Emerson 1F83C-11PR Manual de Usario

Emerson Termostatos 1F83C-11PR

Lee a continuación 📖 el manual en español para Emerson 1F83C-11PR (12 páginas) en la categoría Termostatos. Esta guía fue útil para 5 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/12
Electrical Rating:
Battery Power mV to VAC, NEC Class II, Hz ..................................... 30 50/60
Input-Hardwire to VAC, NEC Class II, / Hz .................................... 20 30 50 60
Terminal Load A per terminal, A maximum all terminals combined .......................................... 1.0 1.5
Setpoint Range to F ( to ........................................ 45° 99° 37° C)
Rated Dierentials: Fast Med Slow
Heat (@ °F/ Hr) 6 .................................. 0.5°F 0.75°F 1.9°F
Cool (@ °F/ Hr) . 6 .................................. 0 9°F 1.2°F 1.7°F
Operating Ambient .................................. 32°F to +105°F (0° to +41°C)
Display Temperature Range 32°F to +99°F (0 to 37°C) .......................
Operating Humidity % non-condensing max ................................. 90
Shipping Temperature Range ................... °F to + °F-20 150 (-29° to +65°C)
Thermostat Dimensions ........................... 3-3/4” H x 6” W x 1-1/8” D
PART NO. 37-7478A-EN
1504
1F83C-11PR (Programmable)
Installation and Operating Instructions
80 Series Single Stage Thermostat
Battery Powered or Hardwired with Common
Thermostat Applications
Maximum
Stages
Heat/Cool
Conventional Gas, Oil, Electric (mV and
24V), Heat Only, Cool Only or Heat/
Cool Systems
1/1
Heat Pump (air source or geothermal)
with no Aux. Heat 1/1
Thermostat Installation 2-4
Wiring 2
Installer Menu 3-4
Using the Thermostat 5-7
Thermostat Overview 5
User Menu 6
Thermostat Operation 6
Thermostat Schedule 7
Troubleshooting 7-8
Homeowner Help Line 8
INDEX
SPECIFICATIONS
emersonthermostats.com
white-rodgers.com
MERCURY NOTICE: This product does not contain
mercury. However, this product may replace a product
that contains mercury. Mercury and products containing
mercury must not be discarded in household trash.
Refer to www.thermostat-recycle.org for information
on disposing of products containing mercury.
Optional Accessory: Wall Cover-Up Plate W x F61-2663 6 3/4, 4 1/2” H
2
Terminal Designations Terminal Function
RC* Power for Cooling
RH* Power for Heating
O/B Changeover Terminal-Energized in Heat (B) or Cool (O)
for Heat Pump or Damper Systems
Y** Cooling Relay
G Fan Relay
W** Heating Relay
C Common wire for (optional with batteries)24V
*When both RC and RH wires are present, cut RC/RH jumper (see next page).
**For heat pump systems, add a jumper wire to connect terminals Y and W
THERMOSTAT INSTALLATION
Leveling Thermostat
Leveling is for appearance only and
will not aect thermostat operation.
WIRING
Refer to equipment manufacturer’s instructions for specic system wiring information. After
wiring, see INSTALLER MENU for proper thermostat conguration. Wiring table shown are
for typical systems and describe the thermostat terminal functions.
WARNING
!
Do not use on circuits exceeding specied voltage.
Higher voltage will damage control and could
cause shock or re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will burn
out thermostat and could cause personal injury
and/or property damage.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electrical power to system,
at main fuse or circuit breaker box,until
installation is complete.
Precautions
Do not exceed the specication ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handing or
distorting components could cause the control to malfunction.
3
1.) Gas/Elec Switch
If the system is a heat pump or electric furnace, the GAS/ELEC Switch must be set to
Elec Gas. If your system is a gas or oil furnace, the switch must be set to .
2.) O/B Terminal Switch
The O/B switch on this thermostat is factory set to the position. This will accommodate O
the majority of heat pump applications, which require the changeover relay to be
energized in . If the heat pump being installed requires a terminal, to energize the Cool B
changeover relay in , the O/B switch must be moved to the position. Heat B
3.) RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not
required. If the application provides a separate wire for RC and RH, clip the RC/RH
jumper. This will isolate both terminals so they can be independently used.
INSTALLER MENU
To prevent changes that may aect system performance, this thermostat has an INSTALLER’S
MENU and an USER MENU. The INSTALLER’S MENU provides access to every option, while
the USER MENU provides access to items that will not aect system performance. To access
the INSTALLER’S MENU press the Menu button for 8 seconds. The display will show item 30 in
the table below. Use Next and Back to navigate through menu items. Press or to change
a menu setting.
Installer’s Menu #
(Hold Menu 8 Seconds) Description Default Setting
(ashing icons)
Settings
(Press or )
30 Heat Cycle Rate (how often
the heat will turn on) MEd
SLO – slow
MEd – medium
FAS – fast
35 Cool Cycle Rate (how often
the cooling will turn on) MEd
SLO – slow
MEd – medium
FAS – fast
50 Compressor Lockout
(protects the compressor
from short cycling)
OFF On minute display 5
OFF – no delay
65 Maximum Heat Limit
(maximum set point for heat mode) 99 47 99to
66 Minimum Cool Limit (minimum
set point for cool mode) 45 45 97to
74 Schedule Type (set as either -Day, 7
5-1-1 Day or Non-Programmable) 5
7 – 7 Day
5 – 5-1-1 Day
0 – Non Programmable
(Installer Menu continued on next page)
1
3
2
Baery Locaon
Premium AA alkaline batteries
are required when C-wire is
not available. When C-wire is
available, the batteries provide
a back-up source of power (this
will maintain the clock in the
event of a power outage).
4
Installer’s Menu #
(Hold Menu 8 Seconds) Description Default Setting
(ashing icons) Settings
76
Early Start (starts heating or
