Emko ECO PID+ Manual de Usario

Lee a continuación 📖 el manual en español para Emko ECO PID+ (4 páginas) en la categoría Controlador de temperatura. Esta guía fue útil para 3 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/4
3
2
1
45
6
Eco PID+, PID Temperature Control Un t
- 4 d g t process (PV) and 4 d g t set (SV) d splay� � � �
- Temperature sensor nput (TC,RTD)
- Programmable ON/OFF, P, PI, PD and PID control forms
- Adaptat on of PID Coeff c ents to the system w th Self-Tune and Auto-Tune � �
- Programmable Heat ng or Cool ng Funct ons for Control Output � �
- Selectable Alarm Funct ons for Alarm Output
- Ser al RS485 Commun cat on (opt onal) � �
Introducton Brochure. ENG EcoPID+ 01 V00 03/22
Easy Access D agram For Program Parameters
Panel Mount ng
Enter Password w th ncrement� �
or decrement buttons.
Approve password
w th Enter button
Password Screen
Eco ser es temperature controllers are des gned for measur ng and controll ng a � �
temperature value. They can be used n many appl cat ons w th the r TC and RTD � �
temperature measurement nput, mult -funct on control outputs, selectable alarm � �
funct ons.
They are ma nly used � �n glass, plast c, petro-chem stry, text le, automot ve and mach ne � �
product on � � ndustr es. Accurate and advanced controll ng � �s performed w th selectable
ON-OFF, P, PI, PD, PID and Self Tune/Auto Tune PID funct ons.
SPECIFICATIONS
Process Input: Thermocouple (TC): J, K, R, S, T and L (IEC584.1)(ITS90)
Thermores stance (RTD): Cu-50 and PT-100 (IEC751)(ITS90)
Measurement Range: Please refer to process nput type select on � �n process menu
parameters sect on.
Accuracy:
Thermocouple (TC):( ± 0.25% of full scale or ± 3ºC, wh ch one � �s greater) ±1 d g t max. � �
Thermores stance (RTD):( ± 0.25% of full scale or ± 2ºC, wh ch one � �s greater) ±1 d g t � �
max.
Cold Junct on Compensat on: Automat cally ±0.1°C/1°C
L ne Compensat on: Max mum 10 Ohm
Sensor Break Protect on: Upscale
Sampl ng Cycle: 0.1 second
Input F lter: Programmable
Control Form: ON/OFF, P, PI, PD or PID (Control form can be programmed by the user)
OUTPUT
Process Output: Relay (5A@250V at res st ve load) or SSR Dr ver Output V� �
(Max mum 10mA, Max. 12V )Z
Alarm Output: Relay (5A@250V at res st ve load)V� �
SUPPLY VOLTAGE (It must be determ ned � �n order)
230V 15%) 50/60Hz - 4VAV
115V (±15%) 50/60Hz - 4VAV
100-240V 50/60Hz - 4VAV
24V (±%15) 50/60Hz - 4VAV
24V (±%15) 50/60Hz - 4VAW
10...30V - 4W Z
DISPLAY
Process D splay: 16 mm Red 4 d g t LED D splay� �
Set Value D splay: 9 mm Orange 4 d g t LED D splay� �
Led Ind cators: PO1 (SSR Process Output Status Led), PO2 (Relay
Process Output Status Led), AL1, AL2 (Alarm Output Status Leds),
ºC, ºF LEDs
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS
Operat ng Temperature: 0...50ºC
Hum d ty :� � 0-90%RH (none condens ng)
Mechan cal Impacts: 1Joule (IK06)
Protect on Class: NEMA 4X (IP65 at front, IP20 at rear)
We ght: 150 gr.
D mens on: 48 x 48 mm, Depth: 86,5 mm
Panel CutOut: 46 x 46 mm
*1 - ON/OFF Hysteres s parameter s not act ve unless parameter s set as . � �
*2 - Soft Start parameters( , , ) s not act ve unless parameter s set as .� �
*3 - Soft Start Control Output and Soft Start Control T me parameters s not act ve f parameter � �
s set as .
*4 - PID control parameters are not act ve unless parameter s set as .� �
*5 - Alarm-2 parameters are not act ve f parameter s set as .� �
*6 - Commun cat on parameters are not act ve on dev ces have no commun cat on module.� � � �
*7 - If s d fferent from 0 and user enters to program menu w thout enter ng the password� �
Prot menu s not shown.
