User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 1 LT _0
ASW - -Pro series inverter Table of Contents LT G2
1 Notes on this Manual ...................................................................... 4
1.1 General Notes ........................................................................................ 4
1.2 Area of Validity 4 ......................................................................................
1.3 Target group 5 ..........................................................................................
1.4 Symbols used in this manual ............................................................... 5
2 Safety .............................................................................................. 7
2.1 Intended use 7 ..........................................................................................
2.2 Important safety information ................................................................ 8
2.3 Symbols on the label ............................................................................. 9
3 Unpacking ..................................................................................... 11
3.1 Scope of delivery ................................................................................. 11
3.2 Check for transport damage ............................................................... 12
4 Mounting ....................................................................................... 13
4.1 Requirements for mounting ............................................................... 13
4.2 Mounting the inverter .......................................................................... 17
5 Electrical connection .................................................................... 20
5 Safety .1 .................................................................................................... 20
5.2 Electrical Connection Panel ............................................................... 21
5.3 Electrical connection diagram with a separate DC isolator ............ 22
5.4 AC Connection ..................................................................................... 22
5.4.1 Conditions for the AC connection .............................................. 22
2 User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 7 LT _0 22
5.4.2 Grid connection ............................................................................ 25
5.4.3 Additional grounding connection ............................................... 27
5.5 DC connection ..................................................................................... 28
5.5.1 Requirements for the DC connetion ........................................... 28
5.5.2 Assembling the DC connectors .................................................. 29
5.5.3 Disassembling the DC connectors ............................................. 30
5.5.4 Connecting the PV Array ............................................................. 32
5.6 Conmunication equipment connection ............................................. 34
5.6.1 Mounting the WiFi or 4G Stick .................................................... 34
5.6.2 Connect the RS485 network cable ............................................. 35
5.6.3 Connect the smart meter cable ................................................... 37
6 Communication ............................................................................ 38
6.1 System monitoring via WLAN ............................................................ 38
6.2 Active power control with Smart meter ............................................. 39
6.3 Remote rmware update ..................................................................... 40
6.4 Active power control via demand response enabling device (DRED)
..................................................................................................................... 40
6.5 Communication with the third party device ...................................... 41
6.6 Earth fault alarm .................................................................................. 41
7 Commissioning ............................................................................. 42
7.1 Electrical check ................................................................................... 42
7.2 Mechanical check ................................................................................ 43
7.3 Safety code check ............................................................................... 44
7.4 Start- up ................................................................................................. 44
4 User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 7 LT _0 22
1 Notes on this Manual
1.1 General Notes
ASW - -Pro series inverter is a three-phase transformerless string LT G2
inverter with two independent MPPTs. It converts the direct current (DC)
generated by the photovoltaic (PV) module into a three-phase alternating
current (AC) and feeds it into the utility grid.
1.2 Area of Validity
This manual describes the mounting, installation, commissioning and
maintenance of the following inverters:
ASW3K- - -P LT G2 ro
ASW4K- - -P LT G2 ro
ASW5K- - -Pro LT G2
ASW6K- - -Pro LT G2
ASW8K- - -Pro LT G2
ASW10K- - -Pro LT G2
ASW12K- - -Pro LT G2
ASW13K- - -Pro LT G2
ASW15K- - -Pro LT G2
ASW17K- - -Pro LT G2
ASW20K- - -Pro LT G2
Please read this manual carefully before using this product, keep it in a
convenient place and make it available at all times.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 5 LT _0
1.3 Target group
This document is for qualied electricians only, who must perform the tasks
exactly as described.
All persons installing inverters must be trained and experienced in general
safety which must be observed when working on electrical equipment.
Installation personnel should also be familiar with local requirements, rules
and regulations.
Qualied persons must have the following skills:
• Knowledge of how an inverter works and is operated
• Training in how to deal with the dangers and risks associated with installing,
repairing and using electrical devices and installations
• Training in the installation and commissioning of electrical devices and
installations
• Knowledge of the applicable laws, standards and directives
• Knowledge of and compliance with this document and all safety information.
1.4 Symbols used in this manual
Safety instructions will be highlighted with the following symbols:
DANGER indicates a hazardous situation which, if not be avoided, will
result in death or serious injury.
WARNING indicates a hazardous situation which, if not be avoided, can
result in death or serious injury.
6 User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 7 LT _0 22
CAUTION indicates a hazardous situation which, if not be avoided, can
result in minor or moderate injury.
