Winland EnviroAlert EA-400 Manual de Usario

Winland Smarth home EnviroAlert EA-400

Lee a continuación 📖 el manual en español para Winland EnviroAlert EA-400 (4 páginas) en la categoría Smarth home. Esta guía fue útil para 3 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/4
Q S GUICK TART UIDE
© 2012 Winland Electronics, Inc.
D-011-0099 Rev (0 /201 )F 7 5
ALWAYS TEST THE YSTEM S
Test the system to ensure proper operation prior to leaving the job site To test the system, either change the probe’s .
temperature so it exceeds your limits, or change the limits to simulate an alarm. If a delay has been programmed, take the
delay out, test the unit, and then put the delay back in.
FREEZER OOLER ONITORING/C M
Never install the EnviroAlert console in a cooler or freezer (condensing environment). Instead, use a remote probe (TEMP-L-S
or TEMP-L-W) and program your zone accordingly. Extend the length of probe wiring up to 1,000’ (304.8m) using 22-18 AWG
twisted pair.
AVOIDING ALSE LARMS ON A F A COOLER OR REEZER F
Both the EA200 and EA400 offer an alarm delay from 0-120 minutes for each zone When a cooler or freezer door is opened, .
the temperature will rise and the probe will detect that rise. Freezers periodically need to enter a defrost cycle which may
also cause the temperature to rise above your limits. Set delays to avoid nuisance alarms under these normal circumstances.
We cannot advise you on what to set for delays or limits.
O -BN OARD TEMP ENSOR ONLY S (EA200 )
The EA200 has an on-board ambient temperature sensor and it is programmed on Zone 1.
More information and product manuals can be found at: www.winland.com
Tech Support 8:00am - 5:00pm Central Time
(800) 635-4269 • +1-507-625-7231 P
www.winland.com
STEP 1: CONNECT POWER AND PROBE(S)
Connect power to the PWR IN terminals, as shown in Figure 1. Be sure to observe proper polarity. Connect the probe(s) to the
zone(s) you intend to monitor. Extend the length of probe wiring up to 1,000’ (304.8m) using 22-18 AWG twisted pair.
EA200 NOTE: Zone 1 is dedicated for the on-board temperature sensor. Remote probes must be programmed on Zone 2.
There is only one input for a remote probe on the EA200 - this is Zone 2.
EA400 NOTE: The EA400 does not have an on-board temperature sensor and uses only remote probes.
STEP 2: UNLOCK CONSOLE FOR PROGRAMMING
To unlock the console, press and simultaneously release the ENTER and ALARM SILENCE buttons. The
“lock” icon should change to “unlocked”.
STEP 3: SET THE TIME AND DATE
Press the TIME/DATE button. Using either the INCREASE or DECREASE button, adjust the hours and then press the ENTER
button. Continue in this manner to set the minutes, AM/PM, year, month, and day. If power is lost, the time and date must
be reset.
STEP 4: PROGRAM THE ZONE(S)
1. Press the ZONE button. The active zone number will be flashing.
2. Select the zone you wish to program using INCREASE or DECREASE and then press ENTER. The “no”
means “not operational” and indicates the zone is currently off. Any zone not programmed should
be set to “no” and therefore turned off.
3. Based on the chart (Figure 2), select the proper sensor type using INCREASE or DECREASE and press ENTER.
Figure 1 - EA200 and EA400 Wiring
POWER REQUIREMENTS:
EA200-12: 11 to 14 VDC @ 120mA 11 to 14 VDC @ 200mAEA400-12:
EA200-24: 23 to 26 VDC @ 120mA 23 to 26 VDC @ 200mAEA400-24:
AUX OUT
Zone 1
PWR IN
PWR OUT
Z one 2
REMOTE PROBE INPUT
ALARM OUTPUTS
(On-Board
Sensor)
Zone 2
(External
Probe)
EA200
AUX OUT
Zone 1
Z one 2
Z one 3
Z one 4
PWR IN
PWR OUT
Z one 1
Zone 2
Zone 3
Z one 4
REMOTE PROBE INPUTS
ALARM OUTPUTS
EA400
Lock Unlock
4. Continue in this manner to set the
high limit
low limit
optional time delay in minutes (this defaults to 0)
non-alarm relay state (ENERGIZE/DE-ENERGIZE)
NOTE: If you are powering this device
from a system with battery back-up,
DE-ENGERGIZE (the default) generally
makes the most sense. If an alarm
is desired upon loss of power to the
EnviroAlert, select ENERGIZE. However,
the normally-open (N.O.) and normally-
closed (N.C.) contacts shown in Figure 1
will then be functionally opposite.
STEP 5: ALARM WIRING
You have the option of using the AUX
relay for all-in-one notification or using
the individual relay outputs. The AUX relay will change state when any zone is in alarm and can be cancelled for 10 minutes
using the ALARM SILENCE button. The individual outputs are not affected by the ALARM SILENCE button.
NOTE: If you are using the individual relay outputs, Output 1 corresponds to Zone 1; Output 2 corresponds to Zone 2; etc.
See Figure 1.
STEP 6: TEST THE SYSTEM
Test the system to ensure proper operation prior to leaving the job site. To test the system, either change the probe’s
temperature so it exceeds your limits, or change the limits to simulate an alarm. If a delay has been programmed, take the
delay out, test the unit, and then put the delay back in.
ADDITIONAL FEATURES
OFFSET button: The EnviroAlert has the ability to adjust the displayed temperature reading for each zone to match to
a known-good reference (±9 degrees). To use this feature, press the OFFSET button, choose which zone you wish to offset,
press ENTER, adjust the value of the offset, and then press ENTER again.
ALARM HISTORY button: This will display the most recent eight alarm events. The display will toggle between
the time and date. To scroll through the alarm events, use the INCREASE or DECREASE buttons. Press the ALARM HISTORY
button again to exit. This feature relies on the time and date being set correctly. To clear the alarm history, press and hold the
ALARM HISTORY button until you see “CLr”.
Probe Type Description
°C or °F Legacy (discontinued) polarity-sensitive temperature probes
1106, 1107, 1108, 1109, 1109A
Red °C or
Red °F
TEMP-H-S (32° to 300° F) and TEMP-H-W (32° to 221° F)
High-temperature range thermistor probes
Blue °C or
Blue °F
TEMP-L-S (-58° to 158° F) and TEMP-L-W (-58° to 158° F)
Low-temperature range thermistor probes
HA-III+ Humidity probe (5 to 95 % RH)
W-S-S and W-UC-S
Water detection probe (surface and under-carpet) supervised
Figure 2 - Remote Probe Selections
To insure proper operation, test weekly.

Especificaciones del producto

Marca: Winland
Categoría: Smarth home
Modelo: EnviroAlert EA-400

¿Necesitas ayuda?

Si necesitas ayuda con Winland EnviroAlert EA-400 haz una pregunta a continuación y otros usuarios te responderán




Smarth home Winland Manuales

Smarth home Manuales

Últimos Smarth home Manuales