Altronix ReServ 3WP Manual de Usario
Altronix
Unión Postal Universal
ReServ 3WP
Lee a continuación 📖 el manual en español para Altronix ReServ 3WP (8 páginas) en la categoría Unión Postal Universal. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios
Página 1/8
Outdoor Video Surveillance UPS
Installation Guide
Models Include:
ReServ1WP
- Twelve (12) true sine wave regulated 24VAC outputs
and Four (4) regulated 12VDC outputs.
- 4 amp total supply current @ 24VAC and 2 amp total supply current @ 12VDC.
- PTC protected power-limited outputs.
ReServ2WP
- Sixteen (16) true sine wave regulated 24VAC outputs.
- 4 amp total supply current.
- PTC protected power-limited outputs.
ReServ3WP
- Sixteen (16) regulated 12VDC outputs.
- 8 amp total supply current.
- PTC protected power-limited outputs.
Rev. 082610 More than just power.™
- 2 - ReServWP
Overview:
ReServWP Outdoor Video Surveillance UPS units are designed to provide power for 24VAC and/or 12VDC cameras during
normal or power outage conditions. True sine wave regulated AC outputs and/or regulated DC outputs.
ReServWP Series Outdoor Video Surveillance UPS Configuration Reference Chart:
Altronix
Model Number
Output/Supply
Current (Amp
Ambient
Temperature
Input Rating
PTC Protected
Power-Limited
Outputs
24VAC Outputs
12VDC Outputs
Agency Listings
UL Listings
and
File Numbers
ReServ1WP
24VAC @ 4 amp (100VA)
and 12VDC @ 2 amp -33º - 30º C 115VAC
60Hz,
3.5 amp
16 12 4
UL File # E329542
UL 60950-1
UL/CUL Listed
for
Information
Technology
Equipment.
UL 60950-22
Information Technology
Equipment - Safety -
Part 22: Equipment to
be Installed Outdoors
24VAC @ 3.5 amp (85VA)
and 12VDC @ 2 amp -33º - 42º C
ReServ2WP
24VAC @ 4 amp (100VA) -33º - 30º C 115VAC
60Hz,
3.5 amp
16 16 ----
24VAC @ 3.5 amp (85VA) -33º - 42º C
ReServ3WP 12VDC @ 8 amp -33º - 42º C
115VAC
60Hz,
3.5 amp
16 16----
Specifications:
Stand-by Specifications:
Stand-by Batteries
ReServ1WP - 4 amp (100VA) load at 24VAC and 2 amp load at 12VDC max.
ReServ2WP - 4 amp (100VA) max. load at 24VAC
ReServ3WP - 8 amp (100VA) max. load at 12VDC
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
Installation Instructions:
This installation should be made by qualified service personnel and should conform to all local codes and in accordance
with the National Electrical Code. This product contains no serviceable parts.
1. Remove back plate inside the enclosure by removing four (4) mounting screws.
2. Mark and drill desired knockouts on the enclosure to facilitate wiring .(Fig. 1, pg. 3)
It is required to use UL Listed outdoor rated conduit hubs with a minimum outdoor rating of 4X.Note:
3. Secure back plate inside the enclosure with four (4) mounting screws.
4. Mount unit in the desired location with the appropriate fasteners utilizing the holes provided on the
enclosure’s flanges . Secure enclosure to earth ground. (Pgs. 7 and 8)
This product needs to be secured to the building/pole before operation.Note:
5. Connect AC power mains to the terminals marked [L] and [N], .(Figs. 2-3, pg. 5-6)
Output:
• PTCprotectedpower-limitedoutputsarerated@1amp.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhenACfails.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
Visual and Audio Indicators:
• AC/DCpowerLEDindicators.
• IndividualpoweroutputLEDindicators.
• LowvoltageinputandShutdownLEDindicators.
• AudioACFailandBatteryFailindicator.
Additional Features:
• TruesinewaveregulatedACoutputs(ReServ1WPand
ReServ2WP). Regulated DC outputs (ReServ1WP and
ReServ3WP).
• Unitmaintainscamerasynchronization.
• Easeofinstallationsavestimeandeliminatescostlylabor.
Enclosure Dimensions :(H x W x D)
• NEMA4/IP66Ratedenclosure.
• Accommodatesuptotwo(2)12VDC/7AHbatteriesor
two (2) 12VDC/12AH batteries.
