GE 15250 Manual de Usario
GE
interruptor horario
15250
Lee a continuación 📖 el manual en español para GE 15250 (3 páginas) en la categoría interruptor horario. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios
Página 1/3
SPECIFICATIONS
Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based
upon dipswitch configuration.
15252 NEMA 3R Indoor & Outdoor BM-A301US5-O2
15253, 15251 NEMA 1 Indoor BM-A301US5-I2
15250 NEMA 3R Indoor & Outdoor EM-A301US9-O2
Switch Rating: DPDT Models
Normally Open Contacts
40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240Vac.
TV-5, 120Vac
Normally Closed Contacts
30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.
NOTE: If loads are connected to both NC and NO contacts, both contacts are
derated to 67% of the above values.
ENVIRONMENTAL RATINGS
Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing
WIRING CONNECTIONS
Screw clamp terminals for up to 2 AWG #8 wires per position. For supply
connections, use 8AWG or larger wires suitable for at least 105° C. Use copper
conductors only.
LIGHTS
Power LED (Orange) – Light illuminates when power is applied to
the timer
Status LED (Green) – Light illuminates when power is applied to load.
INSTALLATION
CAUTION: Before wiring or service, power to this time switch and the
equipment it controls must be turned off. Turning off the timer switch only
will not prevent a shock hazard. Replace cover plate within housing before
supplying power to time switch. Installation should be performed by a licensed
electrician only. Before installing this product read all instructions carefully.
Remove protective cover panel within time switch housing by removing
screws located above timer face and at the bottom of the cover panel.
DIPSWITCH CONFIGURATION
WARNING: Failure to properly configure the dipswitch will result in
damage to the unit and void the warranty! Before installing and wiring the GE
Time Switch, proper configuration must be selected. This is accomplished as
follows:
INPUT VOLTAGE DIP SWITCH SETTING:
1. Do not apply power to the timer prior to setting correct Input Voltage DIP
switch.
2. Determine the input voltage which will be applied to the timer (i.e. L1 and
L2/N terminals, see wiring diagrams)
3. Set the DIP switch according to the diagram below.
NOTE: Unit is shipped with DIP switches set for 277VAC Input Voltage
CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to
the timer may result.
Digital Time Switch
15250
Indoor/Outdoor
NEMA 3R-Rated
Enclosure
NOTE: For outdoor locations (model GE 15252),, rain tight or wet location
conduit hubs that comply with requirements of UL 514B (standard for fittings
for conduit and outlet boxes) must be used.
1. Remove 2 screws retaining the interior cover panel and remove panel
by prying out with a thin blade at the top.. Select knockouts to be used.
Remove the inner 1/2” knockout by inserting a screwdriver in the slot
and carefully punch knockout loose. Remove slug. If the 3/4” knockout
is required, remove the outer ring with pliers after removing the 1/2”
knockout. Smooth edges with knife if necessary.
2. Place enclosure in desired mounting location and mark the three
mounting holes.
3. Drill holes for #10 screws, start screws in holes.
4. Place enclosure over screws and tighten screws.
5. Connect conduit hubs to conduit before connecting the hubs to the
enclosure. After inserting hubs into enclosure, carefully tighten hub lock
nut. Do not over-tighten.
6. Install in accordance with all applicable National and Local code
requirements. See Figure 1 and wiring diagrams.
7. Replace interior cover panel and 2 screws.
GROUNDING: This enclosure is of plastic construction and does not
require a ground connection and does not require bonding in pool
applications.
This enclosure does not provide grounding between conduits. When using
non-metallic conduit or cable, connect the ground wires of all cables together
with a wire nut. When metallic conduit is used, use grounding type bushings
and a jumper wire between each conduit.
120VAC
277VAC (Default)
208~240VAC
NOTE: Unit is shipped with DIP Switches set for 277VAC Input Voltage.
CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to
the timer may result.
INPUT VOLTAGE DIP SWITCH SETTING:
1. Do not apply power to the timer prior to setting correct Input Voltage DIP switch.
2. Determine the input voltage which will be applied to the timer (i.e. L1 and L2/N terminals,
see wiring diagrams).
