRU
according to local code requirements.
Indoor terminal block
Indoor/outdoor unit
connecting wire (A)
Outdoor terminal block
Earth wire
JUHHQ\HOORZ
• Make earth wire a little longer than
others. (More than 55 mm)
)RUIXWXUHVHUYLFLQJJLYHH[WUDOHQJWK
to the connecting wires.
Liquid pipe
Gas pipe
Felt tape (7)
Indoor/outdoor unit
connecting wire (A)
Piping tape (G)
Indoor unit
Wall hole
sleeve (C)
Cut off the
H[WUDOHQJWK 3LSH¿[LQJEDQG
(E)
Be sure to use wall hole
sleeve (C) to prevent
indoor/outdoor connecting
wire (A) from contacting
metal parts in the wall and
WRSUHYHQWGDPDJHE\
rodents in case the wall is
hollow.
Wall hole cover (D)
Seal the wall hole
JDSZLWKSXWW\+
)L[WKHSLSHWRZDOO
ZLWKSLSH¿[LQJ
band (E).
)L[LQJVFUHZ
(F)
$IWHUWKHOHDNWHVWDSSO\
LQVXODWLQJPDWHULDOWLJKWO\
so that there is no gap.
When the piping is to be
attached to a wall contain-
ing metals (tin plated) or
metal netting, use a chemi-
FDOO\WUHDWHGZRRGHQSLHFH
20 mm or thicker between
the wall and the piping or
wrap 7 to 8 turns of insula-
WLRQYLQ\OWDSHDURXQGWKH
piping.
7RXVHH[LVWLQJSLSLQJSHU-
form COOL operation for
30 minutes and pump down
before removing the old air
FRQGLWLRQHU5HPDNHÀDUH
according to the dimension
for new refrigerant.
2. INDOOR UNIT INSTALLATION
2-10 mm × 21 mm slot
Drain piping for outdoor unit
<VA type only>
• Provide drain piping before indoor
and outdoor piping connection.
• Connect drain hose (I) I.D.15 mm
as shown in the illustration.
• Make sure to provide drain pip-
LQJ ZLWK D GRZQKLOO JUDGH IRU HDV\
GUDLQÀRZ
Note:
Do not use drain socket (10) in cold
UHJLRQV'UDLQPD\IUHH]HDQGPDNHWKHIDQVWRS
(10) (I)
Level
* Note:
Place indoor/outdoor unit connecting wire (A)
DQGSRZHUVXSSO\FRUG.DWOHDVWPDZD\
from the TV antenna wire.
Wall
Outdoor
side
$SSHDUDQFHRIWKHRXWGRRUXQLWPD\GLIIHUIURPVRPH
models.
800 mm
500 mm
150
mm
40 mm
344.5 mm
285 mm
304-325 mm
Installation plate (1)
Plumb
Align the plumb
line with the
mark .
Center of
ø 65 mm hole
84 mm or
more
84 mm or
more
Bind the line to the center hole.
60 mm or more
142.5 mm or more for left and left
back piping (using spacer)
Ceiling
Wall
Wall
)L[LQJVFUHZ
* Same for left hole.
Insert
the
scale. *
Align the
scale with
the line. *
100 mm
Terminal block )L[LQJ
screw
Indoor/outdoor unit
connecting wire (A)
VA clamp
Lead wire
Corner
ER[
25 mm
15 mm
15 mm
35 mm
Left or left-rear piping
Note:
Be sure to reattach the drain
hose and the drain cap in case
of left or left-rear piping.
Otherwise, it could cause drops
of water to drip down from the
drain hose.
1) Put the refrigerant piping and the drain hose together,
WKHQ¿UPO\DSSO\IHOWWDSHIURPWKHHQG
Felt tape (7) overlap width should be 1/3 the tape
width. Use a bandage stopper at the end of felt tape (7).
2) Pull out the drain cap at the rear right of the indoor unit.
(Fig. 1)
+ROGWKHFRQYH[VHFWLRQDWWKHHQGDQGSXOOWKH
drain cap.
3) Pull out the drain hose at the rear left of the indoor unit.
(Fig. 2)
+ROGWKHFODZPDUNHGE\WKHDUURZVDQGSXOORXWWKH
drain hose forward.
