Wolf CGB-2-75 Manual de Usario

Lee a continuación 📖 el manual en español para Wolf CGB-2-75 (64 páginas) en la categoría Caldera de calefacción central. Esta guía fue útil para 11 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/64
WOLF GMBH / POSTFACH 1380 / D-84048 MAINBURG / TEL. +49.0.87 51 74- 0 / FAX +49.0.87 51 74- 16 00 / www.WOLF.eu
Doc. no.: 3062555_201804 Subjecttomodications
GB
Installationandoperatinginstructions
Wall mounted gas condensing boiler
CGB wall mounted gas condensing boiler
CGB-75
CGB-100
2 3062555_201804
Tableofcontents
1. Documentation information 3 ................................................................
2. Safety information 4 ..............................................................................
3. Standards and regulations 7 .................................................................
4. Control / Function / Operation 10 ........................................................
5. Delivered condition / standard delivery 12 ............................................
6. Layout ..............................................................................................13
7. Siting instructions 14 ............................................................................
8. Installation .......................................................................................15
9. Dimensions/installation dimensions 16 .................................................
Installation
10. Installation .......................................................................................17
11. Installation of the air/flue gas routing 21 ...............................................
Control
12. Electrical connection 22 ........................................................................
Commissioning
13. Filling the system 28 .............................................................................
14. Conversion to natural gas E/LL (G20/G25) (if necessary) 29 ...............
15. Conversion to LPG P (G31) (if necessary) 30 ......................................
16. Conversion to other gas types (if required) 31 .....................................
17. Checking the gas supply pressure 32 ..................................................
18. Commissioning / setting the BUS address 33 ......................................
19. Displaying / modifying control parameters 34 .......................................
20. Adjusting the modulating pump (accessory) 35 ....................................
21. Limiting the maximum output 36 ...........................................................
22. Testing the combustion parameters 37 .................................................
23. CO2 adjustments 38 .............................................................................
24. Commissioning report 40 ......................................................................
Specication
25. Maintenance and design data 41 .........................................................
26. Technical information for water treatment 43 ........................................
27. System log 45 .......................................................................................
28. Technical information 46 .......................................................................
29. Wiring diagram 56 ................................................................................
30. Specification .................................................................................... 57
31. Troubleshooting ...............................................................................58
32. Product datasheet to EU regulation No. 811/2013 60 ..........................
33. Technical parameters to EU Regulation No. 813/2013 61 ....................
34. Notes ............................................................................................... 62
EU declaration of conformity 63 ...................................................................
33062555_201804
1. Documentationinformation
1.1 Otherapplicabledocuments
- Technical information
- Maintenance instructions
- System and operator’s log
The instructions for all accessory modules and other accessories also apply where
relevant.
1.2 Safekeepingofthesedocuments
The system user or operator should ensure the safekeeping of all instruction manuals
and documents.
► Handovertheseinstallationinstructionsaswellasallotherapplicablemanuals
to the system user or operator.
1.3 Instructingthesystemuser
- Instruct the system user to take out an inspection and maintenance contract with
an approved contractor.
- Inform the system use that the annual inspection and maintenance may only be
performed by an approved contractor.
- Inform the system use that repair work may only be performed by an approved
contractor.
- Inform the system user that only original spare parts may be used.
- Inform the system user that no technical changes may be made to the boiler or
control unit.
- Inform the system user that they are responsible for the safety, environmental com-
patibility and energy quality of the heating system (German Immission Control Act/
Energy Saving Ordinance) [Germany].
- Inform the system user that these instructions and the other applicable documents
must be kept in a safe place.
- Instruct the system user how to operate the heating system.
1.4 Applicabilityoftheseinstructions
These installation instructions apply to CGB-75/100 gas condensing boilers.
1.5 Acceptance
Within four weeks of commissioning of the burner the operator must notify the local
flue gas inspector accordingly. According to the Bundes-KÜO (German Federal
Sweeping and Inspection Act), tests and inspections are only required every 3 years
[Germany].
1.6 Recyclinganddisposal
- Old equipment may only be disconnected from the gas and electricity supply by a
qualiedcontractor.
- Always dispose of materials according to environmental, recycling and waste man-
agement standards.
- Old appliances, wearing parts, defective components and environmentally hazard-
ous liquids and oils must be disposed of or recycled according to applicable waste
disposal regulations without harming the environment.
Theymustnotbedisposedofashouseholdwaste.
- Disposeofpackagingmadeofcardboard,recyclableplasticsandsyntheticller
materials in an environmentally compatible manner through appropriate recycling
systems or a recycling centre.
- Please observe the applicable national and local regulations.
4 3062555_201804
2. Safetyinformation
Danger:ifyousmellgas
- Close the gas valve.
- Open the windows.
- Do not operate any electrical switches.
- Extinguish naked flames.
- From an external location, telephone the gas sup-
ply utility company and an approved contractor.
Danger:ifyousmelluegas
- Switch OFF the appliance.
- Open windows and doors.
