System Sensor SPRK Manual de Usario

Lee a continuación 📖 el manual en español para System Sensor SPRK (4 páginas) en la categoría Vocero. Esta guía fue útil para 7 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/4
SS-140-000 1 I56-3108-004R
FIGURE 1. WIRING DIAGRAM:
INPUT FROM
AMPLIFIER
OUTPUT NEXT TO
DEVICE OR EOL
(+)
(–) (+)
(–)
A0380-00
PRODUCT SPECIFICATIONS
Operating Temperature Standard K Series32°F to 120°F (0°C to 49°C) –40°F to 151°F (–40°C to 66°C)
Humidity Range Standard K Series10% to 93% Non-condensing Meets NEMA 4X and IP56 rating requirements
Nominal Voltage 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage 50 VDC
Speaker Frequency Range 400 - 4000 Hz
Power Settings 1/ , 41/ , 1, 2 watts2
Input Terminal Wire Guage 12-18 AWG
Dimensions for Speakers and Accessories NOTE: V suffix refers to high volume device, C suffix refers to ceiling device.
Wall Product Length Width Depth Ceiling Product Diameter Depth
SP Speaker SPC Speaker6.0˝ 5.0˝ 2.8˝ 6.8˝ 2.8˝
SPV Speaker SPCV Speaker6.0˝ 5.0˝ 2.9˝ 6.8˝ 2.9˝
Weatherproof Back Box** Weatherproof Back Box**6.5˝ 5.5˝ 2.9˝* 7.2˝ 2.9˝*
Surface Mount Skirt Surface Mount Skirt6.5˝ 5.5˝ 2.7˝* 7.2˝ 2.7˝*
*Depth above finished surface of wall or ceiling.**Weatherproof back box dimensions do not include the two mounting tabs.
Mounting Box Options
Indoor Products K Series Products
4 × 4 × 21/ or deeper8
MWBB - red wall metal weatherproof back box
MWBBW - white wall metal weatherproof back box
MWBBCW - white ceiling weatherproof back box
The indoor SP, SPV, SPC, and SPCV Series are suitable for dry and damp environments.
The “K” Series models are suitable for use in both indoor and outdoor applications.
NOTICE: This manual shall be left with the owner/user of this equipment.
The “K” models are suitable for outdoor use in wet environments with out-
door backbox supplied with the product.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range
of indoor and outdoor speakers for wall and ceiling applications, indoors and
outdoors. They are designed to be used at either 25 or 70.7 volts, and operate
at any one for four input power levels. These products are electrically back-
ward compatible with the previous generation of SpectrAlert speakers. With
its low total harmonic distortion, the SpectrAlert Advance SP series offers
high fidelity sound output. The SpectrAlert Advance SPV series offers greater
sound output at every tap setting for applications with high ambient noise
levels. Wall and ceiling products may be used interchangeably (wall products
may be used on the ceiling and ceiling products may be used on the wall). K
Series products are designed to be used over a wider range of temperatures
and are suitable for use in wet locations.
FIRE ALARM SYSTEM CONSIDERATIONS
All wiring must be installed in compliance with the National Electrical Code
(NEC) and applicable local codes. System Sensor recommends installing fire
alarm speakers in compliance with NFPA 72, ANSI/UL1480 and NEC 760.
Electrical Wiring
1. Connect the speaker as shown in Figure 1.
NOTE: Do not loop electrical wiring under terminal screws. Wires con-
necting the device to the control panel must be broken at the device
terminal connection in order to maintain electrical supervision.
2. There are two rotary switches on the back of the product. The first switch
is used to select either 25 or 70.7 volts input. The second switch is used
to select the input power of 1/ , 41/ , 1 or 2 watts.2
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SpectrAlert Advance SP and SPV Series
Dual Voltage Speakers for
Fire Protective Signaling Systems
For use with the following models: SPR, SPW, SPRV, SPWV, SPRK, SPWK, SPCW,
SPCR, SPCWV, SPCRV, and SPCWK
I56-3108-004R
Figure 2.Speaker WaTTage and VoLTage SeTTingS:
A0419-00
ShorTing Spring
NOTE: A shorting spring is provided between terminals 2 and 3 of the mount-
ing plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system.
Figure 3:
SHORTING SPRING
A0381-00
TabLe 1. Sound LeVeLS For eaCh TranSFormer poWer Tap:
UL Reverberant (dBA @ 10 ft.) SP, SPC SPV, SPCV
2W 86 90
1W 83 87
1/ W 80 842
1/ W 77 814
NOTE: V suffix refers to high volume device,
C suffix refers to ceiling mount device.
CAUTION
