Wolf CGB-2-75 Manual de Usario
Wolf
Caldera de calefacción central
CGB-2-75
Lee a continuación 📖 el manual en español para Wolf CGB-2-75 (64 páginas) en la categoría Caldera de calefacción central. Esta guía fue útil para 11 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios
Página 1/64

WOLF GMBH / POSTFACH 1380 / D-84048 MAINBURG / TEL. +49.0.87 51 74- 0 / FAX +49.0.87 51 74- 16 00 / www.WOLF.eu
Doc. no.: 3062555_201804 Subjecttomodications
GB
Installationandoperatinginstructions
Wall mounted gas condensing boiler
CGB wall mounted gas condensing boiler
CGB-75
CGB-100

2 3062555_201804
Tableofcontents
1. Documentation information 3 ................................................................
2. Safety information 4 ..............................................................................
3. Standards and regulations 7 .................................................................
4. Control / Function / Operation 10 ........................................................
5. Delivered condition / standard delivery 12 ............................................
6. Layout ..............................................................................................13
7. Siting instructions 14 ............................................................................
8. Installation .......................................................................................15
9. Dimensions/installation dimensions 16 .................................................
Installation
10. Installation .......................................................................................17
11. Installation of the air/flue gas routing 21 ...............................................
Control
12. Electrical connection 22 ........................................................................
Commissioning
13. Filling the system 28 .............................................................................
14. Conversion to natural gas E/LL (G20/G25) (if necessary) 29 ...............
15. Conversion to LPG P (G31) (if necessary) 30 ......................................
16. Conversion to other gas types (if required) 31 .....................................
17. Checking the gas supply pressure 32 ..................................................
18. Commissioning / setting the BUS address 33 ......................................
19. Displaying / modifying control parameters 34 .......................................
20. Adjusting the modulating pump (accessory) 35 ....................................
21. Limiting the maximum output 36 ...........................................................
22. Testing the combustion parameters 37 .................................................
23. CO2 adjustments 38 .............................................................................
24. Commissioning report 40 ......................................................................
Specication
25. Maintenance and design data 41 .........................................................
26. Technical information for water treatment 43 ........................................
27. System log 45 .......................................................................................
28. Technical information 46 .......................................................................
29. Wiring diagram 56 ................................................................................
30. Specification .................................................................................... 57
31. Troubleshooting ...............................................................................58
32. Product datasheet to EU regulation No. 811/2013 60 ..........................
33. Technical parameters to EU Regulation No. 813/2013 61 ....................
34. Notes ............................................................................................... 62
EU declaration of conformity 63 ...................................................................

33062555_201804
1. Documentationinformation
1.1 Otherapplicabledocuments
- Technical information
- Maintenance instructions
- System and operator’s log
The instructions for all accessory modules and other accessories also apply where
relevant.
1.2 Safekeepingofthesedocuments
The system user or operator should ensure the safekeeping of all instruction manuals
and documents.
► Handovertheseinstallationinstructionsaswellasallotherapplicablemanuals
to the system user or operator.
1.3 Instructingthesystemuser
- Instruct the system user to take out an inspection and maintenance contract with
an approved contractor.
- Inform the system use that the annual inspection and maintenance may only be
performed by an approved contractor.
- Inform the system use that repair work may only be performed by an approved
contractor.
- Inform the system user that only original spare parts may be used.
- Inform the system user that no technical changes may be made to the boiler or
control unit.
- Inform the system user that they are responsible for the safety, environmental com-
patibility and energy quality of the heating system (German Immission Control Act/
Energy Saving Ordinance) [Germany].
- Inform the system user that these instructions and the other applicable documents
must be kept in a safe place.
- Instruct the system user how to operate the heating system.
1.4 Applicabilityoftheseinstructions
These installation instructions apply to CGB-75/100 gas condensing boilers.
1.5 Acceptance
Within four weeks of commissioning of the burner the operator must notify the local
flue gas inspector accordingly. According to the Bundes-KÜO (German Federal
Sweeping and Inspection Act), tests and inspections are only required every 3 years
[Germany].
1.6 Recyclinganddisposal
- Old equipment may only be disconnected from the gas and electricity supply by a
qualiedcontractor.
- Always dispose of materials according to environmental, recycling and waste man-
agement standards.
- Old appliances, wearing parts, defective components and environmentally hazard-
ous liquids and oils must be disposed of or recycled according to applicable waste
disposal regulations without harming the environment.
Theymustnotbedisposedofashouseholdwaste.
- Disposeofpackagingmadeofcardboard,recyclableplasticsandsyntheticller
materials in an environmentally compatible manner through appropriate recycling
systems or a recycling centre.
- Please observe the applicable national and local regulations.

4 3062555_201804
2. Safetyinformation
Danger:ifyousmellgas
- Close the gas valve.
- Open the windows.
- Do not operate any electrical switches.
- Extinguish naked flames.
- From an external location, telephone the gas sup-
ply utility company and an approved contractor.
Danger:ifyousmelluegas
- Switch OFF the appliance.
- Open windows and doors.
- Notify an approved contractor.
Authorised personnel should read these instructions
beforeanyinstallation,commissioningorservicework.
Complywiththespecicationsinthisdocument.Failureto
observetheseinstallationinstructionsvoidsanywarranty
claimagainstWOLF.
Insomecountries,therelevantgassupplycompany
mustbenotiedoftheinstallationofagasboilerand
mustgivetheirapproval.
Pleasenotethatregionalpermitsmayberequiredfor
theuegassystemandconnectingthecondensate
draintothepublicsewer.
Beforestartinginstallationwork,thelocaluegasin-
spectorandwastewaterauthoritymustbeinformed.
Thegascondensingboilermustonlybeinstalled,commis-
sionedandservicedbyqualiedandtrainedpersonnel.
InaccordancewithVDE0105Part1,workonelectrical
components(e.g.control unit)mayonly becarriedout
byqualiedelectricians.
VDE/ÖVE regulations [Germany/Austria] and those of
yourlocalpower supplyutilitycompany areapplicable
toelectricalinstallationwork.
Onlyoperatethegascondensingboilerwithintheoutput
range, which is stated in thetechnical documentation
supplied byWOLF. Intendeduse of the boiler includes
exclusiveuseforhotwaterheatingsystemsinaccordance
with DIN EN 12828.
Neverremove,bypassorotherwisedisableanysafetyor
monitoringequipment.Onlyoperatetheapplianceifitis
inperfecttechnicalcondition.
Anyfaultsordamagewhichimpactormightimpactsafety
mustberemediedimmediatelybyaqualiedcontractor.
Onlyreplacefaultycomponentsandequipmentwithorig-
inalWOLFspareparts.
Dangerfrom"live"electricalcomponents
Nevertouchelectricalcomponentsorcontacts
whentheON/OFFswitchisintheONposition.
Thereisadangerofelectrocution,resultingin
arisktohealthordeath.Themainterminalsare
'live',evenwhentheON/OFFswitchisintheOFF
position.
Riskofscalding
Boilersmaycontainhotwater.
Hotwatercancauseseverescalding.
Beforeworkingonpartswhichareincontact
withwater,allowtheappliancetocooltobelow
40°C,shutoffallvalvesand,ifnecessary,drain
theappliance.
Riskofburns
Boilercomponentsmaybeextremelyhot.
Hotcomponentscancauseburns.
Beforeworkingontheopenedupappliance,al-
lowittocoolbelow40°Corwearsuitablegloves.
Symbols
The following warning symbols are used in these instruc-
tions.
These relate to personal safety and operational reliability.
Instructions that must be followed precisely in order
to prevent risk and injury to persons.
Instructions that must be followed precisely in order
to prevent risk and injury to persons from live electri-
cal components.
Indicates technical instructions that must be
observed to prevent damage to the boiler and
malfunctions.
Note