4) Put the drain cap into the section to which the drain
hose is to be attached at the rear of the indoor unit.
(Fig. 3)
• Insert not sharp-edged tools such as screwdrivers
into the hole at the end of the cap and insert the cap
IXOO\LQWRWKHGUDLQSDQ
,QVHUWWKHGUDLQKRVHIXOO\LQWRWKHGUDLQSDQDWWKHUHDU
right of the indoor unit. (Fig. 4)
&KHFNLIWKHKRVHLVKRRNHGVHFXUHO\WRWKHSURMHF-
tion of its inserting part at the drain pan.
6) Insert the drain hose into wall hole sleeve (C), and
hook the upper part of indoor unit on installation plate
7KHQPRYHWKHLQGRRUXQLWFRPSOHWHO\WRWKHOHIWLQ
order to make placing the piping in the back space of
the unit easier.
&XWRXWDSLHFHRIFDUGERDUGIURPWKHVKLSSLQJER[UROO
it up, hook it onto the back rib, and use it as a spacer
to lift the indoor unit. (Fig. 5)
&RQQHFWWKHUHIULJHUDQWSLSLQJZLWKWKHH[WHQVLRQSLSH%
9) Thrust the lower part of the indoor unit into the installation plate (1).
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from
WKHLQGRRUXQLWFRUUHFWO\RQWKHWHUPLQDOEORFN%HFDUHIXOQRWWRPDNHPLVZLULQJ)L[
WKHZLUHWRWKHWHUPLQDOEORFNVHFXUHO\VRWKDWQRSDUWRILWVFRUHLVDSSHDUHGDQGQR
H[WHUQDOIRUFHLVFRQYH\HGWRWKHFRQQHFWLQJVHFWLRQRIWKHWHUPLQDOEORFN
)LUPO\WLJKWHQWKHWHUPLQDOVFUHZVWRSUHYHQWWKHPIURPORRVHQLQJ$IWHUWLJKWHQLQJ
SXOOWKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH
&RQQHFWSRZHUVXSSO\FRUG.
)L[LQGRRURXWGRRUXQLWFRQQHFWLQJZLUH$DQGSRZHUVXSSO\FRUG.ZLWKWKHFRUG
clamp.
&ORVHWKHVHUYLFHSDQHOVHFXUHO\
3-2. FLARING WORK
&XW WKH FRSSHU SLSH FRUUHFWO\ ZLWKSLSHFXWWHU
(Fig. 1, 2)
&RPSOHWHO\UHPRYHDOOEXUUV IURPWKHFXWFURVV VHF -
tion of pipe. (Fig. 3)
• Put the end of the copper pipe to downward direc-
WLRQDV\RXUHPRYHEXUUVLQRUGHUWRDYRLGWROHW
burrs drop in the piping.
3) Remove flare nuts attached to indoor and outdoor
units, then put them on pipe having completed burr
removal. (Not possible to put them on after flaring
work.)
)ODULQJ ZRUN )LJ )LUPO\ KROG FRSSHU SLSH LQ
the dimension shown in the table. Select A mm from
WKHWDEOHDFFRUGLQJWRWKHWRRO\RXXVH
5) Check
&RPSDUHWKHÀDUHGZRUNZLWK)LJ
,IÀDUHLVQRWHGWREHGHIHFWLYHFXWRIIWKHÀDUHGVHFWLRQDQGGRÀDULQJZRUN
again.
3-3. PIPE CONNECTION
)DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOH
:KHQ IDVWHQHG WRR WLJKW ÀDUH QXWPD\ EUDNH DIWHU D ORQJ SHULRG DQG FDXVH UHIULJHUDQW
leakage.
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
$SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHVHDWVXUIDFHRISLSH
)RUFRQQHFWLRQ¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXW
• Use tightening torque table below as a guideline for indoor unit side union joint section,
DQGWLJKWHQXVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the
same manner applied for indoor unit.
• For tightening, use a torque wrench or spanner and use the
same tightening torque applied for indoor unit.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
)RURXWGRRU XQLW VLGH VXUHO\ LQVXODWH HYHU\ SLSLQJLQFOXGLQJ
valves.