- Notify an approved contractor.
Authorised personnel should read these instructions
beforeanyinstallation,commissioningorservicework.
Complywiththespecicationsinthisdocument.Failureto
observetheseinstallationinstructionsvoidsanywarranty
claimagainstWOLF.
Insomecountries,therelevantgassupplycompany
mustbenotiedoftheinstallationofagasboilerand
mustgivetheirapproval.
Pleasenotethatregionalpermitsmayberequiredfor
theuegassystemandconnectingthecondensate
draintothepublicsewer.
Beforestartinginstallationwork,thelocaluegasin-
spectorandwastewaterauthoritymustbeinformed.
Thegascondensingboilermustonlybeinstalled,commis-
sionedandservicedbyqualiedandtrainedpersonnel.
InaccordancewithVDE0105Part1,workonelectrical
components(e.g.control unit)mayonly becarriedout
byqualiedelectricians.
VDEVE regulations [Germany/Austria] and those of
yourlocalpower supplyutilitycompany areapplicable
toelectricalinstallationwork.
Onlyoperatethegascondensingboilerwithintheoutput
range, which is stated in thetechnical documentation
supplied byWOLF. Intendeduse of the boiler includes
exclusiveuseforhotwaterheatingsystemsinaccordance
with DIN EN 12828.
Neverremove,bypassorotherwisedisableanysafetyor
monitoringequipment.Onlyoperatetheapplianceifitis
inperfecttechnicalcondition.
Anyfaultsordamagewhichimpactormightimpactsafety
mustberemediedimmediatelybyaqualiedcontractor.
Onlyreplacefaultycomponentsandequipmentwithorig-
inalWOLFspareparts.
Dangerfrom"live"electricalcomponents
Nevertouchelectricalcomponentsorcontacts
whentheON/OFFswitchisintheONposition.
Thereisadangerofelectrocution,resultingin
arisktohealthordeath.Themainterminalsare
'live',evenwhentheON/OFFswitchisintheOFF
position.
Riskofscalding
Boilersmaycontainhotwater.
Hotwatercancauseseverescalding.
Beforeworkingonpartswhichareincontact
withwater,allowtheappliancetocooltobelow
40°C,shutoffallvalvesand,ifnecessary,drain
theappliance.
Riskofburns
Boilercomponentsmaybeextremelyhot.
Hotcomponentscancauseburns.
Beforeworkingontheopenedupappliance,al-
lowittocoolbelow40°Corwearsuitablegloves.
Symbols
The following warning symbols are used in these instruc-
tions.
These relate to personal safety and operational reliability.
Instructions that must be followed precisely in order
to prevent risk and injury to persons.
Instructions that must be followed precisely in order
to prevent risk and injury to persons from live electri-
cal components.
Indicates technical instructions that must be
observed to prevent damage to the boiler and
malfunctions.
Note
53062555_201804
2. Safetyinformation
Risksfrompressurisedwater
Boilersaresubjecttohighwaterpressure.
Waterpressurecancausesevereinjuries.
Beforeworkingonpartswhichareincontact
withwater,allowtheappliancetocooltobelow
40°C,shutoffallvalvesand,ifnecessary,drain
theappliance.
Note:
Sensorscanbeincontactwithwaterandthere-
foreexposedtopressure.
Workingonthesystem
- Close the gas shut-off valve and secure it against uninten-
tional reopening.
- Isolate the system from the power supply (e.g. by remov-
ing a separate mains fuse or by means of a main switch
or a heating emergency stop switch) and check to ensure
there is no voltage.
- Safeguard the system against reconnection.
Inspectionandservice
- Ensure the correct operation of the gas boiler by having a
contractor carry out inspections at least once a year and
maintenance/repair when required.
- (DVGW - TRGI 2008 - G600).
We recommend arranging a suitable maintenance con-
tract.
- The operator is responsible for the safety, environmental
compatibility and energy quality of the heating system
(German Immission Control Act/Energy Saving Ordi-
nance) [Germany].
- Use only genuine WOLF spare parts.
73062555_201804
3. Standardsandregulations
Observeallstandardsandguidelinesapplicabletotheinstallationandopera-
tionofthisheatingsysteminyourcountry.
Observetheinformationontheboilertypeplate.
Thefollowinglocalregulationsmustbecompliedwithduringinstallationand
operationoftheheatingsystem:
Siting conditions
Ventilation and extract air facilities and connection to a chimney
Electrical connection to the power supply
Technical regulations of the gas supply utility company regarding the connection of
the gas appliance to the local gas mains
Regulations and standards regarding the safety equipment of the water heating
system
• DHWinstallation
Thefollowinggeneralregulations,rulesandguidelinesmustbeobservedfor
installationinparticular:
EN 806 Drinking water supply systems
(DIN) EN 1717 Protection against pollution of potable water in water installations
• EN12831Heatingsystemsinbuildings–Methodforcalculationofthedesignheat
load
• (DIN)EN12828Heatingsystemsinbuildings-Designofwater-basedheating
systems
• (DIN)EN13384Chimneys–Thermalanduiddynamiccalculationmethods
(DIN) EN 50156-1 (VDE 0116 Part 1) Electrical equipment in combustion systems
VDE 0470/EN 60529 Degrees of protection provided by enclosures (IP rating)
VDI 2035 Prevention of damage in hot water heating systems
- Scale formation (Sheet 1)
- Corrosion by water (Sheet 2)
 -Corrosionbyuegases(Sheet3)
8 3062555_201804
3. Standardsandregulations
Weacceptnoliabilityforlossescausedbytechnicalmodicationsmade
tothecontrolunitorthecontrolsystemcomponents.