Note: User can ex t from any parameter screen w thout sav ng the values by press ng button. If � �
no operat on for 120 seconds, dev ce automat cally return to ma n screen. � �
Easy Access D agram For Sensor Break Output
Value From Ma n Screen
Change the sensor break
output value w th ncrement� �
or decrement buttons.
Press Enter button to save
new sensor break output value
and ex t.
Ma n Screen Ma n Screen� �
Note1: User can ex t from parameter screen w thout sav ng the � �
values by press ng button. If no operat on for 120 seconds, dev ce � �
automat cally ex ts from parameter screen.� �
Note2: Sensor break output value can be adjusted on programm ng
sect on too.
Tune Operat on
Start ng the Tune operat on� �
1- Enter to the parameter n menu and select
or ,then press button for sav ng parameter and turn to ma n � �
screen. Or eas ly press button for 3 seconds* n ma n screen. � �
2- Observe that bl nks n set d splay.� �
*Only Self Tune can be started by th s way.
Cancel ng Tune operat on:� �
1- If sensor breaks;
2- If tune operat on can not be completed n 8 hours;� �
3- Wh le heat ng self tune s runn ng, f process value becomes � �
greater than process set value;
4- Wh le cool ng self tune s runn ng, f process value becomes less � �
than process set value;
5- Wh le tune operat on s runn ng, f user changes the process set � �
value;
6- Wh le tune operat on s runn ng, f user changes the � �
parameter n menu;
Then tune operat on s canceled, dev ce cont nues to run w th former � �
PID parameters w thout chang ng PID parameters.� �
PID TEMPERATURE CONTROL UNIT
PID+
Eco
D mens ons� �
48 mm / 1.89 nch
48 mm / 1.89 nch
6 mm / 0.24 nch80,52 mm / 3.17 nch
Max mum 9 mm / 0.35 nch� �
1- Before mount ng the dev ce n your panel, � �
make sure that the cutout s of the r ght s ze. � �
2- Check front panel gasket pos t on.� �
3- Insert the dev ce through the cutout. If the
mount ng clamps are on the un t, put out them � �
before nsert ng the un t to the panel.� �
4- Insert the mount ng clamps to the two of
des gnated holes that located four s des of � �
dev ce.
5- Drag the mount ng clamps n d rect on 5 � � �
unt l the dev ce completely mmob le w th n the � �
panel.
6- In order to remove dev ce push on the
mount ng clamp as shown w th arrow 6 and � �
pull back.
Access and Change Set Values
Press ncrement or decrement
button to change process set value.
Press Enter button to save new
set value and return the ma n screen.
Ma n ScreenMa n Screen
Temperature Set Value Parameter (Default: 200) MODBUS ADDRESS: 40000
a
Note-1: User can ex t from set value sect on w thout sav ng the values by press ng button. If no � �
operat on for 120 seconds, dev ce automat cally ex ts from Set Value sect on. � �
Note-2: Set value can be adjusted between Set Value Low and H gh L m t ( - ). � �
Press Program button
to access password screen.
Electr cal W r ngs � �
To reduce the effect of electr cal no se on dev ce, low voltage l ne (espec ally sensor� �
� � nput cable) w r ng must be separetely from h gh current and voltage l ne. If poss ble,
use sh elded cable and sh eld must be connected to ground only one s de.� �
c
Note-1: External Fuse s recommended.
Note-2: Stranded cable cross sect on: 1,5mm², Sol d cable cross-sect on: 2,5mm²� �
The str pp ng length s 7mm to 9mm.� �
Note-3: Supply cables must comply w th the requ rements of IEC 60277 or IEC 60245.� �
It s adv sed to use a two-pole supply sw tch, des gnated for th s dev ce, w th open/� � � �
closed pos t ons marked, n order to cut the power. It must be placed on the supply � �
� � nput of the dev ce at a place where the user can eas ly reach.