8VLQJSLSLQJWDSH*DSSO\WDSLQJVWDUWLQJIURPWKHHQWU\RIRXWGRRUXQLW
• Stop the end of piping tape (G) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the tempera-
WXUHDQGKXPLGLW\DUHKLJKZLQGDGGLWLRQDOFRPPHUFLDOO\VROGLQVXODWLRQWRSUHYHQW
condensation.
Rear, right, or downward piping
1) Put the refrigerant piping and the drain hose
WRJHWKHU WKHQ ILUPO\ DSSO\SLSLQJ WDSH*
from the end.
2) Insert the piping and the drain hose into the
wall hole sleeve (C), and hook the upper part
of the indoor unit on the installation plate (1).
&KHFNLIWKHLQGRRUXQLWLVKRRNHGVHFXUHO\RQWKHLQVWDOODWLRQSODWHE\PRYLQJ
the unit to left and right.
4) Thrust the lower part of the indoor unit into the installation plate (1).
Pipe diameter
(mm)
Nut
(mm)
A (mm) Tightening torque
&OXWFKW\SH
tool
for R410A
&OXWFKW\SH
tool
for R22
Wing nut
W\SHWRRO
for R22
N•m kgf•cm
ø 6.35 (1/4”) 17
0 to 0.5 1.0 to 1.5
1.5 to 2.0 13.7 to 17.7 140 to 180
ø 9.52 (3/8”) 22 34.3 to 41.2 350 to 420
ø12.7 (1/2”) 26 2.0 to 2.5 49.0 to 56.4 500 to 575
ø15.88 (5/8”) 29 73.5 to 78.4 750 to 800
Drain Piping
,IWKHH[WHQVLRQGUDLQKRVHKDVWRSDVVWKURXJKDURRPEHVXUHWRZUDSLWZLWKFRP -
PHUFLDOO\VROGLQVXODWLRQ
7KHGUDLQKRVHVKRXOGSRLQWGRZQZDUGIRUHDV\GUDLQÀRZ)LJ
• If the drain hose provided with the indoor unit is too short, connect it with drain hose (I)
WKDWVKRXOGEHSURYLGHGDW\RXUVLWH)LJ
:KHQFRQQHFWLQJWKHGUDLQ KRVHWRWKHKDUGYLQ\OFKORULGHSLSH EHVXUHWRLQVHUWLW
VHFXUHO\LQWRWKHSLSH)LJ
Do not make drain piping as shown below.
Do not raise Accumulated
drain water
Air
Waving
Water
leakage
Water
leakage
Water
leakage
Tip of drain
hose dipped
in water
Ditch
At least
50 mm
gap
Cut off in case of
right piping.
Cut off in case of
downward piping.
Copper
pipe
Good
Tilted Uneven Burred
No good
Fig. 1
Fig. 2
Burr Copper pipe
Spare reamer
Pipe cutter
&OXWFKW\SH
Flaring tool
Fig. 4Fig. 3
Smooth all
around
Even length
all around
Inside is shin-
LQJZLWKRXWDQ\
scratches.
Flare nut
Die
Fig. 5 Fig. 6
Downward
slope
Drain
hose
Soft hose
I.D. 15 mm
Drain hose
+DUGYLQ\OFKORULGH
pipe I.D. 30 mm
Insert
VHFXUHO\
Different
diameter joint
70 cm or
more
Fig. 1 Fig. 2 Fig. 3
Lead wire
Terminal block
Cord clamp
3RZHUVXSSO\
cord (K)
• Make earth wire a little longer
than others. (More than 60 mm)
)RU IXWXUH VHUYLFLQJ JLYH H[WUD
length to the connecting wires.
Drain cap
Drain cap
Drain hose
Cut off in case of left
piping.
Drain cap
Piping tape (G)
Drain hose
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Felt tape (7)
3. OUTDOOR UNIT INSTALLATION
Copper pipe
:LQJQXWW\SH
Indoor/outdoor unit
connecting wire (A)
3RZHUVXSSO\FRUG.
Especificaciones del producto
Marca: | Mitsubishi |
Categoría: | aire acondicionado |
Modelo: | MUZ-FD35VA |
¿Necesitas ayuda?