NOTICE indicates a situation which, if not be avoided, can result in
property damage.
INFORMATION that is important for a specic topic or goal, but is not
safety-relevant.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 7 LT _0
2 Safety
2.1 Intended use
1. ASW - -Pro series inverter converts the direct current from LT G2 the PV
arrays into grid-compliant alternating current.
2. ASW - -PLT G2 ro series inverter is suitable for indoor and outdoor use.
3. ASW - -PLT G2 ro series inverter must only be operated with PV arrays (PV
modules and cabling) of protection class II in accordance with IEC 61730,
application class A. Do not connect any sources of energy other than PV
modules to ASW - -P series inverter. LT G2 ro
4 PV modules with a high capacity to ground must only be used if their .
coupling capacity does not exceed 5 .0μF.
5. When the PV modules are exposed to light, a DC voltage is supplied to this
inverter .
6. When designing the PV power plants, ensure that the values comply with
the permitted operating range of all components at all time .
7. The product must only be used in countries for which it is approved or
released by AISWEI and the grid operator.
8. Use this product only in accordance with the information provided in th is
documentation and with the locally applicable standards and directives. Any
other application may cause personal injury or property damage.
9. The type label must remain permanently attached to the product.
8 User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 7 LT _0 22
2.2 Important safety information
Danger to life due to electric shock when live components or
cables are touched
• All work on the inverter must only be carried out by qualified
personnel who have read and fully understood all safety
information contained in this manual.
• Do not open the inverter.
• Children must be supervised to ensure that they do not play
with the inverter.
Danger to life due to high voltages of the PV array
When exposed to sunlight, the PV array generates dangerous
DC voltage which is present in the DC conductors and the live
components of the inverter. Touching the DC conductors or
the live components can lead to lethal electric shocks. If you
disconnect the DC connectors from the inverter under load,
an electric arc may occur leading to electric shock and burns.
• Do not touch non-insulated cable ends.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Have the inverter mounted, installed and commissioned only
by qualied persons with the appropriate skills.
•If an error occurs, have it rectified by qualified persons only.
•Prior to performing any work on the inverter, disconnect it
from all voltage sources as described in this document (see
Section 9 "Disconnecting the Inverter from Voltage Sources").
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 9 LT _0
2.3 Symbols on the label
Symbol
Explanation
Beware of a danger zone
This symbol indicates that the inverter must be additionally
grounded if additional grounding or equipotential bonding is
required at the installation site.
Risk of injury due to electric shock
Touching an ungrounded PV module or array frame can
cause a lethal electric shock.
connect and ground the PV modules, array frame and
electrically conductive surfaces so that there is continuous
conduction.
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation.
• During operation, do not touch any parts other than the
enclosure lid of the inverter.
Damage to the inverter due to electrostatic discharge
Internal components of the inverter can be irreparably
damaged by electrostatic discharge.
• Ground yourself before touching any component.
10 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
Beware of high voltage and operating current
The inverter operates at high voltage and current. Work on the
inverter must only be carried out by skilled and authorized
electricians.
Beware of hot surfaces
The inverter can get hot during operation. Avoid contact during
operation.
WEEE designation
Do not dispose of the inverter together with the household
waste but in accordance with the disposal regulations for
electronic waste applicable at the installation site.
CE marking
The product complies with the requirements of the applicable
EU directives.
Certication mark
The product s been tested by TUV and got the quality ha
certication mark.
RCM Mark
The product complies with the requirements of the applicable
Australian standards.
Capacitors discharge
Before opening the covers, the inverter must be disconnected
from the grid and PV array. Wait at least 5 minutes to allow the
energy storage capacitors to fully discharge.
Observe the documentation
Observe all documentation supplied with the product
12 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
3.2 Check for transport damage
Thoroughly inspect the packaging upon delivery. If you detect any damage to
the packaging which indicates inverter may have damaged, inform the been
the responsible shipping company immediately. We will be glad to assist you if
required.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 13
4 Mounting
4.1 Requirements for mounting
1. Be sure that the inverter is mounted out of the reach of children.
2. Mount the inverter in areas where it cannot be touched inadvertently.
3. Ensure good access to the inverter for installation and possible service.
4. The ambient temperature should be below 40°C to ensure optimal
operation.
5. Observe the minimum clearances to walls, other inverters, or objects as
follows to ensure suicient heat dissipation.
Danger to life due to re or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where ammable materials are
stored.