V External fuse must be on phase connect on of the supply nput.� �
Z External fuse must be on (+) l ne connect on of the supply nput.� �
Make sure that the power supply voltage range s su table for the dev ce.� �
Sw tch on the power supply only after all the electr cal connect ons are n place. � �
1
2
3
4
5
6
7
8
9
10
11
12
13
14
PO1
(Process Output 1)
SSR Output
12V
Max. 10mA
C
NO
NO
AL1
(Alarm Output 1)
AL2 / PO2
(Alarm Output 2 or
Process Output 2)
Process
Input
5A@250V
5A@250V
Ser al Commun cat on � �
(RS485, Modbus RTU) A+
B-
PID+
Eco
PT-100
TC
Supply
Sw tch
L
N
Supply
Voltage
1A T
Fuse
NOTE-1
AL1 / PO2
(Alarm Output 1 or
Process Output 2)
Process
Input
8
9
10
11
C
NO
5A@250V
12
13
14
PT-100
TC
The Dev ce
w th Two Relays
The Dev ce
w th One Relay
Çal ma Ekranış ı
*1
*5
*2
*4
*2,3
*2,3
*7*6
Warranty
EMKO Elektron k warrants that the equ pment del vered s free from � �
defects n mater al and workmansh p. Th s warranty s prov ded for a � �
per od of two years. The warranty per od starts from the del very � �
date.
Th s warranty s n force f duty and respons b l t es wh ch are � � �
determ ned n warranty document and nstruct on manual performs � �
by the customer completely.
Ma ntenance
Repa rs should only be performed by tra ned and spec al zed � �
personnel. Cut power to the dev ce before access ng nternal parts. � �
Do not clean the case w th hydrocarbon-based solvents (Petrol,
Tr chlorethylene etc.). Use of these solvents can reduce the
mechan cal rel ab l ty of the dev ce. Use a cloth dampened n ethyl � �
alcohol or water to clean the external plast c case.
Other Informat ons
Manufacturer Informat on:
Emko Elektron k Sanay ve T caret A. . � � Ş
Bursa Organ ze Sanay Bölges , (Feth ye OSB Mah.) � �
Al Osman Sönmez Bulvar , 2.Sokak, No: 3 16215 BURSA/TÜRK YE� ı İ
Phone : +90 224 261 1900
Fax : +90 224 261 1912
a
Repa r and Ma ntenance Serv ce Informat on:� �
Emko Elektron k Sanay ve T caret A. . � � Ş
Bursa Organ ze Sanay Bölges , (Feth ye OSB Mah.) � �
Al Osman Sönmez Bulvar , 2.Sokak, No: 3 16215 BURSA/TÜRK YE� ı İ
Phone: +90 224 261 1900
Fax : +90 224 261 1912
10...30V - 4WZ
115V %15) 50/60Hz - 4VAV
230V (±%15) 50/60Hz - 4VAV
3
5
6
100-240V 50/60Hz - 4VA1 V
24V %15) 50/60Hz - 4VAV
Customer Spec f ed� �
7
9
24V %15) 50/60Hz - 4VA2 W
Supply VoltageB
Before comm ss on ng the dev ce, parameters must be set n � �
accordance w th des red use. Incomplete or ncorrect conf gurat on � �
can cause dangerous st uat ons.� �
Because of l m ted mechan cal l fe of relay output contact, SSR � �
output s recommended wh ch the dev ce use PID control algor tm. � �
The dev ce w th ON/OFF control algor tm, hysteres s parameter must � �
be set a su table value for your system, to avo d too much relay � �
sw tch ng.� �
Vac,
Vdc,
Vdc or Vac can be appl ed
: Commun cat on Parameters � � (Only for dev ces w th RS-485 com.)� �
: Protec on Menu Parameters
: Commun cat on access ng address of dev ce. (Default: 1) Modbus � �
Address: 40056
: Commun cat on Baud Rate. (Default: 3) Modbus Address: 40057� �
: 1200 Baud Rate.
: 2400 Baud Rate.
: 4800 Baud Rate.
: 9600 Baud Rate.
: 19200 Baud Rate.
: 38400 Baud Rate.
: Par ty Select on for Commun cat on. (Default: 0) Modbus Address: 40058 � �
: No Par ty.
: Odd Par ty.
: Even Par ty.
: Stop B t Select on for Commun cat on. (Default: 0) Modbus Address: 40059 � �
: 1 Stop B t.
: 2 Stop B t.