Si necesitas ayuda con Mitsubishi MUZ-FD35VA haz una pregunta a continuación y otros usuarios te responderán
aire acondicionado Mitsubishi Manuales
19 Octubre 2024
14 Octubre 2024
9 Octubre 2024
9 Octubre 2024
8 Octubre 2024
4 Octubre 2024
4 Octubre 2024
1 Octubre 2024
1 Octubre 2024
30 Septiembre 2024
aire acondicionado Manuales
- aire acondicionado Zibro
- aire acondicionado Candy
- aire acondicionado Electrolux
- aire acondicionado Samsung
- aire acondicionado LG
- aire acondicionado Bosch
- aire acondicionado AEG
- aire acondicionado Panasonic
- aire acondicionado BEKO
- aire acondicionado Delonghi
- aire acondicionado Daewoo
- aire acondicionado Grundig
- aire acondicionado Honeywell
- aire acondicionado Inventum
- aire acondicionado Siemens
- aire acondicionado Toshiba
- aire acondicionado Unold
- aire acondicionado Whirlpool
- aire acondicionado Vaillant
- aire acondicionado Adler
- aire acondicionado Akai
- aire acondicionado Apc
- aire acondicionado Amana
- aire acondicionado Argo
- aire acondicionado Arcelik
- aire acondicionado Bartscher
- aire acondicionado Tosot
- aire acondicionado Eurom
- aire acondicionado GE
- aire acondicionado Orbegozo
- aire acondicionado Ozito
- aire acondicionado Sharp
- aire acondicionado Klarstein
- aire acondicionado Gorenje
- aire acondicionado Hitachi
- aire acondicionado Nedis
- aire acondicionado Thomson
- aire acondicionado Korona
- aire acondicionado Black And Decker
- aire acondicionado Innoliving
- aire acondicionado Tristar
- aire acondicionado Domo
- aire acondicionado Trisa
- aire acondicionado Hotpoint-Ariston
- aire acondicionado Calor
- aire acondicionado Rowenta
- aire acondicionado Tomado
- aire acondicionado Livoo
- aire acondicionado Manta
- aire acondicionado SereneLife
- aire acondicionado Hisense
- aire acondicionado Hyundai
- aire acondicionado Vox
- aire acondicionado Westinghouse
- aire acondicionado Emerio
- aire acondicionado RCA
- aire acondicionado Clatronic
- aire acondicionado Hotpoint
- aire acondicionado Sencor
- aire acondicionado Midea
- aire acondicionado Blaupunkt
- aire acondicionado Mabe
- aire acondicionado Concept
- aire acondicionado Frigidaire
- aire acondicionado Svan
- aire acondicionado Logik
- aire acondicionado Danby
- aire acondicionado Anslut
- aire acondicionado Stirling
- aire acondicionado Daikin
- aire acondicionado Carson
- aire acondicionado Mesko
- aire acondicionado Profilo
- aire acondicionado Tripp Lite
- aire acondicionado Truma
- aire acondicionado Heinner
- aire acondicionado Sanyo
- aire acondicionado Eldom
- aire acondicionado Jocca
- aire acondicionado Einhell
- aire acondicionado Kenmore
- aire acondicionado Philco
- aire acondicionado TCL
- aire acondicionado Nabo
- aire acondicionado Guzzanti
- aire acondicionado Defy
- aire acondicionado Infiniton
- aire acondicionado Dometic
- aire acondicionado Aspes
- aire acondicionado Dimplex
- aire acondicionado DCG
- aire acondicionado Emerson
- aire acondicionado White Knight
- aire acondicionado Suntec
- aire acondicionado Profile
- aire acondicionado Orima
- aire acondicionado Haier
- aire acondicionado Gree
- aire acondicionado Evolar
- aire acondicionado Elba
- aire acondicionado Proline
- aire acondicionado Royal Sovereign
- aire acondicionado Corberó
- aire acondicionado Zelmer
- aire acondicionado Meaco
- aire acondicionado Fujitsu
- aire acondicionado Be Quiet!
