PRODUCT DATA
69-1960ES-01
Retrofit Round Damper (RRD)
APPLICATION
The RRD is a round damper that is easily inserted into rigid
round ducts for retrofit zoning in forced air heating and cooling
systems. It is available in four sizes for use in 5”, 6”, 7”, and 8”
ducts.
The damper is used with Honeywell TrueZONE®,
EnviraZONE™ and similar zone control systems. The power
open, power closed actuator draws 2 VA allowing multiple
dampers per zone, but delivers high torque for reliable
operation.
FEATURES
Easy slide-in installation
2 VA allows for many dampers on one zone
Available in 4 sizes to fit most rigid round branch ducts
Quiet, long life motor automatically shuts itself off in
full open and closed positions.
Gaskets around blade and under motor housing for
low internal leakage and very low external leakage
Range stops with easy adjustment from top of motor
Easy to see and reliable mechanical blade position
indicator
Easy to hook up with conventional thermostat wire
Simple manual blade positioning with push button
gear release
SPECIFICATIONS
IMPORTANT
The specifications given in this manual do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifica-
tions. In addition, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 1
Ordering Information ......................................................... 2
Installation ........................................................................ 3
Wiring ............................................................................... 3
Adjustments ...................................................................... 4
Checkout .......................................................................... 4
Troubleshooting ................................................................ 4
RETROFIT ROUND DAMPER (RRD)
69-1960ES—01 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Construction
Frame: 18 gauge G-60 or G-90 galvanized steel C channel
with gasket, 20 gauge actuator mounting bracket.
Blade: 20 gauge G-60 or G-90 galvanized steel surrounded by
a black EPDM rubber gasket.
Shaft: 1/2” hex damper blade shaft of cold rolled zinc electro-
plated steel. The shaft runs through a white nylon bushing.
Sizes: 5.125”, 6.125”, 7.125”, 8.125” diameters
Electrical Rating: 24 VAC, 50 or 60 Hz
Power Consumption: 1.5 watts running. Transformer sizing
VA: 2.
Wiring Terminals: Screw terminals for 14 to 26 gauge wire
labeled: M1 (Common), M4 (counter-clockwise, open),
M6 (clockwise, closed)
Nominal Angular Rotation: 90°
Torque: 45 in. lb, (5 Nm)
Nominal Timing: 90 seconds independent of load
Ambient Ratings: -40° F (-40° C) to 122° F (50° C), 5-95%
RH non-condensing
Mounting: Direct couple to 1/2” shaft
Agency Listings: NEMA 1, UL listed, class two
Dimensions: See Fig. 1–2
Weight:
RRD5: 3.6 lb
RRD6: 3.8 lb
RRD7: 4.1 lb
RRD8: 4.3 lb
Leakage (Closed): 3.4% at .5” WC
Pressure Drop (Open): <.05” WC
Fig. 1. Motor dimensions in in. (mm).
Fig. 2. RRD damper.
NEMA1
1
0
M31212A
2-19/32
(66)
57/64
(22)
3-5/8
(92)
MANUAL BLADE RELEASE
ROTATION DIRECTION
RANGE STOPS
2-9/32
(58)
7/32 (5.55)
2-9/32
(58)
4-33/64
(114.7)
WIRING
TERMINALS
POSITION INDICATOR
NEMA1
M31213
10-3/4 (273)
2-3/4
(70)
5-3/8 (137)
2-5/8
(67)
1/2 (13)
1/2
(13)
RETROFIT ROUND DAMPER (RRD)
3 69-1960ES—01
INSTALLATION
Before Installing this Product
1. Read all instructions before installing this product. Fail-
ure to follow instructions can damage the product or
cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to verify that the product is suitable for your
application.
3. Installer must be a trained and experienced service tech-
nician.
4. Install the product in an area that is easily accessible for
checkout and service.
5. After completing installation, use these instructions to
check out product operation.
Installing the Retrofit Round Damper
Select a location for the damper in the ductwork. It is
suggested that the RRD damper be at least 6 feet from the
register for quiet operation.
1.
Peel off the back of the cut-out template. Carefully align
the template with the centerline of the duct. Apply tem-
plate to the section of round ductwork where the damper
is to be installed. Ensure that the template is parallel to
the ductwork. It is suggested that the damper be installed
with the motor under a horizontal duct to reduce twist to
the duct. It may also be necessary to support the duct.
2. Drill a starter hole in the cut-out area of the template.
3. Cut out the area between the holes.
4. Slide the damper into the duct and secure it with the four
supplied self-drilling mounting screws. Be careful to
avoid over-tightening the screws as the duct may be
pulled out of round. See Fig. 3.
Fig. 3. Inserting RRD damper into duct.
WIRING
Wiring the Motor Actuator
Connect the motor to the zone control panel 18 or 20 gauge
wire. The motor terminals are labeled M1 for common, M4 for
open, and M6 for closed. Connect the motor terminals to
corresponding terminals on zone control panel for each zone.
See Fig. 4–6 for hookups.
Multiple RRD dampers can be wired to one zone when wired in
parallel. See Fig. 5 for wiring multiple dampers together in a
daisy chain manner or Fig. 6 using wire nuts. See Table 1 for
the maximum number of dampers that can be connected to
each zone control panel. Note that this is the total number of
dampers connected to all the zones of a zone control panel;
the maximum dampers per zone is 14. If more than 14
dampers are on one zone, a Slave Damper Control Relay
(SDCR) must be used.
When more than the maximum number of dampers allowed
per panel are necessary, a SDCR must be used. The SDCR is
an isolation relay that is powered by a separate transformer so
that it relieves the panel of this additional load. When a SDCR
is used, the dampers of that zone may either be all connected
to the SDCR, or some dampers may be wired to the SDCR and
the remainder to that zone’s damper terminals.
*Maximum of 14 dampers per zone
Fig. 4. RRD wired to zone control panel.
Fig. 5. Wiring multiple RRD dampers in
daisy chain fashion.
M31220
Maximum number of dampers per zone.
One 40 VA
Transformer
Two 40 VA
Transformers (or
One 75 VA)
TrueZONE® Panels* 13 27
W8835* 12 26
SDCR 15 28
R Y W G C M6 M4 M1
R Y W G
ZONE
1, 2, 3, ETC.
M1
M4
M6
M31217
ZONE
THERMOSTAT
R Y W G C M6 M4 M1
R Y W G
ZONE
1, 2, 3, ETC.
M 1
M 4
M 6
M1
M4
M6
M31218
ZONE
THERMOSTAT

Especificaciones del producto

Marca: Honeywell
Categoría: campana extractora
Modelo: RRD6

¿Necesitas ayuda?

Si necesitas ayuda con Honeywell RRD6 haz una pregunta a continuación y otros usuarios te responderán




campana extractora Honeywell Manuales

Honeywell

Honeywell RRD6 Manual de Usario

12 Septiembre 2024

campana extractora Manuales

Últimos campana extractora Manuales