Improperusemaycausearisktolifeandlimbordamagetotheappli-
anceorotherproperty.
Requirements
The installation of the boiler must be in accordance with the relevant requirements
of Gas Safety (Installation and Use) Regulations 1998, Health and Safety
Document No. 635 (The Electricity at Work Regulations 1989), BS 7671 (IEE
Wiring Regulations) and the Water Supply (Water Fitting) Regulations 1999, or The
Water Bylaws 2000 (Scotland). It should also be in accordance with the relevant
requirements of the Local Authority, Building Regulations, including amendments to
the Approved Documents Part L and J 2002, The Building Regulations (Scotland),
The Building Regulations (Northern Ireland) and the relevant recommendations of
the following British Standards:
BS5440: Fluesandventilationofgasredboilersnotexceeding70kWnet:
- Part 1: Flues
- Part 2: Ventilation
BS5449: Specicationforforcedcirculationhotwaterfordomesticpremises.
BS5546: Specicationforforcedcirculationhotwaterfordomesticpremises.
BS 6700: Services supplying water for domestic use within buildings and their
curtilages.
BS6798: Specicationforinstallationofgasredboilersnotexceeding60kW
input.
BS6891: Specicationforinstallationoflowpressuregaspipeworkupto28mm
(R1") in domestic premises (2nd family gas).
BS 7593: Treatment of water in domestic hot water central heating systems.
Institute of Gas Engineers Publication IGE/UP/7/1998:
"Guide for gas installations in timber framed housing"
Important: The appliance must be installed and serviced by a competent person
as stated in the Gas Safety (Installation and Use) Regulations 1998. In IE, the
installation must be in accordance with the current edition of I.S,813 "Domestic
Gas Installations", the current Building Regulations and reference should be made
to the current ECI rules for electrical installation.
When tightening or loosening threaded connections always use suitable open-ended
spanners (not pipe wrench, or extensions, etc.). Incorrect use and/or unsuitable
tools can lead to damage (e.g. gas or water leaks)!
93062555_201804
3. Standardsandregulations
GascondensingboilerCGB-...
Gas condensing boiler to DIN EN 437 / DIN EN 13203-1 /
DIN EN 15502-1 / DIN EN 15502-2-1 / DIN EN 60335-1 /
DIN EN 60335-2-102 / DIN EN 62233 / DIN EN 61000-3-2 /
DIN EN 61000-3-3 / DIN EN 55014-1, as well as 92/42/
EWG (Efciency Directive) / 2016/426/EU (Gas Applianc-
es Directive) / 2014/30/EU (EMC Directive) / 2014/35/
EU (Low Voltage Directive) / 2009/125/EG (ErP Directive) /
2011/65/EU(RoHS-Richtlinie) /Regulation(EU) 811/2013/
Regulation (EU) 813/2013, with electronic ignition and elec-
tronicue gastemperaturemonitoring, forlowtemperature
heatingandDHWheatinginheatingsystemswithowtemper-
atures up to 90°C and 3 bar permissible operating pressure in
accordance with DIN EN 12828. This WOLF gas condensing
boiler is also approved for installation in garages.
Open ue gas condensing boilers must only
beinstalledinaroomwhichcomplieswiththe
appropriateventilationrequirements.Otherwise
there is a risk of asphyxiation or poisoning.
Readtheinstallationandmaintenanceinstruc-
tionsbeforeinstallingtheboiler.Alsotakeinto
considerationalltechnicalinformation.
Whenoperating theboilerwith LPGuse only
propane according to DIN 51 622, otherwise
faults may arise when starting and operating
thegascondensingboiler,whichmayleadto
damagetotheapplianceandpersonalinjury.
 ApoorlyventedLPGtankcanleadtoproblems
withignition.Insuchacase,contactthecom-
panythatllstheLPGtank.
Theadjustablecylinderwatertemperaturecan
exceed 60°C.For short termoperation above
60°Ctheboilermustbemonitoredinorderto
prevent scalding. For continuous operation,
appropriate precautions should be taken to
preventdraw-offtemperaturesabove60°C,e.g.
thermostaticvalves.