- aire acondicionado Kelvinator
- aire acondicionado Element
- aire acondicionado Malmbergs
- aire acondicionado Everglades
- aire acondicionado Heylo
- aire acondicionado Insignia
- aire acondicionado Daitsu
- aire acondicionado Sanus
- aire acondicionado Milectric
- aire acondicionado Wilfa
- aire acondicionado Carrier
- aire acondicionado Olimpia Splendid
- aire acondicionado Trotec
- aire acondicionado Saunier Duval
- aire acondicionado Camry
- aire acondicionado Qlima
- aire acondicionado Alpatec
- aire acondicionado Jocel
- aire acondicionado Comfee
- aire acondicionado Godrej
- aire acondicionado Sauber
- aire acondicionado Maiko
- aire acondicionado MPM
- aire acondicionado Tectro
- aire acondicionado Rotel
- aire acondicionado Becken
- aire acondicionado Bavaria
- aire acondicionado Essentiel B
- aire acondicionado Equation
- aire acondicionado Vivax
- aire acondicionado Edy
- aire acondicionado HTW
- aire acondicionado Maxicool
- aire acondicionado Fuave
- aire acondicionado KDK
- aire acondicionado Dantherm
- aire acondicionado Thermex
- aire acondicionado Bimar
- aire acondicionado HQ
- aire acondicionado Be Cool
- aire acondicionado Master
- aire acondicionado MundoClima
- aire acondicionado Argoclima
- aire acondicionado Baxi
- aire acondicionado Proklima
- aire acondicionado Sonnenkonig
- aire acondicionado Lavorwash
- aire acondicionado Climadiff
- aire acondicionado Home Electric
- aire acondicionado REMKO
- aire acondicionado Fairland
- aire acondicionado Toyotomi
- aire acondicionado Just Fire
- aire acondicionado Avidsen
- aire acondicionado Teco
- aire acondicionado Furrion
- aire acondicionado Cecotec
- aire acondicionado Iceberg
- aire acondicionado Livington
- aire acondicionado Whynter
- aire acondicionado Chigo
- aire acondicionado Firstline
- aire acondicionado Holland Electro
- aire acondicionado Evapolar
- aire acondicionado Orava
- aire acondicionado EcoFlow
- aire acondicionado Duracraft
- aire acondicionado Khind
- aire acondicionado Fronius
- aire acondicionado NewAir
- aire acondicionado Kogan
- aire acondicionado ActronAir
- aire acondicionado Klimaire
- aire acondicionado SEEGER
- aire acondicionado LERAN
- aire acondicionado General Electric
- aire acondicionado Mistral
- aire acondicionado Friedrich
- aire acondicionado Simplicity
- aire acondicionado Starlyf
- aire acondicionado Moa
- aire acondicionado Fuji Electric
- aire acondicionado Kibernetik
- aire acondicionado Prem-i-air
- aire acondicionado Céliera
- aire acondicionado Bodin
- aire acondicionado Brivis
- aire acondicionado MRCOOL
- aire acondicionado B-Air
- aire acondicionado Rinnai
- aire acondicionado GoldAir
- aire acondicionado Ravanson
- aire acondicionado Create
- aire acondicionado Daizuki
- aire acondicionado Bonaire
- aire acondicionado Woods
- aire acondicionado Evapcool
- aire acondicionado Protector
- aire acondicionado Krone
- aire acondicionado IFB
- aire acondicionado Artrom
- aire acondicionado Coolix
- aire acondicionado Heat Controller
- aire acondicionado Luma Comfort
- aire acondicionado Norpole
- aire acondicionado Kaco
- aire acondicionado Omega Altise
- aire acondicionado Goodwe
- aire acondicionado Swegon
- aire acondicionado InAlto
- aire acondicionado JHS
- aire acondicionado FREONIC
- aire acondicionado ARCTIC WIND
- aire acondicionado SHE
- aire acondicionado Electroline
- aire acondicionado BLUEPALM
- aire acondicionado KuulAire
- aire acondicionado Keystone
- aire acondicionado Cool-Space
- aire acondicionado BOSFOR
- aire acondicionado Aconatic
- aire acondicionado AireMax
- aire acondicionado VänEE
- aire acondicionado Mayer
- aire acondicionado Perfect Aire
- aire acondicionado Koldfront
- aire acondicionado Yamazen
Últimos aire acondicionado Manuales
27 Octubre 2024
27 Octubre 2024
27 Octubre 2024
27 Octubre 2024
27 Octubre 2024
26 Octubre 2024
26 Octubre 2024
26 Octubre 2024
25 Octubre 2024