Air King AKF50 Manual de Usario

Lee a continuación 📖 el manual en español para Air King AKF50 (12 páginas) en la categoría Ventilador. Esta guía fue útil para 19 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/12
IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
SAVE THESE INSTRUCTIONS
www.airkinglimited.com
210572203 Rev. N 1-16 1 of 12
Exhaust Fan with Light
Models: AKF50, AKF80LS, AKF100,
AKF80H, AKF100H,
LEDAK80, LEDAK100
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer.If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent power
from being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-related construction.
b) Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment manufacturer’s guideline
and safety standards such as those published by the National Fire
Protection Association (NFPA) and the American Society for Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE), and the local
code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) This unit must be grounded.
f) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
g) Read all instructions before installing or using exhaust fan.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, DO NOT USE THIS FAN WITH
ANY SOLID-STATE SPEED CONTROL DEVICE.
a) If this unit is to be installed over a tub or shower, it must be
marked as appropriate for the application and be connected to a
GFCI (Ground Fault Circuit Interrupter) – protected branch circuit.
b) Do not install in a ceiling with thermal insulation value greater
than R40.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT
ON THE AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE
THE SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR
BEST PERFORMANCE, AND AVOID INSTALLING THE FAN WITH
SMALLER DUCTS THAN RECOMMENDED. INSULATION AROUND
THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD
GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY NOT
ACHIEVE THEIR RATED AIRFLOW.
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
1 - Grill
1 - Light Assembly
1 - Damper Assembly (attached)
4 - Mounting Rails
1 - Fluorescent Lamp
1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it
is recommended that the length of ducting and the number of elbows be kept to a
minimum, the radius of each elbow be as large as possible for the installation, and that
insulated hard ducting be used. This fan will require
at least 8” of clearance in the ceiling or wall, and
will mount through drywall up to 3/4” thick. The fan
mounts between 16 or 24” on center joists using the
4 provided mounting rails.
3. Select the most convenient electrical knockout and
remove using a straight-blade screw driver (Figure 1).
4. No additional vibration deadening materials are needed
for this fan.
SECTION 2
New Construction
1. Install the rails into the mounting channel on the housing. Center the mounting channel in
the slots on the housing, then from inside the housing tighten the mounting channel screws
so the channel is securely in place. Position the housing next to the joist. Line up housing
so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or
nails (not included) to the joists and slide the housing into the final position (Figure 2).
SECTION 3
Existing Construction
1. Set housing in position between the joist and trace an outline onto the ceiling material
(Figure 3). Set housing aside and cut opening, being careful not to cut or damage any
electrical or other hidden utilities. Install the rails into the mounting channel on the
housing. Center the mounting channel in the slots on the housing, then from inside
the housing tighten the mounting channel screws so the channel is securely in place.
Position the housing in the previously cut hole so that it is flush with the finished ceiling.
Secure the ends of the rails to the joists (Figure 2).
www.airkinglimited.com
210572203 Rev. N 1-16 2 of 12
SECTION 4
Ducting
NOTE: 4" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL
BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible
for best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed
with existing ducts may not achieve their rated air flow.
1. Connect the ducting to the fan’s duct collar . Secure in place using tape (Figure 4)
or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is
recommended that low restriction termination fittings be used.
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar material
to create an air-tight path to minimize building heat loss or gain and to reduce the potential
for condensation. Place/wrap insulation around duct and/or fan in order to minimize possible
condensation buildup within the duct, as well as building heat loss or gain (Figure 5).
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL
WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of the
fan’s blower assembly. If you choose to wire the unit from the inside, you will need to remove
the blower assembly and internal wiring compartment. Both methods are equally effective.
1a. Remove the wire compartment cover screw and place External Wire Compartment:
cover in a secure place .(Figure 6)
Figure 1
Figure 2
Housing
Joist
Mounting Rails
Ducting
Duct
Collar
Figure 4
Figure 5
Insulation*
(place around and
over Fan Housing
Fan Housing
Power Cable*
Seal gaps
around Housing
Round
Duct*
Seal duct joints
with tape
Round
Elbows*
Wall Cap*
Roof Cap*
(with built-in
damper)
Keep duct
runs short
*Purchase separately
or
Figure 3
Joist