53062555_201804
2. Safetyinformation
Risksfrompressurisedwater
Boilersaresubjecttohighwaterpressure.
Waterpressurecancausesevereinjuries.
Beforeworkingonpartswhichareincontact
withwater,allowtheappliancetocooltobelow
40°C,shutoffallvalvesand,ifnecessary,drain
theappliance.
Note:
Sensorscanbeincontactwithwaterandthere-
foreexposedtopressure.
Workingonthesystem
- Close the gas shut-off valve and secure it against uninten-
tional reopening.
- Isolate the system from the power supply (e.g. by remov-
ing a separate mains fuse or by means of a main switch
or a heating emergency stop switch) and check to ensure
there is no voltage.
- Safeguard the system against reconnection.
Inspectionandservice
- Ensure the correct operation of the gas boiler by having a
contractor carry out inspections at least once a year and
maintenance/repair when required.
- (DVGW - TRGI 2008 - G600).
We recommend arranging a suitable maintenance con-
tract.
- The operator is responsible for the safety, environmental
compatibility and energy quality of the heating system
(German Immission Control Act/Energy Saving Ordi-
nance) [Germany].
- Use only genuine WOLF spare parts.

73062555_201804
3. Standardsandregulations
Observeallstandardsandguidelinesapplicabletotheinstallationandopera-
tionofthisheatingsysteminyourcountry.
Observetheinformationontheboilertypeplate.
Thefollowinglocalregulationsmustbecompliedwithduringinstallationand
operationoftheheatingsystem:
• Siting conditions
• Ventilation and extract air facilities and connection to a chimney
• Electrical connection to the power supply
• Technical regulations of the gas supply utility company regarding the connection of
the gas appliance to the local gas mains
• Regulations and standards regarding the safety equipment of the water heating
system
• DHWinstallation
Thefollowinggeneralregulations,rulesandguidelinesmustbeobservedfor
installationinparticular:
• EN 806 Drinking water supply systems
• (DIN) EN 1717 Protection against pollution of potable water in water installations
• EN12831Heatingsystemsinbuildings–Methodforcalculationofthedesignheat
load
• (DIN)EN12828Heatingsystemsinbuildings-Designofwater-basedheating
systems
• (DIN)EN13384Chimneys–Thermalanduiddynamiccalculationmethods
• (DIN) EN 50156-1 (VDE 0116 Part 1) Electrical equipment in combustion systems
• VDE 0470/EN 60529 Degrees of protection provided by enclosures (IP rating)
• VDI 2035 Prevention of damage in hot water heating systems
- Scale formation (Sheet 1)
- Corrosion by water (Sheet 2)
-Corrosionbyuegases(Sheet3)

8 3062555_201804
3. Standardsandregulations
Weacceptnoliabilityforlossescausedbytechnicalmodicationsmade
tothecontrolunitorthecontrolsystemcomponents.
Improperusemaycausearisktolifeandlimbordamagetotheappli-
anceorotherproperty.
Requirements
The installation of the boiler must be in accordance with the relevant requirements
of Gas Safety (Installation and Use) Regulations 1998, Health and Safety
Document No. 635 (The Electricity at Work Regulations 1989), BS 7671 (IEE
Wiring Regulations) and the Water Supply (Water Fitting) Regulations 1999, or The
Water Bylaws 2000 (Scotland). It should also be in accordance with the relevant
requirements of the Local Authority, Building Regulations, including amendments to
the Approved Documents Part L and J 2002, The Building Regulations (Scotland),
The Building Regulations (Northern Ireland) and the relevant recommendations of
the following British Standards:
BS5440: Fluesandventilationofgasredboilersnotexceeding70kWnet:
- Part 1: Flues
- Part 2: Ventilation
BS5449: Specicationforforcedcirculationhotwaterfordomesticpremises.
BS5546: Specicationforforcedcirculationhotwaterfordomesticpremises.
BS 6700: Services supplying water for domestic use within buildings and their
curtilages.
BS6798: Specicationforinstallationofgasredboilersnotexceeding60kW
input.
BS6891: Specicationforinstallationoflowpressuregaspipeworkupto28mm
(R1") in domestic premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water central heating systems.
Institute of Gas Engineers Publication IGE/UP/7/1998:
"Guide for gas installations in timber framed housing"
Important: The appliance must be installed and serviced by a competent person
as stated in the Gas Safety (Installation and Use) Regulations 1998. In IE, the
installation must be in accordance with the current edition of I.S,813 "Domestic
Gas Installations", the current Building Regulations and reference should be made
to the current ECI rules for electrical installation.
When tightening or loosening threaded connections always use suitable open-ended
spanners (not pipe wrench, or extensions, etc.). Incorrect use and/or unsuitable
tools can lead to damage (e.g. gas or water leaks)!

93062555_201804
3. Standardsandregulations
GascondensingboilerCGB-...
Gas condensing boiler to DIN EN 437 / DIN EN 13203-1 /
DIN EN 15502-1 / DIN EN 15502-2-1 / DIN EN 60335-1 /
DIN EN 60335-2-102 / DIN EN 62233 / DIN EN 61000-3-2 /
DIN EN 61000-3-3 / DIN EN 55014-1, as well as 92/42/
EWG (Efciency Directive) / 2016/426/EU (Gas Applianc-
es Directive) / 2014/30/EU (EMC Directive) / 2014/35/
EU (Low Voltage Directive) / 2009/125/EG (ErP Directive) /
2011/65/EU(RoHS-Richtlinie) /Regulation(EU) 811/2013/
Regulation (EU) 813/2013, with electronic ignition and elec-
tronicue gastemperaturemonitoring, forlowtemperature
heatingandDHWheatinginheatingsystemswithowtemper-
atures up to 90°C and 3 bar permissible operating pressure in
accordance with DIN EN 12828. This WOLF gas condensing
boiler is also approved for installation in garages.
Open ue gas condensing boilers must only
beinstalledinaroomwhichcomplieswiththe
appropriateventilationrequirements.Otherwise
there is a risk of asphyxiation or poisoning.
Readtheinstallationandmaintenanceinstruc-
tionsbeforeinstallingtheboiler.Alsotakeinto
considerationalltechnicalinformation.
Whenoperating theboilerwith LPGuse only
propane according to DIN 51 622, otherwise
faults may arise when starting and operating
thegascondensingboiler,whichmayleadto
damagetotheapplianceandpersonalinjury.
ApoorlyventedLPGtankcanleadtoproblems
withignition.Insuchacase,contactthecom-
panythatllstheLPGtank.
Theadjustablecylinderwatertemperaturecan
exceed 60°C.For short termoperation above
60°Ctheboilermustbemonitoredinorderto
prevent scalding. For continuous operation,
appropriate precautions should be taken to
preventdraw-offtemperaturesabove60°C,e.g.
thermostaticvalves.
Fig.: Wolf gas condensing boiler
Toprotectagainstscaling,theDHWtemperatureshould
besettomax.50°Cifthetotalwaterhardnessis15°dH
(2.5 mol/m³) or above. Without an accessory regulator,
thiscorrespondstoamaximumhotwaterrotaryselector
settingof6.Withatotalhardnessof20°dHorhigher,use
ofawatertreatmentfacilityinthecoldwatersupplyline
whenheatingDHW isnecessary inordertoextend the
maintenanceintervals.
Failuretotakesuchprecautionswillresultinpremature
scalingoftheapplianceandareductionintheconvenient
availabilityofdomestichotwater.Thecontractorrespon-
sibleshouldalwayscheckthelocalconditions.