Fig.: Wolf gas condensing boiler
Toprotectagainstscaling,theDHWtemperatureshould
besettomax.50°Cifthetotalwaterhardnessis15°dH
(2.5 mol/m³) or above. Without an accessory regulator,
thiscorrespondstoamaximumhotwaterrotaryselector
settingof6.Withatotalhardnessof20°dHorhigher,use
ofawatertreatmentfacilityinthecoldwatersupplyline
whenheatingDHW isnecessary inordertoextend the
maintenanceintervals.
Failuretotakesuchprecautionswillresultinpremature
scalingoftheapplianceandareductionintheconvenient
availabilityofdomestichotwater.Thecontractorrespon-
sibleshouldalwayscheckthelocalconditions.
10 3062555_201804
4. Control/Function/Operation
DHWtemperatureselection.
WhengascondensingboilersarecombinedwithaDHWcylinder,setting1-9corre-
spondstoacylindertemperatureof15-65°C.TheDHWtemperatureselectorsetting
becomes ineffective when the system is combined with a digital room thermostat or a
weather-compensated controller. The temperature will then be selected at the controller
(accessory).
Heatingwatertemperatureselection.
Settings 2 - 8 correspond, when factory-set, to a heating water temperature of 20-80 °C.
The heating water thermostat setting becomes ineffective when the system is combined
with a digital room thermostat or a weather-compensated controller.
ON/OFF switch
The condensing boiler is OFF in position 0.
Reset
A fault is reset by pressing the reset button which will also restart the system. Press-
ing the reset button re-activates the system, if there was no fault.
ON/OFF switch
ON/OFF
DHWtempera-
ture selector
Reset
button
Heatingwater
temperature
selector
Illuminated ring
Thermometer
Illuminatedringforstatusdisplay
Display Meaning
Flashing green Standby (power supply on; no heat demand)
Constant green light Heatdemand:pumprunning;burnerOFF
Flashing yellow Emissions test mode
Constant yellow light Burneron;amesteady
Flashing red Fault
12 3062555_201804
5. Deliveredcondition/
standarddelivery
Deliveredcondition
Gascondensingboiler
The standard delivery includes:
 1 Gascondensingboilerreadytoconnectwiththecasingtted
1 Mounting bracket for mounting on the wall, with installation
accessories
1 Installation instructions
1 Operating instructions
1 Maintenance instructions
1 Trap with hose
1 Maintenance tools
Accessories
The following accessories are required for installation of the
gas condensing centre:
- Balancedueaccessories(seetechnicalinformation)
- Room temperature-dependent or weather-compensated
control
- Condensate drain outlet with hose retainer
- Gasballvalvewithreprotection
- Fittingassemblyforheatingow,heatingreturnandintegral
safety assembly
- Pump assembly with variable speed pump and integral safety
assembly
- Low loss header set for one or two appliances in a cascade
- Dirtlterintheheatingreturn
Boilerconnections
Fig.: Connections with heating circuit connection set (accessory)
Heatingow
G 1½"
Gas connection
R ¾"
Heatingreturn
G 1½"
Condensate
drain
Heatingcircuitpumpassembly(accessory)
Fig.: Pump assembly (accessory)
Heatingow
G 2"
Heatingreturn
G 2"
Trap
Gas tap
Connection
Expansion vessel 1"
Drain&llvalve
Drain&llvalve
Pressure gauge
Safety valve
Modulating
pump
133062555_201804
CGB-75 / CGB-100
6. Layout
Quick-action air vent valve Gas fan
Heatingwaterheat
exchangers
Condensate trap
Gas combination valve
Heatingreturn Gas supply pipe
Flue gas temperature limiter
Combustion chamber casing
Return sensor
Combustion chamber
cover temperature limiter
Flue
Heatingow
Burner
Flow sensor
Temperature limiter
Flow
Intake pipe
Flue gas test point
Ventilation air test point
Gas:air mixing chamber
Flash trap
Displacement device
Water pressure switch
Gas restrictor
Monitoring electrode
Ignition electrode
Non-return valve
14 3062555_201804
First determine where the appliance is to be installed.
For this, take into account the ue gas connection, lateral
clearances towards walls and the ceiling, and any existing
connectionsforgas,heating,DHWandelectrics.
7. Sitinginstructions
Sound insulation: Under certain critical installation conditions
(e.g. installation on a drywall), additional measures may be
necessary to soundproof the boiler. In such conditions, use
anti-vibration rawl plugs and, if necessary, rubber mounts or
insulation strips.
When using a
low loss header set
Min. 830 mm
Min.
350 mm
Min.
350 mm
Electrical connection must be made on site.
Please maintain the 350 mm clearance to the ceiling to enable
inspection and maintenance work on the boiler to be carried
out, otherwise the necessary inspection and function tests
on components cannot be ensured during maintenance. The
drain hoses must be secured with the retainer above the drain
outlet (trap). The drain must be able to be easily inspected.
Theboilermaybeinstalledonlyinrooms
thatareprotectedfromfrost.
The temperature in the installation room must be be-
tween 0°C and 40°C.