: Password for access ng to the programm ng sect on. It can be adjusted from 0 to � �
9999. If s 0, password screen s not seen. If s d fferent from 0 and user � �
enters to the menu pages w thout enter ng the password, all the menus can be � �
observed except protect on menu . But dev ce does not allow to do any changes � �
n parameters. (Default: 0) Modbus Address: 40063
: User default parameters. Th s parameter s used for sav ng all parameters to � �
restore later or restore all parameters saved before. If s chosen, all parameters
saved before are restored. If s chosen, all parameters saved to restore later. If
� �s chosen, noth ng s changed. (Default: ) Modbus Address: 40064
: Th s parameter s used for restore factory defaults. If s chosen, factory � �
defaults parameters restored. If s chosen, noth ng s changed. (Default: ) � �
Modbus Address: 40065
Remove all nput/output connect ons on term nals before restor ng � �
parameters to user/factory defaults.
c
Modbus Addresses of Dev ce Operat on Info. (Read Input Reg ster)� �
Modbus Address: 30000
Modbus Address: 30001
Modbus Address: 30002
D splayed Temperature Value
Status of LEDs: b t.1 , b t.2 , b t.9 ALR1 ALR2 °C
b t.10 , b t.11 , b t.12 °F PO2 PO1
Status of Dev ce: b t.0 Sensor Break Status� �
Alarm Types
Alarm
Set
Alarm
Hysteres s
Alarm
Hysteres s
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteres s
Alarm
Hysteres s
Process
Set
Process
Set
Alarm
Set
Alarm
Output
Alarm
Output
Alarm
Output
Alarm
Output
Process Value
Process Value
Process Value
Process Value
Process H gh
Alarm
Process Low
Alarm
Dev at on H gh� �
Alarm
Dev at on Low� �
Alarm
: Alarm-1 set value. (Default: 300) Modbus Address: 40036
: Alarm-1 hysteres s value. It can be adjusted from %0 to %50 of the scale
( - ). (Default: 0) Modbus Address: 40037
: Alarm-1 type select on. (Default: ) Modbus Address: 40038
: Alarm-1 set low l m t parameter. It can be adjusted from operat on scale m n mum � �
to alarm-1 set h gh l m t. (Default: 0) Modbus Address: 40039 � �
: Alarm-1 set h gh l m t parameter. It can be adjusted from alarm-1 set low l m t to � � � �
operat on scale m n mum. (Default: 500) Modbus Address: 40040 � �
: Alarm-1 on Delay T me. It can be adjusted from 0 to 9999 seconds. (Default: 0)
Modbus Address: 40041
: Alarm-1 off Delay T me. It can be adjusted from 0 to 9998 seconds. If t s h gher � �
than 9998, s seen on the screen and alarm latch ng output s selected. In alarm � �
latch ng output mode n order to make pass ve alarm outputs, press enter button at � �
ma n screen. (Default: 0) Modbus Address: 40042
: Alarm-1 Menu Parameters
PID menu parameters can be seen only f parameter s .� �
: If tune parameter s set to or , dev ce start to calculate PID � �
parameters automat cally. (Default: ) Modbus Address: 40027
: Proport onal band. It can be adjusted from %1.0 to %100.0. (Default: 10.0)
Modbus Address: 40028
: Integral T me. It can be adjusted from 0 to 3600 second. (Default: 100) Modbus
Address: 40029
: Der vat ve T me. It can be adjusted from 0.0 to 999.9 second. (Default: 25.0) � �
Modbus Address: 40030
: Output Control Per od. It can be adjusted from 0.5 to 150 second. (Default: 1.0)
Modbus Address: 40031
: Set value offset. (Set + ) s used as set value n PID calculat ons. Th s � �
parameter s used for sh ft ng the proport onal band. It can be adjusted from (- /2) to � �
( /2). (Default: 0) Modbus Address: 40032
: PID Menu Parameters
: Alarm-2 Menu Parameters (Only for dev ces w th two relays)� �
Alarm-2 menu parameters can be seen only f parameter s .� �
: Alarm-2 set value. (Default: 400) Modbus Address: 40046
: Alarm-2 hysteres s value. It can be adjusted from %0 to %50 of the Scale
( - ). (Default: 0) Modbus Address: 40047
: Alarm-2 type select on. (Default: ) Modbus Address: 40048
: Alarm-2 set low l m t parameter. It can be adjusted from operat on scale m n mum � �
to alarm-2 set h gh l m t. (Default: 0) Modbus Address: 40049 � �
: Alarm-2 set h gh l m t parameter. It can be adjusted from alarm-2 set low l m t to � � � �
operat on scale max mum. (Default: 500) Modbus Address: 40050� �
: Alarm-2 on delay t me. It can be adjusted from 0 to 9999 seconds. (Default: 0)
Modbus Address: 40051
: Alarm-2 off delay t me. It can be adjusted from 0 to 9998 seconds. If t s h gher � �
than 9998, s seen on the screen and Alarm Latch ng Output s selected. In � �
alarm latch ng output mode n order to make pass ve alarm outputs, press enter � �
button at ma n screen. (Default: 0) Modbus Address: 40052
Installat on
In package,
-One p ece un t� �
-Two p eces mount ng clamp� �
-One p ece nstruct on manual� �
A v sual nspect on of th s product for poss ble damage occured � �
dur ng sh pment s recommended before nstallat on. It s your � �
respons b l ty to ensure that qual f ed mechan cal and electr cal � �
techn c ans nstall th s product.� �
If there s danger of ser ous acc dent result ng from a fa lure or defect � �
� � n th s un t, power off the system and the electr cal connect on of the
dev ce from the system.