3. Set the DIP Switch according to the diagram below.
http://waterheatertimer.org/GE-timers-and-manuals.html
TIMERN CN O
COM
NC2
NO2
COM2
LOAD
L1
L2
TIMERN CN O
COM
TO 200/240/277V LINE
TO 120V LINE
NC2
NO2
COM2
H
N
LOAD
TIMERN CN O
COM
TO 24V LINE
NC2
NO2
COM2
H
N
LOAD
N
H
TO 120V LINE
TO LOAD
T
T
T
120V Timer, 120V Load and 24V Load
Wired as Single Throw
200/240/277V Timer, 200/240/277V Load, Double Break
Wired as Single Throw
120V Timer, 200/240/277V Load Double Break
Wired as Single Throw
Typical Wiring Diagrams—DPDT
TO POWER SUPPLY
TO POWER SUPPLY 1 TO POWER SUPPLY 2
Timer and Load, Same Voltage
Wired as Single Throw
TO LOAD
TO 120V LINE
H
N
HIGH
LOW
COM
T
LOAD
T
NCTIMERN OC OM
TIMERN CN OC OM
T
TIMERN CN OC OM
120V Two Speed Fan
Wired as Double Throw
Timer and Load, Different Voltage
Wired as Single Throw
Typical Wiring Diagrams—SPDT
Field Wiring
Timer Internab Wiring
FIGURE 1
Override
(Manual ON/OFF Switched)
Timer
(9 Programs Setting)
Clock
(Current Time Setting)
LCD
(Function Figures)
R
(Reset)
H-
(Hours Setting)
M-
(Minutes Setting)
Day
(Days Setting)
OPERATING INSTRUCTIONS
BASIC SETTINGS:
Initial Set Up:
1. Push the “R” button before programming to clear out any settings. Once
the “R” button is pressed the screen will begin to flash. A paperclip may
be needed for this step.
(If the “R” button appears to stick down, use a toothpick to maneuver
it until it pops back up. The screen will flash if the button is popped up
successfully.)
2. Press the “Clock” button and the screen will stop flashing and be ready
for programming.
Setting the Current Time:
1. Press and Hold the “Clock” button during the entire setting.
2. Press the “H+” button to set the hours.
3. Press the “M+” button to set the minutes.
4. Press the “Day” button to set the day of the week.
5. Release the “Clock” button.
Programming ON/OFF Settings:
1. Press the “Timer” button once and the TIMER 1 ON - - : - - appears.
2. Press the “H+” and “M+” button to set the hours and minutes to the
desired time.
3. Press the “Day” button to select the day(s) the setting will be active. Refer
to the Multiple Weekday Group below to see the available settings.
4. Press the “Timer” button to store the setting and proceed to the next
setting TIMER 1 OFF - - : - -.
5. Repeat for all remaining setting options (9 Total ON/OFF settings). Once
completed press the “Clock” button to return to the main display.
Multiple Weekday Groups:
Apart from individual week days, pressing the “Day” button also selects
multiple day combinations such as:
- Monday thru Friday - Tuesday & Thursday & Saturday
- Saturday & Sunday - Monday thru Wednesday
- Monday thru Saturday - Thursday thru Saturday
- Monday & Wednesday & Friday - Monday thru Sunday
After setting a single day or a multi-day-combination the programmed timer
settings will be carried out on each of the week-days at the same time.
Programming Countdown Operation:
1. Press the “Timer” button to scroll through the 9 events settings to get to
the ON C setting.
2. Press the “Override” button to select whether the timer will turn ON or OFF
during teh countdown period.
3. Press the “H+” and “M+” buttons to set the hours and minutes of the
countdown.
4. Press the “Clock” button to store the setting and return to the current time
display. See the diagram below for more information.
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE 3 PHASE
120 V. 240 V. 208 V. 240 V.
14
12
10
8
15
20
30
40
60
60
60
105
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
ADVANCED SETTINGS
Activate the Countdown Feature:
1. Press the “Clock” and “Override” button at the same time to
start the countdown function.