Do not mount the inverter in areas where there is a risk of explosion.
14 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
Clearances f one inverter or
Clearances f multiple inverters or
6. In order to avoid power reduction caused by overheating, do not mount
the inverter in a location that allows long-term exposure to direct sunlight.
7. Ensure optim eration and extend service life avoid exposing the um op ,
inverter to direct sunlight, rain and snow.
Min. clearance (mm)
500
500
300
16 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
12. Never install the inverter horizontally, or with a forward tilt or with a
backward tilt or even with upside down. The horizontal installation can
result in damage to the inverter.
13. Mount the inverter at eye level for easy inspection.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 17
4.2 Mounting the inverter
Mounting procedure:
1. Use the wall bracket as a drilling template and mark the positions of the drill
holes, then drill 3 holes ( 10) a depth about . During operation, Φto 70mm
k drill vertical to the wall, and hold the drill steady to avoid tilteep the ed
holes.
Risk of injury when lifting the inverter, or if it is dropped
The weight of Solplanet inverter is max. 18.6 kg. There is risk of injury if
the inverter is lifted incorrectly or dropped while being transported or when
attaching it to or removing it from the wall bracket.
• Transport and lift the inverter carefully.
Risk of injury due to damaged cables
There may be power cables or other supply lines (e.g. gas or water)
routed in the wall.
• Ensure that no lines are laid in the wall which could be damaged when
drilling holes.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 21
5.2 Electrical Connection Panel
Object
Description
A
DC-switch
B
MPP1 connector
(3-10K has 1 pair of terminals, 12K-20K has 2 pairs of
terminals)
C
MPP2 connector
(3K-15K has 1 pair of terminals, 17K-20K has 2 pairs of
terminals)
D
RS485 Communication interface COM1/2
E
Communication Stick interface COM3
F
AC connector
G
Additional grounding screw
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 23
Object
Description
Value
A
External diameter
10…16 mm
B
Conductor cross-section
2.5…6 mm2
C
Stripping length of the insulated conductors
Approx. 13 mm
D
Stripping length of the AC cable’s outer
s heath
Approx. 53 mm
The PE insulated conductor must be 2 mm longer than the L and N
conductors
Larger cross-sections should be used for longer leads.
Cable Design
The conductor cross-section should be dimensioned to avoid power loss in
cables exceeding 1% of rated output power.
The required conductor cross-section depends on the inverter rating, ambient
temperature, routing method, cable type, cable losses, valid installation
requirements of installation side.
Residual current protection
The product is equipped with an integrated universal current-sensitive residual
current monitoring unit inside. The inverter will disconnect immediately from
the mains power as soon as fault current with a value exceeding the limit.
Overvoltage category
The inverter can be used in grids of overvoltage category III or lower in
accordance with IEC 60664-1. This means that it can be permanently
If an external residual-current protection device is
required, please install a type B residual-current protection
device with a protection limit of not less than 100mA.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 25
5.4.2 Grid connection
Procedure:
1. Switch off the circuit breaker and secure it against reconnection.AC
2. Insert the copper wire into a suitable European style tube connector
(according to DIN 46228-4) and crimp it.
Safety in accordance with IEC 62109 when the grounding
conductor monitoring is deactivated.
In order to guarantee safety in accordance with IEC 62109 when the
grounding conductor monitoring is deactivated, carry out one of the
following measures:
• Connect a copper-wire grounding conductor with a cross-section of at
least 10 mm² to the AC connector bush insert.
• Connect an additional grounding that has at least the same cross-section
as the connected grounding conductor to the AC connector bush insert.
This prevents touch current in the event of the grounding conductor on the
AC connector bush insert failing.
Danger to life due to high voltages in the inverter
Touching the live components can lead to lethal electric shocks.
Before performing the electrical connection, ensure that the AC circuit-
breaker is switched off and cannot be reactivated.
26 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
3. Insert the grounding wire (PE), neutral wire (N) and live wire (L1, L2 and L3)
of the crimped European connector into the corresponding holes of the
terminal block as indicated by the arrows below, and tighten the screws with
a 3mm wide Allen wrench. The torque is 2.0 Nm.
4. Push the holding buckle and the sealing plug into the screw sleeve body,
and then assemble the terminal block, the screw sleeve body and the
tightening nut together. First clamp the terminal block with a plastic clamp,
then screw the screw sleeve body onto the terminal block, and nally tighten
the tightening nut.