10 3062555_201804
4. Control/Function/Operation
DHWtemperatureselection.
WhengascondensingboilersarecombinedwithaDHWcylinder,setting1-9corre-
spondstoacylindertemperatureof15-65°C.TheDHWtemperatureselectorsetting
becomes ineffective when the system is combined with a digital room thermostat or a
weather-compensated controller. The temperature will then be selected at the controller
(accessory).
Heatingwatertemperatureselection.
Settings 2 - 8 correspond, when factory-set, to a heating water temperature of 20-80 °C.
The heating water thermostat setting becomes ineffective when the system is combined
with a digital room thermostat or a weather-compensated controller.
ON/OFF switch
The condensing boiler is OFF in position 0.
Reset
A fault is reset by pressing the reset button which will also restart the system. Press-
ing the reset button re-activates the system, if there was no fault.
ON/OFF switch
ON/OFF
DHWtempera-
ture selector
Reset
button
Heatingwater
temperature
selector
Illuminated ring
Thermometer
Illuminatedringforstatusdisplay
Display Meaning
Flashing green Standby (power supply on; no heat demand)
Constant green light Heatdemand:pumprunning;burnerOFF
Flashing yellow Emissions test mode
Constant yellow light Burneron;amesteady
Flashing red Fault

12 3062555_201804
5. Deliveredcondition/
standarddelivery
Deliveredcondition
Gascondensingboiler
The standard delivery includes:
1 Gascondensingboilerreadytoconnectwiththecasingtted
1 Mounting bracket for mounting on the wall, with installation
accessories
1 Installation instructions
1 Operating instructions
1 Maintenance instructions
1 Trap with hose
1 Maintenance tools
Accessories
The following accessories are required for installation of the
gas condensing centre:
- Balancedueaccessories(seetechnicalinformation)
- Room temperature-dependent or weather-compensated
control
- Condensate drain outlet with hose retainer
- Gasballvalvewithreprotection
- Fittingassemblyforheatingow,heatingreturnandintegral
safety assembly
- Pump assembly with variable speed pump and integral safety
assembly
- Low loss header set for one or two appliances in a cascade
- Dirtlterintheheatingreturn
Boilerconnections
Fig.: Connections with heating circuit connection set (accessory)
Heatingow
G 1½"
Gas connection
R ¾"
Heatingreturn
G 1½"
Condensate
drain
Heatingcircuitpumpassembly(accessory)
Fig.: Pump assembly (accessory)
Heatingow
G 2"
Heatingreturn
G 2"
Trap
Gas tap
Connection
Expansion vessel 1"
Drain&llvalve
Drain&llvalve
Pressure gauge
Safety valve
Modulating
pump

133062555_201804
CGB-75 / CGB-100
6. Layout
Quick-action air vent valve Gas fan
Heatingwaterheat
exchangers
Condensate trap
Gas combination valve
Heatingreturn Gas supply pipe
Flue gas temperature limiter
Combustion chamber casing
Return sensor
Combustion chamber
cover temperature limiter
Flue
Heatingow
Burner
Flow sensor
Temperature limiter
Flow
Intake pipe
Flue gas test point
Ventilation air test point
Gas:air mixing chamber
Flash trap
Displacement device
Water pressure switch
Gas restrictor
Monitoring electrode
Ignition electrode
Non-return valve

14 3062555_201804
First determine where the appliance is to be installed.
For this, take into account the ue gas connection, lateral
clearances towards walls and the ceiling, and any existing
connectionsforgas,heating,DHWandelectrics.
7. Sitinginstructions
Sound insulation: Under certain critical installation conditions
(e.g. installation on a drywall), additional measures may be
necessary to soundproof the boiler. In such conditions, use
anti-vibration rawl plugs and, if necessary, rubber mounts or
insulation strips.
When using a
low loss header set
Min. 830 mm
Min.
350 mm
Min.
350 mm
Electrical connection must be made on site.
Please maintain the 350 mm clearance to the ceiling to enable
inspection and maintenance work on the boiler to be carried
out, otherwise the necessary inspection and function tests
on components cannot be ensured during maintenance. The
drain hoses must be secured with the retainer above the drain
outlet (trap). The drain must be able to be easily inspected.
Theboilermaybeinstalledonlyinrooms
thatareprotectedfromfrost.
The temperature in the installation room must be be-
tween 0°C and 40°C.
Generalinformation
Clearancebetweentheboilerandcombustible
materials or components is not required, as
temperatureswillnotexceed85°Cattherated
boiler heating output. However, explosive or
readilyammablematerialsmustnotbeused
intheinstallationroomasthiswouldcreatea
riskofreorexplosion.
Duringboilerinstallation,ensurethatnocon-
taminants (e.g. drilling swarf) enter the gas
boiler,otherwisefaultsmaydevelop.
Note
Theinstallation roomand thecombustion air
supplied to the appliance must be free from
chemicals, e.g. uorine, chlorine or sulphur.
These substances are contained in sprays,
paints, adhesives, solvents and cleaning
agents.Underunfavourableconditions,these
mayleadtocorrosion,includingintheuegas
system.

173062555_201804
10.Installation
Heatingcircuitconnectionset
We recommend you connect the heating system with the aid
of a heating circuit connection set.
Connection set comprising: Connection to the appliance with
atgasket,connectiontoheatingow/returnwithballvalves
1" female thread.
Note:
Provideadrain&llvalveatthelowestpointinthesystem. Fig.:Heatingcircuitconnectionset(accessory)
Fig.: Pump assembly (accessory)
TheCGB-75andCGB-100havenotbeenttedwithanex-
pansionvessel atthefactory.Thismustbe ttedexternally
(available from the Wolf accessories range). The expansion
vesselmustbesizedsufciently,inaccordancewithDIN4807.
There must be no shut-offvalve between the
expansion vessel and the condensing boiler,
otherwisethepressurebuild-upwouldperma-
nentlydamagetheboilerduringheating.There
isariskofsystemcomponentsrupturing,giving
risetoariskofscalding.
Thisdoesnotincludebutteryvalvesupstreamoftheexpan-
sionvessel. Thepump ortting assembly includesa 3bar
safety valve (6 bar safety valve is available as an accessory).
Route the discharge pipe line into a drain funnel. The mini-
mum system pressure is 1.0 bar. The boilers are approved
exclusively for sealed systems of up to 6 bar. The maximum
owtemperatureisfactory-setto80°Candmaybeadjusted
to 90°C if required.
Safetyequipment

22 3062555_201804
12.Electricalconnection
Generalinformation
Theinstallationmaybecarriedoutonlyby
anapprovedelectricalcontractor.Observe
VDEregulations [Germany]and alllocal
regulationsofyourpowersupplyutility.
Forinstallation inAustria:The ÖVEreg-
ulationsand requirementsand thoseof
your local power supply utility must be
observed.
Anomnipolarisolatorwithatleast3mm
contactseparationmustbeintegratedin
thepowercableupstreamoftheappliance.
Aconnectionbox mustalsobe installed
onsite.
Neverroutesensorleadsalongside230V
cables.
Danger through 'live' electrical compo-
nents.
Pleasenote:Turnoff theON/OFF switch
beforeremovingthecasing.
Nevertouchelectricalcomponentsorcon-
tactswhentheON/OFFswitchisintheON
position.Thereisadangerofelectrocution,
resultinginarisktohealthordeath.
Themain terminalsare 'live',even when
theON/OFFswitchisintheOFFposition.
During servicing and installation work,
isolatetheentiresystemfromthepower
supplyacross all poles,otherwise there
willbeariskofelectrocution.