Generalinformation
Clearancebetweentheboilerandcombustible
materials or components is not required, as
temperatureswillnotexceed85°Cattherated
boiler heating output. However, explosive or
readilyammablematerialsmustnotbeused
intheinstallationroomasthiswouldcreatea
riskofreorexplosion.
Duringboilerinstallation,ensurethatnocon-
taminants (e.g. drilling swarf) enter the gas
boiler,otherwisefaultsmaydevelop.
Note
Theinstallation roomand thecombustion air
supplied to the appliance must be free from
chemicals, e.g. uorine, chlorine or sulphur.
These substances are contained in sprays,
paints, adhesives, solvents and cleaning
agents.Underunfavourableconditions,these
mayleadtocorrosion,includingintheuegas
system.
173062555_201804
10.Installation
Heatingcircuitconnectionset
We recommend you connect the heating system with the aid
of a heating circuit connection set.
Connection set comprising: Connection to the appliance with
atgasket,connectiontoheatingow/returnwithballvalves
1" female thread.
Note:
Provideadrain&llvalveatthelowestpointinthesystem. Fig.:Heatingcircuitconnectionset(accessory)
Fig.: Pump assembly (accessory)
TheCGB-75andCGB-100havenotbeenttedwithanex-
pansionvessel atthefactory.Thismustbe ttedexternally
(available from the Wolf accessories range). The expansion
vesselmustbesizedsufciently,inaccordancewithDIN4807.
There must be no shut-offvalve between the
expansion vessel and the condensing boiler,
otherwisethepressurebuild-upwouldperma-
nentlydamagetheboilerduringheating.There
isariskofsystemcomponentsrupturing,giving
risetoariskofscalding.
Thisdoesnotincludebutteryvalvesupstreamoftheexpan-
sionvessel. Thepump ortting assembly includesa 3bar
safety valve (6 bar safety valve is available as an accessory).
Route the discharge pipe line into a drain funnel. The mini-
mum system pressure is 1.0 bar. The boilers are approved
exclusively for sealed systems of up to 6 bar. The maximum
owtemperatureisfactory-setto80°Candmaybeadjusted
to 90°C if required.
Safetyequipment
22 3062555_201804
12.Electricalconnection
Generalinformation
Theinstallationmaybecarriedoutonlyby
anapprovedelectricalcontractor.Observe
VDEregulations [Germany]and alllocal
regulationsofyourpowersupplyutility.
Forinstallation inAustria:The ÖVEreg-
ulationsand requirementsand thoseof
your local power supply utility must be
observed.
Anomnipolarisolatorwithatleast3mm
contactseparationmustbeintegratedin
thepowercableupstreamoftheappliance.
Aconnectionbox mustalsobe installed
onsite.
Neverroutesensorleadsalongside230V
cables.
Danger through 'live' electrical compo-
nents.
Pleasenote:Turnoff theON/OFF switch
beforeremovingthecasing.
Nevertouchelectricalcomponentsorcon-
tactswhentheON/OFFswitchisintheON
position.Thereisadangerofelectrocution,
resultinginarisktohealthordeath.
Themain terminalsare 'live',even when
theON/OFFswitchisintheOFFposition.
During servicing and installation work,
isolatetheentiresystemfromthepower
supplyacross all poles,otherwise there
willbeariskofelectrocution.
233062555_201804
12.Electricalconnection
Terminalbox
The control and safety devices are fully wired and tested.
230Vmainsconnection
In the case of a permanent connection, provide the power
supply via a mains isolator (e.g. heating system emergency
stop button), which ensures at least 3 mm contact separation
for all poles. Flexible power cable, at least 3x1.0 mm2
No other consumers may be connected to the cable.
In rooms with a bathtub or shower, the appliance may only be
connected via an RCD.
Installationinformation–electricalconnection
Isolate the system from the power supply before opening.
Check that the appliance is isolated from the power supply
Swivel the control unit to one side.
Unclip the terminal box from the holder.
The terminal box can be mounted on the wall to the right or
left of the boiler.
Open the terminal box.
Screw the strain relief into the holes provided.
Strip approx. 70 mm off the power cable insulation.
Push the cable through the strain relief and tighten the strain
relief.
Clamp the appropriate cores to the Rast5 plug.
Push the inserts back into the terminal box casing.
Push the Rast-5 plugs back into the correct positions.
Strain relief
F 3.15 A
Rast-5 plug
Terminal box, factory-set
L.h. option
R.h.
option
Power supply
230VAC/50Hz
Power supply, ext. Accessories
230VAC/50Hz/max.300VA
Programmable
output
230VAC/50Hz
Programmable
input
oating
Outside sensor
2-wire eBUS
Connecting digital
WOLF control accessories
24 3062555_201804
12.Electricalconnection
Cylindersensorconnection
- If a cylinder is to be connected, the blue socket of the cylinder
sensor must be connected to the blue plug of the control unit.
- Follow the cylinder installation instructions.
Fig.: Blue plug for cylinder sensor connection
Blue plug
Isolate the condensingboiler from the power
supply priorto changingafuse. The ON/OFF
switchontheappliancedoesnotprovideiso-
lationfromthepowersupply.