The un t s normally suppl ed w thout a power sw tch or a fuse. Use � �
power sw tch and fuse as requ red.� �
Be sure to use the rated power supply voltage to protect the un t
aga nst damage and to prevent fa lure.� �
Keep the power off unt l all of the w r ng s completed so that electr c � �
shock and trouble w th the un t can be prevented.� �
Never attempt to d sassemble, mod fy or repa r th s un t. Tamper ng � �
w th the un t may results n malfunct on, electr c shock or f re.� �
Do not use the un t n combust ble or explos ve gaseous � �
atmospheres. Dur ng the equ pment s putted n hole on the metal � �
panel wh le mechan cal nstallat on some metal burrs can cause � �
njury on hands, you must be careful.
Montage of the product on a system must be done w th t’s mount ng � �
clamp. Do not do the montage of the dev ce w th nappropr ate � �
mount ng clamp. Be sure that dev ce w ll not fall wh le do ng the � �
montage.
It s your respons b l ty f th s equ pment s used n a manner not � �
spec f ed n th s nstruct on manual. � �
Before beg nn ng nstallat on of th s product, please � �
read the nstruct on manual and warn ngs below � �
carefully.
Error Messages
Dev at on Range� �
H gh Alarm
Process
Set
Alarm
Set
Process
Set
Alarm
Hysteres s
Alarm
Output
Process Value
Process
Set
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteres s
Alarm
Hysteres s
Alarm
Output
Process Value
Dev at on Range� �
Alarm
1-Sensor fa lure n analog nputs. Sensor connect on s wrong or there � �
� �s no sensor connect on.
a
2-If programm ng sect on enter ng password s d fferent from “0” and � �
user accesses to the parameter by enter button w thout enter ng the � �
password and wants to change a parameter, the warn ng message s � �
shown on the bottom d splay as shown on the left. Dev ce does not � �
allow to do any changes w thout enter ng the password correctly.� �
a
3-If value that s read from the analog nput s lower than process set � �
low l m t parameter value ( ), value on the top d splay starts to bl nk � �
as shown on the p cture.
a
4-If value that s read from the analog nput s h gher than process set � �
h gh l m t parameter value ( ), value on the top d splay starts to bl nk � �
as shown on the p cture.
a
5-If value that s read from the analog nput s lower than sensor scale � �
low l m t, value on the top d splay starts to bl nk as shown on the � �
p cture.
a
6-If value that s read from the analog nput s h gher than sensor scale � �
h gh l m t, value on the top d splay starts to bl nk as shown on the � �
p cture.
Process
Set
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteres s
Alarm
Hysteres s
Alarm
Output
Process Value
Dev at on Band� �
Alarm
: Control Menu Parameters
: Th s parameter determ nes, wh ch output w ll be Process control output. If s � �
chosen, process output s relay output, f s chosen, process output s SSR output. � �
(Default: ) Modbus Address: 40015
: Process Type Select on. It can be (Heat ng) or (Cool ng).(Default: ) � �
Modbus Address: 40016
: Process Control Type Select on. It can be or . (Default: ) Modbus
Address: 40017
: Hysteres s value. It can be adjusted from %0 to %50 of the Scale ( - ).