233062555_201804
12.Electricalconnection
Terminalbox
The control and safety devices are fully wired and tested.
230Vmainsconnection
In the case of a permanent connection, provide the power
supply via a mains isolator (e.g. heating system emergency
stop button), which ensures at least 3 mm contact separation
for all poles. Flexible power cable, at least 3x1.0 mm2
No other consumers may be connected to the cable.
In rooms with a bathtub or shower, the appliance may only be
connected via an RCD.
Installationinformation–electricalconnection
Isolate the system from the power supply before opening.
Check that the appliance is isolated from the power supply
Swivel the control unit to one side.
Unclip the terminal box from the holder.
The terminal box can be mounted on the wall to the right or
left of the boiler.
Open the terminal box.
Screw the strain relief into the holes provided.
Strip approx. 70 mm off the power cable insulation.
Push the cable through the strain relief and tighten the strain
relief.
Clamp the appropriate cores to the Rast5 plug.
Push the inserts back into the terminal box casing.
Push the Rast-5 plugs back into the correct positions.
Strain relief
F 3.15 A
Rast-5 plug
Terminal box, factory-set
L.h. option
R.h.
option
Power supply
230VAC/50Hz
Power supply, ext. Accessories
230VAC/50Hz/max.300VA
Programmable
output
230VAC/50Hz
Programmable
input
oating
Outside sensor
2-wire eBUS
Connecting digital
WOLF control accessories

24 3062555_201804
12.Electricalconnection
Cylindersensorconnection
- If a cylinder is to be connected, the blue socket of the cylinder
sensor must be connected to the blue plug of the control unit.
- Follow the cylinder installation instructions.
Fig.: Blue plug for cylinder sensor connection
Blue plug
Isolate the condensingboiler from the power
supply priorto changingafuse. The ON/OFF
switchontheappliancedoesnotprovideiso-
lationfromthepowersupply.
Danger through 'live' electrical components.
Nevertouchelectricalcomponentsorcontacts
ifthecondensingboilerhasnotbeenisolated
fromthepowersupply.Dangertolife!
Changingthefuse
Fig.: Terminal box cover open
Fuse
Fig.: Connecting output A1
OutputconnectionA1(230VAC;200VA)
Insert the cable glands into the terminal box. Insert and secure
the connecting cable through the cable gland. Connect the
connecting cable to terminals L1, N and .
The parameters for output A1 are described in the table on
the next page.
Connectionofanexternalheatingcircuitpump
(onsite)(230VACmax.300VA)
Insert the cable glands into the terminal box. Insert and secure
the connecting cable through the cable gland.
Connect the pump 230 V AC to terminals L1 and N and
Thepumpisactivatedwhenthereisdemandinheating,DHW
or frost protection mode.
Fig.: Connection, heating circuit pump

26 3062555_201804
12.Electricalconnection
The functions of input E1 can be scanned and adjusted with eBUS-enabled Wolf control accessories. The following functions
can be allocated to input E1:
Code Meaning
0Nofunction
Input E1 is not taken into consideration by the control unit
1Roomthermostat(factorysetting)
With open input E1, heating operation will be blocked (summer mode), independent of any digital Wolf control
accessories.
2Maximumthermostat,systempressureswitchorcondensateliftingsystem
Connection option for a maximum thermostat, system pressure switch or condensate lifting system. To enable the
burner,inputE1mustbeclosed.Whenthecontactisopen,theburnerisblockedbothforDHWandheating,as
well as for emissions tests and frost protection.
3Notassigned
4Flowswitch
Optionalconnectionforanadditionalwaterowswitch.
input E1 must be closed within 12 seconds after the pump has been switched. Where this is not the case, the
burner will be switched OFF, and fault 41 will be displayed.
5Ventilationairdampermonitoring
See parameters for output A1, no. 7. Supply air damper
8Burnerblock(BOB)
Operation without burner
Closed contact, burner blocked
Heatingcircuitpumpandcylinderchargingpumpoperateinstandardmode
In emissions test mode and frost protection the burner is enabled
Open contact enables the burner again
Connection,inputE1(24V),potential-free
Connect the cable for input 1 at terminals E1 in accordance
withthe wiringdiagram;rstremovethejumperbetweena
and b from the respective terminals.
No external voltage may be connected to in-
put E1, as this could destroy the component.
Note
Fig.: Connection, room thermostat
Connectinglowvoltagedevices
When installing the appliance in places
where there is a risk of increased electro-
magneticinterference,itisadvisabletot
screened sensor leads and eBUS cables.
The cable shield should be connected at
one end to the PE potential in the control
unit.
Note

273062555_201804
12.Electricalconnection
Connection,digitalWolfcontrolaccessories
(e.g.BM,MM,KM,SM1,SM2)
Only controllers from the Wolf range of accessories may be
connected. Each accessory is supplied with its own connection
diagram.
Useatwo-corecable(cross-section>0.5mm²)asthecon-
necting cable between the control unit accessory and the
condensing boiler. Fig.: Connecting digital Wolf control accessories (eBUS interface)
Connectingtheoutsidesensor
The outside temperature sensor for digital control accessory
may be connected to the terminal strip of the boiler connection
AF, or the terminal strip of the control accessory.
Fig.: Connecting the outside sensor

28 3062555_201804
13.Fillingthesystem
Fill the system and vent it properly to safeguard the perfect
functioning of the condensing boiler.
Beforeconnectingthegascondensingboiler,
ush the heating system to remove residues
suchasweldingpearls,hemp,putty,etc.from
thepipework.Checkthedirtlter.
- The gas tap must be shut
- The locking cap on the quick-acting air vent valve should
not be unscrewed
- Open all radiator valves
- Open the return valves, and the heat exchanger will then be
graduallylledwithwaterfrombelow
- With the entire heating system and boiler in a cold condition,
slowlyll thesystem viathe inspection/BDFvalveon the
return until approx. 2 bar pressure is indicated
- Opentheowvalvesonthecondensingboiler
- Fill the heating system to 2 bar pressure In operation, the pressure
gauge (on site) must indicate between 1.5 and 2.5 bar
- Check the entire system for water leaks
- Open the air vent valve
- Start the condensing boiler, set the heating water temperature
selector to position "2" (pump running, illuminated indicator
ring for status display constantly green)
- Ventthepump;todothis,brieyopenandthenretighten
the air vent screw.
- Vent the heating circuit completely, switching the condensing
boiler ON for 5 seconds and OFF for 5 seconds at the ON/
OFFswitch,vetimesinsuccession
- Top up with water (technical information) if the system pres-
sure falls below 1.5 bar
- Open the gas ball valve
- Press reset.
Note
Note: - In continuous mode, the heating circuit is auto-
matically vented via the air vent valve
- At a system pressure below 1.0 bar, the boiler
will enter a fault state
Drain&llvalve
ON/OFF switch ThermometerReset button
Automatic air vent valve
Air vent valve, heating
circuit pump
- Fillthetrapwithwaterandtittotheboiler
Trap