5. Insert the wired AC connector into the corresponding AC output port of the
inverter and tighten it clockwise..
Damage to the inverter due to wrong wiring
If the phase line was connected to PE terminal, the inverter will not
function properly.
Please ensure that the type of the conductors matches the signs of the
terminals on the socket element.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 31
1. Make sure DC power is cut o.
2. Unscrew the swivel nut.
3. To release the DC connector, insert a flat-blade screwdriver (blade width:
3.5 mm) into the side catch mechanism and lever open.
4. Carefully pull the DC connector apart.
5. Release the clamping bracket. To do so, insert a flat-blade screwdriver
(blade width: 3.5 mm) into the clamping bracket and lever it open.
6. Remove the cable.
32 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
5.5.4 Connecting the PV Array
Procedure:
1. Ensure that the individual AC circuit breaker is switched o and secure it
against reconnection.
2. Ensure that the DC-switch is switched o and secure it against
reconnection.
3. Ensure that there is no ground fault in the PV strings.
4. Check whether the DC connector has the correct polarity. If the DC
connector ts with a DC cable having the wrong polarity, the DC connector
must be reassembled again. The DC cable must always have the same
polarity as the DC connector.
5. Ensure that the open-circuit voltage of the PV strings does not exceed the
maximum DC input voltage of the inverter.
6. Unplug the sealing plug on the input end of the DC connector and connect
the assembled DC connectors to the inverter until they audibly snap into
place. Do not unplug the sealing plug from the input end of unused DC
connector.
Destruction of the inverter due to overvoltage
If the voltage of the strings exceeds the maximum DC input voltage of the
inverter, it can be destroyed due to overvoltage. All warranty claims
become void.
Do not connect strings with an open-circuit voltage greater than the
maximum DC input voltage of the inverter.
Check the design of the PV system
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 33
Damage to the inverter due to moisture and dust penetration
Seal the unused DC inputs with sealing plugs so that moisture and dust
cannot penetrate the Inverter.
Make sure all DC connectors are securely sealed.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 43
Check the grid voltage: check that the grid voltage at the point of
connection of the inverter is within permitted range. the
7.2 Mechanical check
Carry out the main mechanical checks to ensure the inverter is waterproof as
follows:
Make sure the inverter has been correctly mounted with wall bracket.
Make sure the cover has been correctly mounted.
Make sure the communication cable and AC connector have been
correctly wired and tightened.
Danger to life due to the presence of AC-Voltage
Touching the live conductors can lead to lethal electric shocks.
• Only touch the insulation of the AC cables.
Wear personal protective equipment such as insulating gloves.
User Manual UM0014_ASW 3K-20K- -G2 PRO_EN_V03 722 LT _0 49
5. Release and disconnect the AC connector. Rotate the socket element
counterclockwise to open.
6. Wait until all LEDs and the display have gone out.
50 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
10 Technical data
10.1 DC input data
Type
ASW - -3K LT
G2-Pro
ASW - -4K LT
G2-Pro
ASW - -5K LT
G2-Pro
ASW - -6K LT
G2-Pro
Max. PV
modules power
(STC)
4500W
6000W
7500W
9000W
Max. input
voltage/ Rated
input voltage
1100V/630V
MPPT voltage
range
1501000 V
Full load MPPT
voltage range
270850 V
Intitial feed-in
voltage
180V
Min input
voltage
125V
Max. DC input
current
16A/16A
Isc PV, absolute
max.
25A/25A
Maximum
reverse current
from the inverter
in the system for
max. 1 ms
0A
Number of MPP
trackers
2
52 User Manual UM0014_ASW 3K- - -G2 PRO_EN_V03 7 20K LT _0 22
inverter in the
system for max.
1 ms
Number of MPP
trackers
2
Strings per
MPP tracker
1/1
2/1
Overvoltage
category in
accordance with
IEC60664-1
II
Type
ASW15K- -LT
G2-Pro
ASW17K-
LT- -Pro G2
ASW20K- -LT
G2-Pro
Max. PV modules
Power (STC)
22500W
25500W
30000W
Max. input voltage/
Rated input voltage
1100V/630V
MPP voltage range
1501000 V
Full load MPP voltage
range
400850V
Intitial feed-in voltage
180V
Min input voltage
125V
Max. DC input current
32A/20A
2*32A
Isc PV, absolute max.
48A/30A
2*48A
Maximum reverse
current from the
inverter in the system
for max. 1 ms
0A