Danger through 'live' electrical components.
Nevertouchelectricalcomponentsorcontacts
ifthecondensingboilerhasnotbeenisolated
fromthepowersupply.Dangertolife!
Changingthefuse
Fig.: Terminal box cover open
Fuse
Fig.: Connecting output A1
OutputconnectionA1(230VAC;200VA)
Insert the cable glands into the terminal box. Insert and secure
the connecting cable through the cable gland. Connect the
connecting cable to terminals L1, N and .
The parameters for output A1 are described in the table on
the next page.
Connectionofanexternalheatingcircuitpump
(onsite)(230VACmax.300VA)
Insert the cable glands into the terminal box. Insert and secure
the connecting cable through the cable gland.
Connect the pump 230 V AC to terminals L1 and N and
Thepumpisactivatedwhenthereisdemandinheating,DHW
or frost protection mode.
Fig.: Connection, heating circuit pump
26 3062555_201804
12.Electricalconnection
The functions of input E1 can be scanned and adjusted with eBUS-enabled Wolf control accessories. The following functions
can be allocated to input E1:
Code Meaning
0Nofunction
Input E1 is not taken into consideration by the control unit
1Roomthermostat(factorysetting)
With open input E1, heating operation will be blocked (summer mode), independent of any digital Wolf control
accessories.
2Maximumthermostat,systempressureswitchorcondensateliftingsystem
Connection option for a maximum thermostat, system pressure switch or condensate lifting system. To enable the
burner,inputE1mustbeclosed.Whenthecontactisopen,theburnerisblockedbothforDHWandheating,as
well as for emissions tests and frost protection.
3Notassigned
4Flowswitch
Optionalconnectionforanadditionalwaterowswitch.
input E1 must be closed within 12 seconds after the pump has been switched. Where this is not the case, the
burner will be switched OFF, and fault 41 will be displayed.
5Ventilationairdampermonitoring
See parameters for output A1, no. 7. Supply air damper
8Burnerblock(BOB)
Operation without burner
Closed contact, burner blocked
Heatingcircuitpumpandcylinderchargingpumpoperateinstandardmode
In emissions test mode and frost protection the burner is enabled
Open contact enables the burner again
Connection,inputE1(24V),potential-free
Connect the cable for input 1 at terminals E1 in accordance
withthe wiringdiagram;rstremovethejumperbetweena
and b from the respective terminals.
No external voltage may be connected to in-
put E1, as this could destroy the component.
Note
Fig.: Connection, room thermostat
Connectinglowvoltagedevices
When installing the appliance in places
where there is a risk of increased electro-
magneticinterference,itisadvisabletot
screened sensor leads and eBUS cables.
The cable shield should be connected at
one end to the PE potential in the control
unit.
Note
273062555_201804
12.Electricalconnection
Connection,digitalWolfcontrolaccessories
(e.g.BM,MM,KM,SM1,SM2)
Only controllers from the Wolf range of accessories may be
connected. Each accessory is supplied with its own connection
diagram.
Useatwo-corecable(cross-section>0.5mm²)asthecon-
necting cable between the control unit accessory and the
condensing boiler. Fig.: Connecting digital Wolf control accessories (eBUS interface)
Connectingtheoutsidesensor
The outside temperature sensor for digital control accessory
may be connected to the terminal strip of the boiler connection
AF, or the terminal strip of the control accessory.
Fig.: Connecting the outside sensor
28 3062555_201804
13.Fillingthesystem
Fill the system and vent it properly to safeguard the perfect
functioning of the condensing boiler.
Beforeconnectingthegascondensingboiler,
ush the heating system to remove residues
suchasweldingpearls,hemp,putty,etc.from
thepipework.Checkthedirtlter.
- The gas tap must be shut
- The locking cap on the quick-acting air vent valve should
not be unscrewed
- Open all radiator valves
- Open the return valves, and the heat exchanger will then be
graduallylledwithwaterfrombelow
- With the entire heating system and boiler in a cold condition,
slowlyll thesystem viathe inspection/BDFvalveon the
return until approx. 2 bar pressure is indicated
- Opentheowvalvesonthecondensingboiler
- Fill the heating system to 2 bar pressure In operation, the pressure
gauge (on site) must indicate between 1.5 and 2.5 bar
- Check the entire system for water leaks
- Open the air vent valve
- Start the condensing boiler, set the heating water temperature
selector to position "2" (pump running, illuminated indicator
ring for status display constantly green)
- Ventthepump;todothis,brieyopenandthenretighten
the air vent screw.
- Vent the heating circuit completely, switching the condensing
boiler ON for 5 seconds and OFF for 5 seconds at the ON/
OFFswitch,vetimesinsuccession
- Top up with water (technical information) if the system pres-
sure falls below 1.5 bar
- Open the gas ball valve
- Press reset.
