Altronix Trove3SH3 Manual de Usario

Lee a continuación 📖 el manual en español para Altronix Trove3SH3 (20 páginas) en la categoría No categorizado. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/20
SIGNALING
Rev. 101817
Combine Altronix Power and Accessories with
Access Controllers from the Industry’s Leading Manufacturers
Installation Guide
All registered trademarks are property of their respective owners. More than just power.™
Installing Company: Service Rep. Name: _____________________ __________________________________________
Address: Phone #: ________________________________________________________ _________________________
Access & Power Integration
- 2 - Trove
Overview:
Trove accommodates various combinations of access controllers and accessories from the industry’s leading manufacturers with or without
Altronix power supplies and accessories for access systems. A variety of backplanes offer a wide range of scalable access and power config-
urations. Trove simplifies board layout and wire management, while reducing installation and labor costs.
Trove Model Identification:
Series Trove
Enclosure Size
Backplane Model
(Access Controller Manufacturer) Backplane Size
Trove
1
18” x 14.5” x 4.625”
(457mm x 368mm x 118mm)
C = CDVI
1
16.625” x 12.5” x 0.06”
(422.3mm x 317.5mm x 1.5mm)
BV = Brivo
1
16.625” x 12.5” x 0.3125”
(422.3mm x 317.5mm x 7.9mm)
DM = DMP
JC = Johnson Controls
M = Mercury
PD = ProdataKey
SA = Salto
V = HID/VertX
2
27.25” x 21.75” x 6.5”
(692.2mm x 552.5mm x 165.1mm)
AM = AMAG
2
25.375” x 19.375” x 0.3125”
(644.5mm x 492.1mm x 7.9mm)
AG = AMAG
BH = Bosch
BL = Universal Blank Backplane
BV = Brivo
CV = CDVI
DM = DMP*
HN = Honeywell NetAXS
HW = Honeywell ProWatch/WinPak
JC = Johnson Controls
KA = Keyscan
KH = Kantech
M = Mercury
PX = Paxton*
SA = Salto*
SH = Software House
SL = Sielox*
V = HID/VertX
Z = ZKTeco
3
36.12” x 30.125x 7.06”
(917.5mm x 768.1mm x 179.3mm)
BL = Universal Blank Backplane
3
34.0” x 28.0” x 0.3125”
(863.6mm x 711.2mm x 7.9mm)
BV = Brivo
CV = CDVI
HW = Honeywell ProWatch/WinPak
JC = Johnson Controls
M = Mercury
SH = Software House
V = HID/VertX
Door Backplanes for System Expansion:
TMV2 - Trove2 and Trove3 door backplane compatible with Mercury or HID/VertX boards and Altronix sub-assemblies (Fig. 11, pg. 13).
THWD2 - Trove2 and Trove3 door backplane compatible with Honeywell ProWatch/WinPak boards.
Specifications:
Agency Listings:
UL 294 - 6th edition. Trove1 and Trove2 Power Controllers: Line Security I, Destructive Attack I, Endurance IV, Stand-by Power II.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme á la norme NMB-003 du Canada.
CE European Conformity.
Environmental:
Humidity and Temperature conditions as tested by UL (85%, +/-5% @ 30 +/-2ºC), ULC (93%, +/-2% @ 32 +/-2ººC ºC C).
Trove - 3 -
Specifications:
Battery Backup:
Trove1 enclosure accommodates up to two (2) 12VDC/7AH batteries.
Trove2 enclosure accommodates up to four (4) 12VDC/12AH batteries.
Trove3 enclosure accommodates up to four (4) 12VDC/12AH batteries.
Additional Features:
16 Gauge enclosure with ample knockouts for convenient access.
Installation Instructions:
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install
two/three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower
holes. Remove the enclosure. Drill the lower holes and install the two/three fasteners. Place the
enclosure’s upper keyholes over the two/three upper screws. Install the two/three lower screws
and make sure to tighten all screws (refer to enclosure drawings pages 18-20).
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired
location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure
approximately 2” from the right side . Connect tamper switch wiring to (Fig. 1, pg. 3)
the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount boards to backplane, refer to individual Trove installation instructions.
Power Supply Sub-Assembly Specifications:
Altronix
Power Supply Input Rating Output Rating Battery Size for
30 min. Backup Refer to
AL400ULXB2 115VAC, 60Hz, 3.5A 12VDC @ 4A or 24VDC @ 3A 4AH
ULXB Installation Instructions
Rev. ULXB-020419
AL600ULXB 115VAC, 60Hz, 3.5A 12VDC or 24VDC @ 6A 7AH
AL1012ULXB 115VAC, 60Hz, 2.6A 12VDC @ 10A 12AH
AL1024ULXB2 115VAC, 60Hz, 4.2A 24VDC @ 10A 12AH
eFlow4NB* 120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 4A 4AH
eFlow Installation Instructions
Rev. EFNB-021319
eFlow6NB* 120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 6A 7AH
eFlow102NB* 120VAC, 60Hz, 3.5A 12VDC @ 10A 12AH
eFlow104NB* 120VAC, 60Hz, 4.5A 24VDC @ 10A 12AH
* LINQ2 can be installed when utilizing eFlow power supply/charger boards.
Sub-Assembly Specifications:
Altronix UL Listed
Sub-Assembly Description Current Draw Refer to
ACM4(CB) 4 Fused (or PTC) Output
Access Power Controller
12VDC @ 0.4A max. or
24VDC @ 0.2A max. ACM4/ACM4CB Installation Instructions Rev. 052819
ACM8(CB) 8 Fused (or PTC) Output
Access Power Controller
12VDC @ 0.6A max. or
24VDC @ 0.3A max. ACM8/ACM8CB Installation Instructions Rev. 031819
ACMS8(CB) 8 Fused (or PTC) Output
Access Power Controller
12VDC @ 0.6A max. or
24VDC @ 0.3A max. ACMS8/ACMS8CB Installation Instructions Rev. 090518
MOM5 5 PTC Output Power Distribution
Module with Fire Alarm Interface 12-24VDC 55mA max. MOM5 Installation Instructions Rev. 020119
PD4UL(CB) 4 Fused (or PTC) Output
Power Distribution Module N/A PD4UL Installation Instructions Rev. 020119
PD4ULCB Installation Instructions Rev. 020119
PD8UL(CB) 8 Fused (or PTC) Output
Power Distribution Module N/A PD8UL Installation Instructions Rev. 020119
PD8ULCB Installation Instructions Rev. 020119
PD16W(CB) 16 Fused (or PTC) Output
Power Distribution Module N/A PD16W/PD16WCB Installation Instructions Rev. 020119
PDS8(CB) 8 Fused (or PTC) Dual Input
Power Distribution Module N/A PDS8/PDS8CB Installation Instructions Rev. 070116
VR6 Voltage Regulator 24VDC @ 1.75A or 3.5A
Output: 5VDC or 12VDC @ 6A VR6 Installation Instructions Rev. 050517
LINQ2* Network Communication Module 12-24VDC 100mA max. LINQ2 Installation Instructions Rev. 060514
* LINQ2 can be installed when utilizing eFlow power supply/charger boards.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure

Especificaciones del producto

Marca: Altronix
Categoría: No categorizado
Modelo: Trove3SH3

¿Necesitas ayuda?

Si necesitas ayuda con Altronix Trove3SH3 haz una pregunta a continuación y otros usuarios te responderán




No categorizado Altronix Manuales

No categorizado Manuales

Últimos No categorizado Manuales