If = , then th s parameter can be seen. (Default: 3) Modbus Address: 40018
: Sensor Break Output Value. It can be adjusted from %0 to %100. (Default: 0.0)
Modbus Address: 40019
: The cho ce of d splayed text on process value d splay when sensor s broken.� �
It can be or . (Default: ) Modbus Address: 40020
: Soft Start Set value. Dev ce operates n Soft Start mode, unt l the temperature � �
reaches Soft Start set value. If s selected, Soft Start mode s d sabled. (Default: ) � �
Modbus Address: 40021
: Soft Start Control Output. Th s parameter determ nes soft start mode control� �
output percentage. It can be adjusted from %10 to %90. (Default: 10.0) Modbus
Address: 40022
: Soft Start Control T me. Th s parameter determ nes soft start mode control t me. � �
(Default: 1.0) Modbus Address: 40023
: Process Menu Parameters
: Process nput type select on; (Default: ) Modbus Address: 40004� �
: J type (Fe,Cu,N ) Thermocouple , -200ºC,900ºC ; -328ºF,1652ºF
: J type (Fe,Cu,N ) Thermocouple , -199.9ºC,900.0ºC ; -199.9ºF,999.9ºF
: K type (N ,Cr,N ) Thermocouple , -200ºC,1300ºC ; -328ºF,2372ºF� �
: K type (N ,Cr,N ) Thermocouple , -199.9ºC,999.9ºC ; -199.9ºF,999.9ºF� �
: R type (Pt13%RhPt) Thermocouple , 0ºC,1700ºC ; 32ºF,3092ºF
: R type (Pt13%RhPt) Thermocouple , 0.0ºC,999.9ºC ; 32.0ºF,999.9ºF
: S type (Pt10%RhPt) Thermocouple , 0ºC,1700ºC ; 32ºF,3092ºF
: S type (Pt10%RhPt) Thermocouple , 0.0ºC,999.9ºC ; 32.0ºF,999.9ºF
: T type (Cu,Cu,N ) Thermocouple , -200ºC,400ºC ; -328ºF,752ºF
: T type (Cu,Cu,N ) Thermocouple , -199.9ºC,400.0ºC ; -199.9ºF,752.0ºF
: L type (N ,Cr,Co / N ,Fe,Mn,Cu) Thermocouple , -150ºC,800ºC; -238ºF,1472ºF� �
: L type (N ,Cr,Co / N ,Fe,Mn,Cu) Thermocouple,-150.0ºC,800.0ºC;-199.9ºF,999.9ºF� �
: Cu-50 , -199ºC,200ºC ; -199ºF,392ºF
: Cu-50 , -199.0ºC,200.0ºC ; -199.0ºF,392.0ºF
: Pt-100 , -200ºC,650ºC ; -328ºF,1202ºF
: Pt-100 , -199.9ºC,650.0ºC ; -199.9ºF,999.9ºF
: Un t Select on. or can be chosen. (Default: ) Modbus Address: 40005� �
: Operat on Scale m n mum (Low L m t) value. It changes accord ng to the process � �
nput type and scale. (Default: -199) Modbus Address: 40006
: Operat on Scale max mum (H gh L m t) value. It changes accord ng to the � �
process nput type and scale. (Default: 900) Modbus Address: 40007
: Process Set value Low L m t. M n mum set value s def ned w th th s parameter. � �
It can be adjusted between Operat on Scale m n mum and max mum ( - ) � �
values. (Default: -199) Modbus Address: 40008
: Process Set value H gh L m t. Max mum set value s def ned w th th s parameter. � � � �
It can be adjusted between Operat on Scale m n mum and max mum ( - ) � �
values. (Default: 900) Modbus Address: 40009
: D splay offset for process value. It can be adjusted from -10% of scale to 10% of
scale. It s added to the process d splay value. (Default: 0) Modbus Address: 40010� �
: Def ne f lter t me(sec) for d splayed value. (Default: 1.0) Modbus Address: 40011� �
Order ng Informat on� �
Eco PID+ ( 48x48 DIN 1/16 )
D mens on� �
48x48 DIN 1/16
A
4
A
4 .
B
.
C
.
D
S .
E
Outputs-1
1R 1 x Relay Output (5A@250V at Res st ve Load) (NO,C)V� �
C
2R 2 x Relay Output (5A@250V at Res st ve Load) (NO,NO,C)V� �
S SSR Dr ver Output (Max. 10mA, Max. 12V )Z
Outputs-2D
Commun cat on� �
0 None
485 RS-485 Commun cat on� �
E

Especificaciones del producto

Marca: Emko
Categoría: Controlador de temperatura
Modelo: ECO PID+

¿Necesitas ayuda?

Si necesitas ayuda con Emko ECO PID+ haz una pregunta a continuación y otros usuarios te responderán