17.375”x12”x6.5”(441.3mmx304.8mmx165.1mm)
ReServWP - 3 -
Use18AWGorlargerforallpowerconnections(Battery,output)(Figs. 2-3, pg. 5-6).
Use18AWGto22AWGforpower-limitedcircuits(ACFail/LowBatteryreporting)(Figs. 2-3, pg. 5-6).
A readily accessible disconnect device shall be incorporated in the building installation wiring.Note:
Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
6. The LEDs on the power supply board will illuminate when AC power is present.
7. Measure output voltage before connecting cameras/devices to outputs. This helps avoiding potential damage.
8. ReServ3WP only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the board prior
to connecting devices.
9. Connecting cameras/devices:
- Connect 12VDC cameras/devices to the terminals marked [P 1-4, N 1-4] .ReServ1WP (Fig. 2, pg. 5)
Connect 24VAC cameras/devices to the terminals marked [5-16] .(Fig. 2, pg. 5)
- Connect 24VAC cameras/devices to the terminals marked [1-16] .ReServ2WP (Fig. 2, pg. 5)
- Connect 12VDC cameras/devices to the terminals marked [P 1-16, N 1-16] .ReServ3WP (Fig. 3, pg. 6)
10. Connect batteries to the terminals marked [--BAT+] . Use two (2) 12VDC batteries connected in (Figs. 2-3, pg. 5-6)
series for 24VDC operation (battery leads included).
Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH) or NP7-12 (12V/12AH), Ultratech UT1270
(12V/7AH) or Ultratech UT12120 (12V/12AH).
11. ConnectappropriatesignalingnotificationdevicestoACFAILandBATFAIL(Figs. 2-3, pg. 5-6)
supervisory relay outputs.
12. The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present . (Figs. 2-3, pg. 5-6)
If any of the power LEDs are not illuminated the cause may be due to the following:Note:
a. AC mains and battery fail.
b. One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
c. Unit damaged/defective.
To reset the PTC:
1. Disconnect corresponding camera/device connected to terminals marked [1-16] .(Figs. 2-3, pg. 5-6)
2. Eliminate the trouble condition (short circuit or overload).
3. Allow 1 minute for PTC to cool off (reset).
4. Connect corresponding cameras/devices to terminals marked [1-16] .(Figs. 2-3, pg. 5-6)
5. Power LEDs will illuminate indicating power has been restored to outputs .(Figs. 2-3, pg. 5-6)
WARNING: This installation should be made by qualified service personnel and should conform to all
local codes and in accordance with the National Electrical Code.
Right PanelLeft Panel
Suggested Locations
for Wire Entries
Bottom Panel
Fig. 1
Especificaciones del producto
Marca: | Altronix |
Categoría: | Unión Postal Universal |
Modelo: | ReServ 3WP |
¿Necesitas ayuda?
Si necesitas ayuda con Altronix ReServ 3WP haz una pregunta a continuación y otros usuarios te responderán
Unión Postal Universal Altronix Manuales
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
Unión Postal Universal Manuales
- Unión Postal Universal AEG
- Unión Postal Universal IKEA
- Unión Postal Universal HP
- Unión Postal Universal Apc
- Unión Postal Universal Lenovo
- Unión Postal Universal Tripp Lite
- Unión Postal Universal Energenie
- Unión Postal Universal Voltcraft
- Unión Postal Universal Adj
- Unión Postal Universal Digitus
- Unión Postal Universal LevelOne
- Unión Postal Universal Eaton
- Unión Postal Universal CyberPower
- Unión Postal Universal Block
- Unión Postal Universal Avocent
- Unión Postal Universal Minuteman
- Unión Postal Universal Maruson
- Unión Postal Universal V7
- Unión Postal Universal Phoenix Contact
- Unión Postal Universal Puls Dimension
- Unión Postal Universal Salicru
- Unión Postal Universal Equip
- Unión Postal Universal Murr Elektronik
- Unión Postal Universal Ditek
- Unión Postal Universal Bxterra
- Unión Postal Universal Middle Atlantic
- Unión Postal Universal FSP
- Unión Postal Universal Atlantis Land
- Unión Postal Universal PowerWalker
- Unión Postal Universal FSP/Fortron
- Unión Postal Universal Online USV
Últimos Unión Postal Universal Manuales
24 Octubre 2024
22 Octubre 2024
22 Octubre 2024
22 Octubre 2024
20 Octubre 2024
18 Octubre 2024
18 Octubre 2024
12 Octubre 2024
12 Octubre 2024
12 Octubre 2024