1b. Internal Wire Compartment: Remove the screws holding the blower assembly in place
and lift assembly out of housing . Remove the wire compartment cover screw (Figure 7)
and place the cover in a secure place (Figure 8).
NOTE: If the fan motor plug is
connected to the fan housing
receptacle, unplug so the
blower assembly can be
completely removed.
STANDARD MODELS
2b. Run wiring from an approved wall switch carrying the appropriate rating. One neutral
(White), one ground (green or bare copper), and three hot (Black, Purple, Yellow leads
connected to the switch, one for each function). Secure the electrical wires to the
housing with an approved electrical connector. Make sure you leave enough wiring in the
box to make the connection to the fan’s receptacle.
2b. From where you have chosen to access the fan’s junction box, connect the White wire from
the house to the two White wires from the fan. Connect one Hot (Black) wire from the wall
switch to the Black wire from the fan (this is the fan control). Connect second Hot (Purple)
wire from the wall switch to the Purple wire from the fan (this is the night light control).
Connect the third Hot (Yellow) wire from the wall switch to the Yellow wire from the fan (this
is the main light control). Connect the ground wire (green or bare copper) from the house to
the Green wire from the fan . Use approved methods for all connections.(Figure 9)
HUMIDITY SENSING MODELS
3a. For proper fan operation, the humidity sensing fan will require a 3 way switch (not
included). Run wiring between the fan and the switch location. Make sure you leave
enough wiring in each box to make the connections. At the switch box connect the Black
wire from the house to the common terminal of the switch. Connect the black wire from
the fan to one of the switched terminals on the switch. This position will energize the
automatic mode and the fan will energize upon a rise in humidity. Connect the Red wire
from the fan to the other switched terminal on the switch. This position will activate the
Manual On feature and energize the fan. Use approved methods for all connections.
3b. To operate the main light and the night light, run wiring from two toggle switches (not
included). At the switch box, connect the Black wire from the house to the common
www.airkinglimited.com
210572203 Rev. N 1-16 3 of 12
terminal of each toggle switch. Connect the Yellow wire from the fan to one of the toggle
switches (this is the main light control). Connect the Purple wire from the fan to the other
toggle switch (this is the night light control). Use approved methods for all connections.
3c. From where you have chosen to access the fan’s junction box, connect the White wire
from the house to the two White wires from the fan. Connect the ground wire (green or
bare copper) from the house to the Green wire from the fan . Use approved (Figure 10)
methods for all connections.
NOTE: The fan’s receptacle wires might need to be pulled outside compartment for connection.
Only pull the three loose wires outside of compartment. Additional wires will be present.
4. Carefully tuck wires back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
SECTION 6
Completing the Installation
1. Use a sealant appropriate for contact with the building materials present and for the
temperature requirements of the installation to prevent air leakage from unconditioned
spaces is recommended. If gaps between unit housing and ceiling are great, additional
material (backing rod, ceiling material) may be required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan
be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.
2. If the fan’s blower assembly was removed during the wiring process, reinstall the blower
by reversing the directions in in .Step 1b Section 5 Wiring
3. Connect the fan wire harness by plugging the 3 pin quick connect end into the receptacle
located on the side of the wire compartment cover. Confirm that the 5 pin quick connect
end is plugged into the receptacle from the blower assembly. Connect the light wire harness
by plugging the 3 pin rectangular quick connect end into the receptacle located at the top of
the wire compartment. These cords will only fit one way into the receptacles (Figure 11).
4. Install the included lamp into the lamp holder by lining up the pins on the lamp base to the
socket of the lamp holder and turning the lamp body clockwise until the lamp snaps into
place and is firmly seated in the lamp holder. Install a 4 watt maximum type C7 (candelabra
base) night light (not included) into the side lamp holder (Figure 12).
Figure 6
Screw
Wire
Compartment
Cover
Figure 7
Screws
Plug
Venturi
Figure 9
Supply from house
Neutral (White)
Ground (Green or Bare)
Fan
Neutral (White)
Green
Hot (Black)
Yellow
Purple
Black
Figure 10
Supply from house
Neutral (White)
Ground (Green or Bare)
Fan
Neutral (White)
Green
Red
Hot (Black)
Yellow
Purple
Black
Hot (Black)
Hot (Black)
Figure 12
Lamp Lamp Holder
Pin
Night Light
Socket
NOTE: Fluorescent lamp shown
Figure 8
Screw Wire
Compartment
Cover
NOTE: Wire compartment configuration
will be dependent on model.
Figure 11 NOTE: Wire compartment configuration will be dependent on model.

Especificaciones del producto

Marca: Air King
Categoría: Ventilador
Modelo: AKF50

¿Necesitas ayuda?

Si necesitas ayuda con Air King AKF50 haz una pregunta a continuación y otros usuarios te responderán




Ventilador Air King Manuales

Ventilador Manuales

Últimos Ventilador Manuales