293062555_201804
14.ConversiontonaturalgasE/LL
(G20/G25)(ifnecessary)
Asdelivered,thegascondensingboilersCGB-75/CGB-100areequippedforoperationwithnaturalgasE/H(G20).
For operation with natural gas LL (G25), the gas restrictor must be replaced.
The necessary gas restrictor with the code number “1260” for operation with natural gas LL (G25) is included in the scope of delivery
and is attached to the gas pipe for use.
Re-assemble in reverse order.
Note: DuringtheconversionfromLPGtonaturalgas,thegascombinationvalveandtheuegasoriceplate(seepage24/25)
must be removed prior to assembly.
5)
Remove integral gas restrictor and replace with the gas
restrictor for the new gas type (in accordance with the
table on page 25).
Gas restrictor
4)
Undo the gas combination valve from the mixing chamber
for gas/air (four SW8 screws).
4 x screws
SW8
Unplug the connector (rstunscrewthePhillipshead
screws)
1)
Undo gas connection at the gas combination valve
2)
3)
Unscrew the mixing chamber from the fan (three Allen screws 5
mm), and remove air inlet pipe if necessary
6)
After assembly of the gas restrictor, gas combination valve
and air inlet pipe, push the O-ring lubricated with silicone
grease into the packing groove of the fan and ret the
mixing chamber.
O-ring
1
2

30 3062555_201804
15.ConversiontoLPGP(G31)(ifnecessary)
RemovethefourSW8screwsatthegasconnectiontting
andremovethettingfromthegascombinationvalve.
Remove the gas combination valve and gas restrictor.
Place the protective labels at the valve inlet and valve
outlet of the new gas combination valve at the apertures
of the removed valve.
4)
Undo the gas combination valve from the mixing chamber
for gas/air (four SW8 screws).
4 x screws
SW8
3)
Unscrew the mixing chamber from the fan (three Allen
screws 5 mm), and remove air inlet pipe if necessary
7)
6)
Push the O-ring, lubricated with silicone grease, into the
packinggrooveofthefanandtthemixingchamberwith
the gas combination valve to the burner fan.
Tightengasconnectionttingtogassupplyline.
O-ring
Gas combina-
tion valve
Gas connection
tting
O-ring 23.47 x 2.62
Gas restrictor 6.7
Gas combina-
tion valve
Gas restrictor
5)
4 x SW8 screw
Gas connection
tting
Unplug the connector (rstunscrewthePhillipshead
screws)
1)
Undo gas connection at the gas combination valve
2)
Mixing cham-
ber
ScrewthegasconnectionttingwithO-ring26x4tothe
new LPG gas combination valve.
Insert the new 6.7 gas restrictor into the gas combination
valve.
Use screws to secure the gas combination valve with O-ring
23.4 x 2.6 to the mixing chamber.
Threadedtting
Gas connection

333062555_201804
Energysavings
-Instructthecustomeraboutenergysavingoptions.
-Referthecustomertothesection"Informationforen-
ergyefcientoperation"intheoperatinginstructions.
18.Commissioning/settingtheBUS
address
Only qualied personnel must carry out the
commissioningandinitialstart-upoftheboiler
andinstructionoftheuser.
- Check that all ue gas accessories have been correctly
installed
- Opentheshut-offvalvesintheowandreturn
- Open the gas shut-off valve
- Switch on the system ON/OFF switch on the control unit
-Check the ignition and the regular ame structure of the
burner
- The illuminated ring shows a yellow colour, if the boiler starts
correctly
- Check the condensate drain
- Familiarise customers with the operation of the boiler with
reference to the operating instructions and advise them of
therequiredwatertreatmentforllandtop-upwater
- Complete the commissioning report and hand over the
instructions to the customer.
Fig.: Control unit overview
ON/OFF
ON/OFF
switch
ThermometerReset button
Illuminated ring
- Check the boiler and system for leaks;
Normaloperatingpressurewhensystemiscold
1.5-2.0bar;preventwaterleaks
- Checkthelocationandseatingofttedcom-
ponents
- Checkallconnectionsandcomponentunions
forleaks.
- Ifleaktightnesscannotbeensured,thereis
ariskofwaterdamage.
Note
BUSaddresssetting
Whenoperatingseveralboilers(numberofboilers>1)inconjunctionwithacascademodule,settheBUSaddressofeachboiler
in accordance with the table below.
BUS address setting:
Holddowntheresetbutton;after5seconds,thecorrespondingashingcodewillbedisplayed(seetable).Selectthecorresponding
addresswiththeDHWtemperaturerotaryselector.Thenreleasetheresetbuttonagain.
Busaddress RotaryselectorpositionDHW Illuminatedringdisplay
1 1 ashingred
2 2 ashingyellow
3 3 ashingyellow/red
4 4 ashingyellow/green
5 5 ashinggreen/red
0 6 ashinggreen(factorysetting)

34 3062555_201804
19.Displaying/modifyingcontrolparameters
ThecontrolparameterscanbemodiedordisplayedviacontrolaccessorieswitheBUScapability.Forprocedures,checkthe
operating instructions of the relevant accessories.
Topreventdamagetotheheatingsystem,can-
celnightreductionifoutsidetemperaturesfall
below-12°C.Ifthisrequirementisnotobserved,
icemayformontheueoutletwhichmaycause
injuryormateriallosses.
Youcanndtheoutputdatafortheboileron
thetypeplate.
Modications must only be carried out by a
recognisedheatingcontractororbyWolfcus-
tomerservice.
Incorrectoperationcanleadtosystemfaults.
PleasenotewhenadjustingparameterGB05/
A09(frostprotection/outsidetemperature),that
frostprotectionisnolongersafeguardedifyou
settemperatureslowerthan0°C.Thiscanlead
toheatingsystemdamage.
Note
Note
The settings in column 1 apply to control accessories ART, AWT
The settings in column 2 apply to Wolf control systems with BM programming unit
1 2 Parameter Unit Factory setting min Max.
GB01 K 8 5 30HG01 Burnerswitchingdifferential
HG02 Lowfanspeed
Minimum fan speed in %
% CGB-75: 30
CGB-100: 25
30
25
100
100
HG03 TopfanspeedWW
MaximumfanspeedforDHWin%
% CGB-75: 90
CGB-100: 90
30
25
100
100
GB04 HG04 TopfanspeedHZ
Maximum fan speed for heating in %
% CGB-75: 90
CGB-100: 90
30
25
100
100
GB05 A09 Frostprotection,outsidetemperature
Pump ON with connected outside temperature sensor and
insufcienttemperature
°C 2 -10 10
GB06 HG06 Pumpmode
0->PumpONinwintermode
1->PumpeONduringburneroperation
0 0 1
GB07 HG07 Boilercircuitpumpsrun-ontime
Heatingcircuitpumprun-ontimeinminutesinheatingmode
min 1 0 30
GB
08
HG08or
HG22
Maximumlimit,boilercircuitTV-max
applicable to heating operation
°C 80 40 90
GB09 HG09 Burnercycleblock
applies to heating mode
min 7 1 30
HG10 eBUSaddress
heat source BUS address
0 0 5
HG11 DHWquickstart,
temperature of the plate heat exchanger in summer mode
(only applicable for combi boilers)
°C 10 10 60
HG12 Gastype
not supported
0 0 1
GB13 HG13 ProgrammableinputE1
Various functions can be allocated to input E1. See chapter
"Connection input E1"
1
Room
thermostat
0 5
GB14 HG14 ProgrammableoutputA1
Output A1 (230 V AC)
Various functions can be allocated to output A1. See
chapter "Connection output A1"
6
Cylinder
charging pump
0 9
GB15 HG15 Cylinderhysteresis
Switching differential during cylinder re-charging
5 1 30
HG21 MinimumboilerwatertemperatureT-boilermin. °C 20 20 90