Note
Note: - In continuous mode, the heating circuit is auto-
matically vented via the air vent valve
- At a system pressure below 1.0 bar, the boiler
will enter a fault state
Drain&llvalve
ON/OFF switch ThermometerReset button
Automatic air vent valve
Air vent valve, heating
circuit pump
- Fillthetrapwithwaterandtittotheboiler
Trap
293062555_201804
14.ConversiontonaturalgasE/LL
(G20/G25)(ifnecessary)
Asdelivered,thegascondensingboilersCGB-75/CGB-100areequippedforoperationwithnaturalgasE/H(G20).
For operation with natural gas LL (G25), the gas restrictor must be replaced.
The necessary gas restrictor with the code number “1260for operation with natural gas LL (G25) is included in the scope of delivery
and is attached to the gas pipe for use.
Re-assemble in reverse order.
Note: DuringtheconversionfromLPGtonaturalgas,thegascombinationvalveandtheuegasoriceplate(seepage24/25)
must be removed prior to assembly.
5)
Remove integral gas restrictor and replace with the gas
restrictor for the new gas type (in accordance with the
table on page 25).
Gas restrictor
4)
Undo the gas combination valve from the mixing chamber
for gas/air (four SW8 screws).
4 x screws
SW8
Unplug the connector (rstunscrewthePhillipshead
screws)
1)
Undo gas connection at the gas combination valve
2)
3)
Unscrew the mixing chamber from the fan (three Allen screws 5
mm), and remove air inlet pipe if necessary
6)
After assembly of the gas restrictor, gas combination valve
and air inlet pipe, push the O-ring lubricated with silicone
grease into the packing groove of the fan and ret the
mixing chamber.
O-ring
1
2
30 3062555_201804
15.ConversiontoLPGP(G31)(ifnecessary)
RemovethefourSW8screwsatthegasconnectiontting
andremovethettingfromthegascombinationvalve.
Remove the gas combination valve and gas restrictor.
Place the protective labels at the valve inlet and valve
outlet of the new gas combination valve at the apertures
of the removed valve.
4)
Undo the gas combination valve from the mixing chamber
for gas/air (four SW8 screws).
4 x screws
SW8
3)
Unscrew the mixing chamber from the fan (three Allen
screws 5 mm), and remove air inlet pipe if necessary
7)
6)
Push the O-ring, lubricated with silicone grease, into the
packinggrooveofthefanandtthemixingchamberwith
the gas combination valve to the burner fan.
Tightengasconnectionttingtogassupplyline.
O-ring
Gas combina-
tion valve
Gas connection
tting
O-ring 23.47 x 2.62
Gas restrictor 6.7
Gas combina-
tion valve
Gas restrictor
5)
4 x SW8 screw
Gas connection
tting
Unplug the connector (rstunscrewthePhillipshead
screws)
1)
Undo gas connection at the gas combination valve
2)
Mixing cham-
ber
ScrewthegasconnectionttingwithO-ring26x4tothe
new LPG gas combination valve.
Insert the new 6.7 gas restrictor into the gas combination
valve.
Use screws to secure the gas combination valve with O-ring
23.4 x 2.6 to the mixing chamber.
Threadedtting
Gas connection
333062555_201804
Energysavings
-Instructthecustomeraboutenergysavingoptions.
-Referthecustomertothesection"Informationforen-
ergyefcientoperation"intheoperatinginstructions.
18.Commissioning/settingtheBUS
address
Only qualied personnel must carry out the
commissioningandinitialstart-upoftheboiler
andinstructionoftheuser.
- Check that all ue gas accessories have been correctly
installed
- Opentheshut-offvalvesintheowandreturn
- Open the gas shut-off valve
- Switch on the system ON/OFF switch on the control unit
-Check the ignition and the regular ame structure of the
burner
- The illuminated ring shows a yellow colour, if the boiler starts
correctly
- Check the condensate drain
- Familiarise customers with the operation of the boiler with
reference to the operating instructions and advise them of
therequiredwatertreatmentforllandtop-upwater
- Complete the commissioning report and hand over the
instructions to the customer.
Fig.: Control unit overview
ON/OFF
ON/OFF
switch
ThermometerReset button
Illuminated ring
- Check the boiler and system for leaks;
Normaloperatingpressurewhensystemiscold
1.5-2.0bar;preventwaterleaks
- Checkthelocationandseatingofttedcom-
ponents
- Checkallconnectionsandcomponentunions
forleaks.
- Ifleaktightnesscannotbeensured,thereis
ariskofwaterdamage.
Note
BUSaddresssetting
Whenoperatingseveralboilers(numberofboilers>1)inconjunctionwithacascademodule,settheBUSaddressofeachboiler
in accordance with the table below.
BUS address setting:
Holddowntheresetbutton;after5seconds,thecorrespondingashingcodewillbedisplayed(seetable).Selectthecorresponding
addresswiththeDHWtemperaturerotaryselector.Thenreleasetheresetbuttonagain.