2. Press the “Override” button to pause and continue the
countdown function.
3. Press the “Clock” button to go view the current time display.
Manual Override:
The timer comes with the ability to control the ON and OFF function while the
timer is deactivated. Press and Hold the “Override” button to switch between
timer mode and manual mode. Timer mode will be indicated by an A next to
the ON or OFF. When the timer is in manual mode (not controlled by timer) the
A will not appear on the display. Any time the “A” is on the display the timer is
in control and will always follow the programmed settings (even if it
is temporarily deactivated by moving from ON to OFF or OFF to ON).
Random, ON/OFF Setting:
This feature allows the timer to switch ON and OFF at random times. It is
particularly useful in helping to prevent house burglary as the timer is not
switching ON and OFF at regular times. The programmed settings set will be
executed in a random delay varying within 30 minutes. This function will only
operate if one or more programmed switching commands are set.
1. Press both “Day” and “H+” buttons at the same time. The display will show
the “TIMER” symbol blinking. The random feature is now activated.
2. To turn the random feature off repeat step 1.
Summer Time Feature (DST):
Press the “H+” and “M+” buttons for 3 seconds to advance the current time
1 hour, SUMMER should appear on the display. Repeating this process will
decrease the time by 1 hour and the SUMMER will disappear.
Power Back Up Feature:
In the event of a power failure, the timer will retain its settings for an
estimated 3 months assuming the power back up is fully charged.
Button Lock:
This function allows the user to lock the buttons so that they are not
accidentally pressed.
1. Press and HOLD the “Clock” button for more than 5 seconds. An
“ “ icon will appear on the display. The buttons are now locked.
2. To unlock the buttons repeat this step.
Note:
“ “ Flashing: the timer is in the manual mode with key lock.
“ “ Not flashing: the timer is in the timer mode with key lock.
Lockout a Programmed Setting (Skip a Setting):
1. Press the “Timer” button to scroll to the setting that needs to be skipped.
2. Press the “Override” button to lockout the time setting. The display will
display “H I : d E” and lock the hours and minutes setting.
3. Press the “Override” button again to recall the setting time.
(Will not work for Lockout Countdown feature)
Especificaciones del producto
Marca: | GE |
Categoría: | interruptor horario |
Modelo: | 15250 |
¿Necesitas ayuda?
Si necesitas ayuda con GE 15250 haz una pregunta a continuación y otros usuarios te responderán
interruptor horario GE Manuales
5 Septiembre 2024
5 Septiembre 2024
5 Septiembre 2024
interruptor horario Manuales
- interruptor horario Quigg
- interruptor horario Intermatic
- interruptor horario Brennenstuhl
- interruptor horario Tevion
- interruptor horario Renkforce
- interruptor horario Vivanco
- interruptor horario Theben
- interruptor horario Tork
- interruptor horario Profile
- interruptor horario Perel
- interruptor horario Goobay
- interruptor horario Hager
- interruptor horario Sygonix
- interruptor horario Gamma
- interruptor horario Duro
- interruptor horario Finder
- interruptor horario Orbis
- interruptor horario Grasslin
- interruptor horario Gira
- interruptor horario Praxis
- interruptor horario Go Green
- interruptor horario Handson
- interruptor horario Unitec
- interruptor horario Muller
- interruptor horario GAO
- interruptor horario Suevia
- interruptor horario Bachmann
- interruptor horario Obi
- interruptor horario Kinel
- interruptor horario Masterclear
- interruptor horario Paladin
- interruptor horario PROmax
- interruptor horario Wachsmuth - Krogmann
- interruptor horario TimeControl
Últimos interruptor horario Manuales
20 Octubre 2024
23 Septiembre 2024
23 Septiembre 2024
17 Septiembre 2024
16 Septiembre 2024
8 Septiembre 2024
8 Septiembre 2024
8 Septiembre 2024
8 Septiembre 2024
8 Septiembre 2024