353062555_201804
20.Adjustingthemodulatingpump(accessory)
Inheatingmode:
The heating circuit pump (accessory) modulates in proportion to the burner output. This means at maximum burner output, the
pump operates at the maximum pump speed for heating mode. At minimum burner output, the pump operates at the minimum
pump speed for heating mode. In other words, the burner output and pump speed are regulated subject to the required heat load.
Modulating the pump reduces the power consumption.
In DHW mode:
The heating circuit pump will not modulate, but operates constantly at the selected pump speed.
Instandbymode:
The heating circuit pump will not modulate, but operates constantly at the selected pump speed.
Standby mode 20%
Settinglimits:
The speed limits for heating mode can be changed with the BM programming unit.
Solution:
The settings in column 1 apply to control accessories ART, AWT
The settings in column 2 apply to Wolf control systems with BM programming unit
1 2 Parameter Unit Factory
setting
min Max.
GB16 % 20 20 100HG16 Minimumheatingcircuitpumprate
GB 17 HG17 Heatingcircuitpumpoutput,maximum
This parameter must be set at least 5% higher than the
parameter
Minimum heating circuit pump output
% 100 20 100
Fortheminimumpumpspeedforheatingmode,onlysettingsinaccordancewiththistablearepermissible.
Otherwise,thereisariskthatthepumpwillnotstart.
Inaddition,the"Max.pumpspeedforheatingmode"mustbeatleast5%higherthanthe"Minimumpumpspeed
forheatingmode",otherwisethepumpwouldrunat100%.
Note
Problem Troubleshooting
Individual radiators do not heat up properly. Createhydronicbalancing,i.e.reducetheowrateof
hotter radiators
In the spring and autumn (average outside temperature),
the required room temperature is not achieved.
Increase the set room temperature at the controller
e.g. from 20 °C to 25 °C
When the outside temperature is extremely low, the selected
room temperature is not achieved.
Select a steeper heating curve at the controller
e.g. from 1.0 to 1.2

36 3062555_201804
CGB-75/100
Outputsetting(parameterGB04orHG04)
TheoutputsettingcanbemodiedwithWolfcontrolaccessorieswitheBUScapability.
The heating output is determined by the gas fan speed. By reducing the gas fan speed in accordance with the table, the maximum
outputwillbematchedat80/60°CtonaturalgasE/H/LLandLPG.NaturalgasLLisnotapplicableforAustria/Switzerland.LNG
is not applicable for Switzerland.
21.Limitingthemaximumoutput
CGB-75
Heatingoutput (kW) 18 22 25 29 33 37 40 44 48 51 55 59 63 66 70
Display value (%) 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Table: Output settings
CGB-100
Heatingoutput (kW) 18 23 28 34 39 44 49 55 60 65 70 75 81 86 91
Display value (%) 25 30 36 41 46 52 57 63 68 73 79 84 89 95 100
Limitingthemaximumheatingoutputrelativetoaow/returntemperatureof80/60°C
SettingsforparameterGB04/HG04orwithWolfconnectionaccessorieswitheBUScapabilityin[%]
MaximumoutputinkW

373062555_201804
22.Testingthecombustionparameters
Testthecombustionparameterswiththeboilerclosed!
Testingtheintakeair
- Remove the screw from the l.h. test port
- Open the gas shut-off valve
- Insert the test probe
- Start the gas condensing boiler and turn the heating water
temperature selector to the emissions test symbol (illumi-
natedringofthestatusdisplayashesyellow)
- Measure the temperature and CO 2.
In the case of a concentric balanced ue, the ue is not
gas-tight if the CO 2contentis>0.2%.Theleakmustbe
rectied.
- After the test has been completed, switch the boiler off,
remove the test probe and close the test port. Ensure the
screws are tightly secured.
Fig.: Test ports
Test port
"Flue gas"
Test port
"Inlet air"
Testingtheuegasparameters
Whenthetestportisopen,uegascanes-
capeintotheinstallationroom.Thereisarisk
ofasphyxiation.
- Remove the screw from the r.h. test port
- Open the gas shut-off valve
- Start the gas condensing centre and turn the temperature
selector to the emissions test symbol (illuminated ring of
thestatusdisplayashesyellow)
- Insert the test probe
- Measuretheuegasvalues
- After the test has been completed, remove the test probe
and close the test port again. Ensure the screws are tight-
ly secured.
Fig.: Control unit overview
ON/OFF switch Temperature selector

38 3062555_201804
23. CO
2
adjustments
Settingthegas/airmixture
Carryouttheadjustmentsintheorderdescribedbelow.Thegascombinationvalvehasbeensetatthefactory
tothegastypespeciedonthetypeplate.Onlyadjustthegascombinationvalveafterthesystemhasbeen
changedtoadifferentgastypeorwhenservicing.
Iftoolittleheatisdrawnoff,opensomeradiatorvalves.
Note
A)CO2settingforupperload(emissionstestmode)
Release the casing cover with the l.h. and r.h. screw. Release
the bottom of the casing cover and unhook at the top.
- Remove the screw from the l.h. "Flue gas" test port.
- Insert the test probe of the CO
2testinstrumentintothe"ue
gas" test port (approx. 120 mm).
- Turn the temperature selector to "Emissions test"
.
(illuminatedsignalringasstatusindicatorashesyellow.)
- Ensure that the boiler is not limited electronically.
- Check the CO2 content at full load, and compare the actual
values with those in the table below.
- Correct the CO
2adjustmentasrequiredusingthegasow
adjusting screw on the gas combination valve in accordance
with the table.
Gasowadjust-
ing screw
Fig.: Gas combination valve
- Terminate the emissions test mode by returning the temper-
ature selector to its original position.
- Turnclockwise-lowersCO2 content
- Turnanti-clockwise-raisesCO2 content
Fig.: Emission test with open appliance
Test port
"Flue gas"
Applianceopen
at loadupper
NaturalgasE/H/LL
8.6% ± 0.2%
LNG P
10.1% ± 0.2%
Screws
Fig.: Undoing screws
Aftercompletingservicing,closethefrontcasing
againandfastenthescrewstightly.Thereisa
riskofcarbonmonoxide poisoningiftheue
systemisfaulty.

