Tripp Lite RELAYCARDSV Manual de Usario

Lee a continuación 📖 el manual en español para Tripp Lite RELAYCARDSV (28 páginas) en la categoría No categorizado. Esta guía fue útil para 6 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/28
1
Owner’s Manual
Relay I/O Card
Model: RELAYCARDSV
1 Introduction 2
1.1 Product Features 2
1.2 Package Contents 2
2 Installation and Setup 2
2.1 System Requirements 2
2.2 Installation 2
3 Specifications 3
3.1 Internal Circuit 3
3.2 Electric Specifications 3
3.3 Pin Assignment 3
3.4 Function Description 4
3.5 Application Example 4
4 Internal Logic Connection 5
4.1 Pin Definition and 5
Internal Logic Connection
4.2 Connection for Normally Closed 5
4.3 Connection for Normally Open 5
5. Jumper Configuration 6
5.1 Jumper Setup 6
5.2 Jumper Function Description 6
6. Warranty and Product Registration 7
Español 8
Français 15
Русский 22
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite. All rights reserved. All trademarks are the property of their respective owners.
2
1.1 Product Features
The RELAYCARDSV communication card provides contact closures for remote
UPS monitoring. To meet different application requirements, the RELAYCARDSV
allows the user to select status of the dry-contact signal (normally closed or
open) by setting the jumper. Typical applications include:
IBM Server, PC and workstation equipment
Auto-controlled industrial equipment
and communication applications
1.2 Package Contents
RELAYCARDSV
Owner’s Manual
9-Pin Communication Cable
2.1 System Requirements
The RELAYCARDSV supports Tripp Lite SmartOnline® SVTX 400V Non-Modular, SVX 400V Modular, and SV 208V Modular UPS systems.
2.2 Installation
1. Introduction
2. Installation and Setup
Step 2: Insert RELAYCARDSV into the ACC Slot.
Step 3: Using a screwdriver and screws provided from removing
the ACC Slot cover in Step 1, secure the RELAYCARDSV to the UPS
chassis.
Step 1: Using a screwdriver, remove the ACC Slot cover located on
the rear panel (SVTX Series) or front panel for Modular systems (SVX-
and SV-Series).
Step 4: Use the 9-pin communication cable to connect UPS and
equipment for remote monitoring and control.
3
3.1 Internal Circuit
DB9 Internal Circuit Diagram
3. Specifications
3.2 Electric Specifications
DB9 Port Electric Specifications
Parameter Symbol Max. Min. Unit
Resistor* DC Current IR 6 1 mA
Diode Reverse Voltage VR 6 - V
Forward Current IF 50 - mA
Peak Forward Current IF (Peak) 1 - A
Relay DC Voltage VDC 24 - V
DC Current IDC 1.0 - A
Note: DC current should be lower than 6mA. When the DC current exceeds 6mA, a resistor within DC current limitation should be added within the Remote
Shutdown/Common loop (e.g. a 2K resistor with at least 0.1W rating power). For more information, refer to diagrams A and B in .3.5 Application Example
3.3 Pin Assignment
Pin Assignment Function I/O
Pin 1 UPS Failure O/P
Pin 2 UPS Audible Alarm O/P
Pin 3 GND (Common for Pin 4) Power Ground
Pin 4 Remote Shutdown I/P
Pin 5 Common for Relays Power Supply
Pin 6 Bypass Active O/P
Pin 7 Low Battery O/P
Pin 8 UPS On O/P
Pin 9 Utility Failure O/P
Note: The shutdown pin (pin 3 and pin 4) only accepts 3-10s high level signal to perform the UPS shutdown.