Signal levels exceeding 130% rated signal voltage can damage the speaker.
Consequently, an incorrect tap connection may cause speaker damage. This
means that if a 25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select the proper taps for the
amplifier voltage/input power level combination being used.
mounTing indoor WaLL or CeiLing produCTS
1. Attach mounting plate to junction box as shown in Figures 4 and 5. The
mounting plate is compatible with 4˝ x x 2
1/8˝ junction boxes. If using
a back box skirt or trim ring, attach the mounting plate to the skirt or
trim ring and then attach the entire assembly to the junction box (see
Figures 4, 5, 6 and 7).
2. Connect field wiring to terminals, as shown in Figure 1.
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate.
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on the mounting plate.
5. Then, swing product into position to engage the pins on the product with
the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front
of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
k SerieS mounTing
1. K Series products may be used indoors or outdoors. They must be in-
stalled using the proper SpectrAlert Advance weatherproof back box. Do
not attempt to use boxes other than those specified for use with the
product.
2. The plastic weatherproof back box is equipped with removable side
flanges for mounting. The back box may be secured directly to the wall
or ceiling using the flanges(plastic or metal back boxes) or by using the
knockout plugs(plastic back boxes). Knockout plugs are provided to
mount directly to the wall or ceiling or to a 1900 weatherproof electrical
box, see Figure 12.
3. Threaded holes are provided in the sides of the box for ¾ inch conduit
adapters. Knockout plugs in the back of the box can be used for ½ or
¾ inch rear entry. Unused holes must be sealed. Plugs and O-Rings are
provided with the box for this purpose.
4. It is the responsibility of the installer to make sure that all openings and
connections are sealed properly. Outdoor installations that are protected
from direct exposure to rain are still subject to condensation or leakage
through hidden areas, such as a soffit.
5. Water may pool on the back box due to condensation or direct exposure
to rain or snow. Use watertight fittings for all wiring connections, includ-
ing the knockout plugs on the back of the box. When using the plastic
plugs to fill unused threaded holes, make sure the O-rings supplied are
properly positioned on the plug. The plugs must be sealed with PTFE
thread seal tape.
SS-140-000 2 I56-3108-004R
UL ANechoic (dBA @ 10 ft.) SP, SPC SPV, SPCV
2W 88 93
1W 86 90
1/ W 83 872
1/ W 80 844
6. Attach the mounting plate to the weatherproof back box using the four
non-painted screws.
7. Follow steps 2-5 of the indoor mounting instructions to wire and attach
the product. The product must be mounted to the weather proof back
box using the painted screws (wall product has 4 screws, ceiling product
has 3 screws)
CAUTION
The ‘hold-in-place’ snaps are not intended to secure the product to the back
box. The product must be secured to the back box using the screws provided
Figure 4. WaLL mounT produCT WiTh Trim ring:
A0382-00
Figure 5. CeiLing mounT produCT WiTh Trim ring:
A0383-00
Figure 6. WaLL mounT produCT WiTh baCk box SkirT :
A0386-00
Figure 7. CeiLing mounT produCT WiTh baCk box SkirT :
A0385-00
SS-140-000 3 I56-3108-004R
Figure 8. ouTdoor WaLL mounT produCT WiTh pLaSTiC
WeaTherprooF baCk box:
A0384-00
Figure 9. ouTdoor CeiLing mounT produCT WiTh pLaSTiC
WeaTherprooF baCk box:
A0420-00
Figure 10. ouTdoor WaLL mounT produCT WiTh meTaL
WeaTherprooF baCk box:
A0410-00
Figure 11. ouTdoor CeiLing mounT produCT WiTh meTaL
WeaTherprooF baCk box:
A0407-00
A0424-00
Figure 12. For knoCkouTS uSe a FLaT bLade SCreWdriVer.
NOTE: Place the blade along
the edge of the slot and slowly
work your way around the slot
as you strike the srewdriver.

Especificaciones del producto

Marca: System Sensor
Categoría: Vocero
Modelo: SPRK

¿Necesitas ayuda?

Si necesitas ayuda con System Sensor SPRK haz una pregunta a continuación y otros usuarios te responderán




Vocero System Sensor Manuales

Vocero Manuales

Últimos Vocero Manuales