393062555_201804
B)CO2settingforlowerload(softstart)
- Remove the protective screw over the zero point adjusting
screw with a Torx screwdriver.
- Restart the condensing boiler by pressing the "Reset button".
- Check and correct (if required) the CO2 content approx. 20 s
after the burner start with the CO
2tester,byneadjusting
the zero point adjusting screw with Torx in accordance with
the table. Make this adjustment within 180 s of the burner
start. If necessary, repeat the start phase for the setting
procedure by pressing the reset button.
- Duringthisadjustment,theremustbenoDHWoperation!
- Retighten the protective screw.
23. CO
2
adjustments
- Clockwiserotation–higherCO
2contentincreased!
- Anti-clockwiserotation–lowerCO2contentreduced!
Zero point
screw
Fig.: Gas combination valve
Protective
screw
Gas throughput
adjusting screw
D)Completingtheadjustments
- Shut down the boiler and close the test ports and hose
connection nipples again. Check the gas supply line and
hydraulics for tightness.
C)CheckingtheCO2setting
- Aftercompletingthework,retthecasingcoverandcheck
the CO2 values with the appliance closed.
Observe the CO emissions whilst making
CO2 settings. The gas combination valve is
incorrectly adjusted if the CO value is > 300
ppm when theCO2 value is correct. Takethe
followingsteps:
- Fully insert the zero point adjusting screw
- Open the zero point adjusting screw 1½ revolutions
- Repeat the adjusting process from section A)
- The condensing boiler is correctly adjusted if the CO
2 values
correspond to those in the adjacent table. Fig.: Emission test with closed appliance
Test port
"Flue gas"
Applianceopen
at loadlower
NaturalgasE/H/LL
8.5% ± 0.2%
LNG P
9.7% ± 0.2%
Applianceclosed
at loadupper
NaturalgasE/H/LL
8.8% ± 0.5%
LNG P
10.3% ± 0.5%
Applianceclosed
at loadlower
NaturalgasE/H/LL
8.7% ± 0.5%
LNG P
9.9% ± 0.5%

40 3062555_201804
24.Commissioningreport
Commissioning steps Testvaluesorconrmation
1.) Gas type
NaturalgasE/H
Natural gas LL
LNG
Wobbe Index
Operationalcaloricvalue
________________
________________
kWh/m³
kWh/m³
2.) Gas supply pressure checked?
3.) Gas tightness test carried out?
4.) Air/uesystemchecked?
5.) Water connections checked for tightness?
6.) Filling the trap
7.) Boiler and system vented?
8.) System pressure 1.5 - 2.5 bar?
9.) Systemushed?
10.) Water treatment carried out according to “Technical
information for water treatment”.
pHvalueset
total hardness set
________________
________________
pHvalue
°dH
11.) No chemical additives (inhibitors; antifreeze) added?
12.) Gas type and heating output entered on label?
13.) Function test carried out?
14.) Flue gas test:
Flue gas temperature gross
Inlet air temperature
Flue gas temperature net
Carbon dioxide content (CO2) or oxygen content (O2)
Carbon monoxide content (CO)
________________
________________
________________
________________
________________
tA (°C)
tL (°C)
(t A
-tL)
(°C)
%
ppm
15.) Casingtted?
16.) System user instructed; documentation handed over?
17.) ________________Commissioningconrmed?

413062555_201804
25.Maintenanceanddesigndata
Hydraulicpressuredropintheboilerexcludingpump
Residualheadoftheheatingcircuitpump(accessory)
The pump modulates subject to burner load. The residual head can be obtained from the diagrams.
CGB-75/100residualhead
withpumpassembly(accessory)
Residual head [mbar]
Water volume [l/h]
CGB-75/100pressuredrop
Pressure drop [mbar]
Water volume [l/h]
0
20
40
60
80
10
0
12
0
14
0
16
0
18
0
20
0
22
0
24
0
26
0
28
0
30
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
CGB-75
20° spread
CGB-100
20° spread
Maximum
Water volume

42 3062555_201804
25.Maintenanceanddesigndata
Sensorresistances
Resistance [Ohm]
Temperature [°C]
Temperature/resistance
0°C 16325 15°C 7857 30°C 4028 60°C 1244
5°C 12697 20°C 6247 40°C 2662 70°C 876
10°C 9952 25°C 5000 50°C 1800 80 °C 628
Max.spread A heat exchanger protective functionisintegratedintotheCGB-75/100. This prevents
stressesinthematerialbylimitingthemaximumtemperaturedifferentialbetweenow
and return. The output is restricted at 28 K and above. If 38 K is nevertheless reached, the
burnershutsdownbrieywithoutafaultmessage.Thischaracteristicmustbetakeninto
account when selecting the components (e.g. pumps, heat exchangers and cylinders).
Max.owrate Excessiveowvelocitiesmayleadtoerosion.
MaximumowrateatQmax: CGB-75/100 6000 l/h (100 l/min)
1)Mark"x"indicatesthatallcomponentsoftheuearesur-
rounded by combustion air and meet higher requirements
for gas tightness.
2) For type B23, B33 the combustion air is drawn from the
installationroom(openuegascombustionequipment).
3) In Switzerland, observe the G1 gas guidelines!
For type C, combustion air is drawn through a sealed system
from the outside (room sealed combustion equipment).
Connectiontypes
Device Type 1) Operating mode Can be connected to
Openue Balanced
ue
chimney
moisture resistant
Balanced
ue
chimney
Air/uegas
routing
Certied
balanced
ue
Moisture
resistantue
CGB-
75/100
B23, B33, C13x3),
C33x, C43x, C53,
C53x, C63, C83x,
C93x
X X B33, C53, C83x C43x C13x2),
C33x, C53x
C63x B23, C53x,
C83x, C93x
Category: Germany II2ELL3P, Austria II2H3P,Switzerland I2H