cooling early so your programmed
temperature is reached by the
programmed time)
OFF
On – start early
OFF – start at program
period time
79 Fahrenheit or Celsius °F °F – Fahrenheit
°C – Celsius
81
Temperature Display
Adjustment (adjust the displayed
“Room Temperature”)
0-5 to +5
83 Continuous Display Light (keep
the backlight always on – “C” wire
required)
OFF On – always on
OFF – momentarily
86 Change Air Filter (set up a
monthly reminder) OFF
1 to 12 reminder time
(months)
OFF – no lter reminder
99 Keypad Lock (prevent unwanted
changes to the thermostat) OFF
On – disable buttons
OFF – all buttons are
active
INSTALLER MENU (C0ntinued)
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to . Heating System
1.) Move fan switch to On position. The blower should begin to operate.
2.) Move fan switch to Auto position. The blower should stop immediately.
Heating System
1.) Move System Heat Switch to position.
2.) Press to adjust thermostat setting to above room temperature. The system should
begin to operate and the thermostat will indicate . Heat On
3.) Press to adjust thermostat setting below room temperature. The heating system
should stop operating and the thermostat should indicate Heat.
Cooling System
1.) Move System Cool Switch to position.
2.) Press to adjust thermostat setting below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate There can be up to a Cool On. 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press to adjust thermostat setting to above room temperature. The cooling system
should stop operating and the thermostat will indicate Cool.
Note: If is shown on the display, the compressor lockout feature is operating. Starting Soon
There will be up to a minute delay before the compressor turns on.(see INSTALLER MENU, 5
item )50
CAUTION
!
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational
for hours and the system has not been operational for at least minutes. 6 5
5
THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and
the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS AND SWITCHES THE DISPLAY
1. 10.)) Fan Switch Thermostat is protecting the equipment from short
cycling ( minute delay)5-
2 11.).) System Switch Indicates that the system is running in cool or heat
3.) Backlight Button (located on the top
of the thermostat
12.) Displays the current time
4 13.).) Set Correct Time Battery status indicator
5.) Hold a Permanent Temperature Low battery indicator14.)
6.) Cancels Hold – Returns to Programmed
Schedule
15.) Day of the week used when programming a schedule
7.) Raises Temperature Setting 16.) Permanent hold (bypassing the schedule)
8.) Access Menu Options 17.) Temperature setpoint
9.) Lowers Temperature Setting 18.) Appears when the keypad is locked (to prevent unwanted
changes)
19.) is used to navigate within a menuNext (Menu button)
20.) Access the schedule and customize thermostat features
21.) Back (Run button) is used to navigate within a menu
22.) Exit (Hold button) returns to the home screen
23.) SEE TROUBLESHOOTING
USING THE THERMOSTAT
1
2
3
4 5 6
7
8
9
10
11
12 13 14 15 17
18
19
20
21
22
16
23
Whenever Replace appears in the display, new premium brand AA alkaline batteries
should be installed. If the house will be unoccupied for an extended period and either
or “ Replace
” is displayed, install new batteries before leaving.
6
THERMOSTAT OPERATION
Set Current Time and Day
Note: Time icons will ash at initial power up or after a reset.
1.) Press Set Time
2.) Use or to adjust the hour
3.) Press Next to advance to set the minutes and day of the week
4.) Press Exit when nished.
The default program is , but can be setup as a or 5-1-1 Day 7-Day Non-Programmable
thermostat (refer to the above) User Menu
Hold Temperature (bypassing the schedule) With the switch set to or System Heat
Cool Hold Hold, momentarily press the button. will be displayed. Use or to adjust
the temperature. The thermostat will hold the room temperature at the selected setting
until you press to start program operation again. Run
Program Override (Temporary Hold) – Press or until the desired temperature is
displayed. The thermostat will override the schedule until the next programmed time
period with a minimum override of hours. Then the thermostat will automatically revert 2
to the program.
Keypad Lockout To prevent unwanted changes, the buttons can be disabled. To turn
this feature On, press and hold and the button Menu unl the icon appears (this can
also be turned on in the menu). To turn O, press and hold and the button for Menu 3
seconds.
USER MENU
To customize thermostat settings, press the button from the home screen. Use the Menu
or buttons to highlight and press and to navigate Settings Next. Use Next Back
through menu items. Press or to change the setting.
User’s Menu #
(Press Menu button
and release)
Description Default Setting
(ashing icons)
Settings
(Press or )
01 Schedule Type (set as either -Day, 7
5-1-1 Day or Non Programmable) 5
7 – 7 Day
5 – 5-1-1 Day
0 – Non-programmable
02
Early Start (starts heating or
cooling early so your programmed
temperature is reached by the
programmed time)
OFF
On – start early
OFF – start at program
period time
03 Fahrenheit or Celsius °F °F – Fahrenheit
°C – Celsius
04 Temperature Display Adjustment
(adjust the Room Temperature) 0 -5 to +5
05
Continuous Display Light (keep
the backlight always on – “C” wire
required)
OFF On – always on
OFF – momentarily
06 Change Air Filter (set up a monthly
reminder) OFF
1 12to – reminder time
(months)
OFF – no lter reminder
07 Keypad Lock (prevent unwanted
changes to the thermostat) OFF On – disable buttons
OFF – all buttons are active

Especificaciones del producto

Marca: Emerson
Categoría: Termostatos
Modelo: 1F83C-11PR

¿Necesitas ayuda?

Si necesitas ayuda con Emerson 1F83C-11PR haz una pregunta a continuación y otros usuarios te responderán