433062555_201804
26.Technicalinformationforwatertreatment
The system must be thoroughly cleaned / ushed before
commissioningandasludgelter/dirttrap(<5μm)e.g.Wolf
accessory installed in the return line. This must be in close
proximity to the boiler.
Thellandtop-upwatermustonlybetreatedwithadesalina-
tion process. The “Water treatment diagram” and the "Maxi-
mum permissible total hardness" table shows the degree to
which water treatment is required. The system water must not
fallbelowatotalhardnessof2°dH,whichcorrespondstocon-
ductivityof≈60μS/cm.Themax.permissibletotalhardness
andthecorrespondingmax.conductivityaresystem-specic
and must be calculated (see also "Maximum permissible
total hardness" table). The desalinated water (conductivity
<=30 μS/cm) must not be mixed with untreated DHW. The
addition of chemicals or de-scaling using single stage ion
exchangers is not permissible, as system damage with asso-
ciated water leaks may occur.
We recommend regular emptying of the sludge lter and
keeping of a system log.
Permissible methods:
- Desalination using mixed-bed cartridges. These are multi
stage ion exchangers. We recommend, for example, using
e.g.GrünbeckorJudocartridgesfortherstll,andlater
as and when required.
- Desalination via reverse osmosis
- Topping up with distilled water
TreatmentofheatingwaterinaccordancewithVDI2035:
WerecommendaheatingwaterpHvalueofbetween8.2and
8.5, also in mixed installations with various materials.
Request a water analysis from the water supply utility. This
mustverifythatthetotalhardnessissufcientlylow.
For a specic system volume V
A,specic >= 10l/kW the next
smaller limit must be used, for V
A,specic>=20l/kWthenext-
but-one limit and for V
A,specic >=40l/kW the smallestvalue
from the following table must be used.
Foraspecicsystemvolumeof>50l/kW,adjustthetotalhard-
nessto2-3°dHusingadesalinationprocess.Thiscorresponds
toconductivityof60-100μS/cm.
If the boiler is integrated in the system without a low loss
header,adjustthetotalhardnessto2-3°dH(Conductivity=
60-100μS/cm).
2
6
10
14
18
600 800200 400 1000 16001200 1400 1800 2000
CGB-75
CGB-100
Water treatment
required
No water treatment
required
System volume in l
Totalhardnessin°dH
Figure: Water treatment
LimitsinrelationtothespecicsystemvolumeVA
(VA=Systemvolume/maximumratedheatingpower
1))
Totalhardnessconversion:1mol/m³=5.6°dH=10°fH
Total
heating
output
VA ≤20l/kW VA >20l/kWand<50l/kW V
A ≥50l/kW
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
[kW] [mol/m³] C [µS/cm] [mol/m³] C [µS/cm] [mol/m³] C [µS/cm][°dH] [°dH] [°dH]
1≤50 ≤16.8 ≤3.0 <800 ≤11.2 ≤2 <800 ≤0.11
3) ≤0.02 <800
2 50-200 ≤11.2 ≤2
<100
≤8.4 ≤1.5
<100
≤0.113) ≤0.02
<1003 200-600 ≤8.4 ≤1.5 ≤0.113) ≤0.02 ≤0.113) ≤0.02
4≤600 ≤0.113) ≤0.02 ≤0.11
3) ≤0.02 ≤0.113) ≤0.02
Thetotalamountofllandtop-upwateroverthelifecycleoftheboilermustnotexceedthreetimesthenominalvolumeofthe
heating system.
1) In systems with multiple boilers, the max. rated heating output of the smallest boiler must be used in accordance with VDI 2035
2) Highsalinity<800µS/cm
Lowsalinity<100µS/cm
3) <0.11°dHrecommendedstandard;permissibleuptolimitof<1°dH
Table 1
GradualincreaseinthedemandforthespecicSystemvolume(V
S
=systemvolume/lowestindividualoutput)andtotalheat-
ing output.
Thetotalamountofllwateroverthelifecycleoftheappliancemustnotexceedthreetimesthenominalvolumeoftheheating
system.
Please note: Thetotalhardnessmustnotfallbelow2°dH.
Heatingwaterqualityrequirementrelatingtotheentireheatingsystem

44 3062555_201804
Example:
Systemoutput=170kW;
system volume VSystem=4000l;
Volume of top-up water
VTop-up =1000l
Total hardness of drinking water CDHW=18.5°dH;
Maximum permissible total hardness Cmax=8.4°dH
Systemoutput=170kW;
system volume VSystem=4.000l;
Volume of top-up water VTop-up=1000l
VAspec=4000l/170kW=23.53l/kW
Total hardness of drinking water CDHW=18.5°dH;
Maximum permissible total hardness Cmax=8.4°dH
Proportionofllingwatertobetreated:
A=100%-[(8.4-0.1)/(18.5–0.1)]x100%=54.9%
54.9%ofthellingandtop-upwatermustbedesalinated.
VTreatment=54.9%x(4.000l+1.000l)=2.746l
Whenllingthesystem,2,745lofdesalinatedwatermust
be added. The system can then be topped up to V max with
drinking water.
When topping up, it is important to check regularly that the
permissible total hardness is not exceeded.
26.Technicalinformationforwatertreatment
Example:
System with a 170 kW boiler;
system volume VSystem=4000l;
VA,specic=4000l/170kW=23.5l/kW
This is greater than 10 l/kW, therefore stage 3 must be se-
lectedinsteadofstage2.Thellandtop-upwatermustbe
in the range of .2 to 8.4 °dH
If the total hardness of the untreated drinking water is too high,
someofthellandtop-upwatermustbedesalinated.
A% desalinated water should be added:
A=100%–[(Cmax–0.1°dH)/(CDHW–0.1°dH)]x100%
Cmax maximumpermissibletotalhardnessin°dH
CDrinking water total hardness of the untreated drinking water
in°dH
We recommend allowing for the expected top-up water during
therstll.Untreateddrinkingwatercanthenbeaddedlater.
VTreatment=Ax(VSystem + VTop-up)
In large systems in stage 4, the top-up water should not be
takenintoaccountduringtherstll.
VTreatment=Ax(VSystem)

46 3062555_201804
Air/uegasrouting
28.Technicalinformation
B23
B33
C53 C93x C43x C83x
C53x
C33x
IIIIIIIIIIII IIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIIII IIIII IIIII IIIII IIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIII
IIIIIIIIIIIIIIIIIIIIIII
II
II
II
I
II
II
I
II
II
II
I
II
II
III
I
IIIII
IIII
II
I
I
II
II
I
II
II
C33x C43x
C83x C93x B33
C13x
Especificaciones del producto
Marca: | Wolf |
Categoría: | Caldera de calefacción central |
Modelo: | CGB-2-75 |
¿Necesitas ayuda?
Si necesitas ayuda con Wolf CGB-2-75 haz una pregunta a continuación y otros usuarios te responderán
Caldera de calefacción central Wolf Manuales

9 Septiembre 2024

9 Septiembre 2024

8 Septiembre 2024

8 Septiembre 2024

8 Septiembre 2024

8 Septiembre 2024

8 Septiembre 2024

15 Agosto 2024
Caldera de calefacción central Manuales
- Caldera de calefacción central ATAG
- Caldera de calefacción central Bosch
- Caldera de calefacción central Junkers
- Caldera de calefacción central Nefit
- Caldera de calefacción central Remeha
- Caldera de calefacción central Vaillant
- Caldera de calefacción central A.O. Smith
- Caldera de calefacción central ACV
- Caldera de calefacción central AGPO
- Caldera de calefacción central Itho
- Caldera de calefacción central De Dietrich
- Caldera de calefacción central Truma
- Caldera de calefacción central Intergas
- Caldera de calefacción central Buderus
- Caldera de calefacción central Elco
- Caldera de calefacción central Nibe
- Caldera de calefacción central Ferroli
- Caldera de calefacción central Viessmann
- Caldera de calefacción central Itho-Daalderop
- Caldera de calefacción central Saunier Duval
- Caldera de calefacción central Vokèra
- Caldera de calefacción central Bulex
- Caldera de calefacción central AWB
- Caldera de calefacción central Fantini Cosmi
- Caldera de calefacción central Daalderop
- Caldera de calefacción central Baxi
- Caldera de calefacción central Morco
- Caldera de calefacción central Mikoterm
- Caldera de calefacción central Oertli
- Caldera de calefacción central Ygnis
- Caldera de calefacción central ROC
- Caldera de calefacción central Thermona
Últimos Caldera de calefacción central Manuales

27 Octubre 2024

19 Octubre 2024

17 Octubre 2024

17 Octubre 2024

17 Octubre 2024

17 Octubre 2024

15 Octubre 2024

10 Octubre 2024

8 Octubre 2024

7 Octubre 2024