Busaddress RotaryselectorpositionDHW Illuminatedringdisplay
1 1 ashingred
2 2 ashingyellow
3 3 ashingyellow/red
4 4 ashingyellow/green
5 5 ashinggreen/red
0 6 ashinggreen(factorysetting)
34 3062555_201804
19.Displaying/modifyingcontrolparameters
ThecontrolparameterscanbemodiedordisplayedviacontrolaccessorieswitheBUScapability.Forprocedures,checkthe
operating instructions of the relevant accessories.
Topreventdamagetotheheatingsystem,can-
celnightreductionifoutsidetemperaturesfall
below-12°C.Ifthisrequirementisnotobserved,
icemayformontheueoutletwhichmaycause
injuryormateriallosses.
Youcanndtheoutputdatafortheboileron
thetypeplate.
Modications must only be carried out by a
recognisedheatingcontractororbyWolfcus-
tomerservice.
Incorrectoperationcanleadtosystemfaults.
PleasenotewhenadjustingparameterGB05/
A09(frostprotection/outsidetemperature),that
frostprotectionisnolongersafeguardedifyou
settemperatureslowerthan0°C.Thiscanlead
toheatingsystemdamage.
Note
Note
The settings in column 1 apply to control accessories ART, AWT
The settings in column 2 apply to Wolf control systems with BM programming unit
1 2 Parameter Unit Factory setting min Max.
GB01 K 8 5 30HG01 Burnerswitchingdifferential
HG02 Lowfanspeed
Minimum fan speed in %
% CGB-75: 30
CGB-100: 25
30
25
100
100
HG03 TopfanspeedWW
MaximumfanspeedforDHWin%
% CGB-75: 90
CGB-100: 90
30
25
100
100
GB04 HG04 TopfanspeedHZ
Maximum fan speed for heating in %
% CGB-75: 90
CGB-100: 90
30
25
100
100
GB05 A09 Frostprotection,outsidetemperature
Pump ON with connected outside temperature sensor and
insufcienttemperature
°C 2 -10 10
GB06 HG06 Pumpmode
0->PumpONinwintermode
1->PumpeONduringburneroperation
0 0 1
GB07 HG07 Boilercircuitpumpsrun-ontime
Heatingcircuitpumprun-ontimeinminutesinheatingmode
min 1 0 30
GB
08
HG08or
HG22
Maximumlimit,boilercircuitTV-max
applicable to heating operation
°C 80 40 90
GB09 HG09 Burnercycleblock
applies to heating mode
min 7 1 30
HG10 eBUSaddress
heat source BUS address
0 0 5
HG11 DHWquickstart,
temperature of the plate heat exchanger in summer mode
(only applicable for combi boilers)
°C 10 10 60
HG12 Gastype
not supported
0 0 1
GB13 HG13 ProgrammableinputE1
Various functions can be allocated to input E1. See chapter
"Connection input E1"
1
Room
thermostat
0 5
GB14 HG14 ProgrammableoutputA1
Output A1 (230 V AC)
Various functions can be allocated to output A1. See
chapter "Connection output A1"
6
Cylinder
charging pump
0 9
GB15 HG15 Cylinderhysteresis
Switching differential during cylinder re-charging
5 1 30
HG21 MinimumboilerwatertemperatureT-boilermin. °C 20 20 90
353062555_201804
20.Adjustingthemodulatingpump(accessory)
Inheatingmode:
The heating circuit pump (accessory) modulates in proportion to the burner output. This means at maximum burner output, the
pump operates at the maximum pump speed for heating mode. At minimum burner output, the pump operates at the minimum
pump speed for heating mode. In other words, the burner output and pump speed are regulated subject to the required heat load.
Modulating the pump reduces the power consumption.
In DHW mode:
The heating circuit pump will not modulate, but operates constantly at the selected pump speed.
Instandbymode:
The heating circuit pump will not modulate, but operates constantly at the selected pump speed.
Standby mode 20%
Settinglimits:
The speed limits for heating mode can be changed with the BM programming unit.
Solution:
The settings in column 1 apply to control accessories ART, AWT
The settings in column 2 apply to Wolf control systems with BM programming unit
1 2 Parameter Unit Factory
setting
min Max.
GB16 % 20 20 100HG16 Minimumheatingcircuitpumprate
GB 17 HG17 Heatingcircuitpumpoutput,maximum
This parameter must be set at least 5% higher than the
parameter
Minimum heating circuit pump output
% 100 20 100
Fortheminimumpumpspeedforheatingmode,onlysettingsinaccordancewiththistablearepermissible.
Otherwise,thereisariskthatthepumpwillnotstart.
Inaddition,the"Max.pumpspeedforheatingmode"mustbeatleast5%higherthanthe"Minimumpumpspeed
forheatingmode",otherwisethepumpwouldrunat100%.
Note
Problem Troubleshooting
Individual radiators do not heat up properly. Createhydronicbalancing,i.e.reducetheowrateof
hotter radiators
In the spring and autumn (average outside temperature),
the required room temperature is not achieved.
Increase the set room temperature at the controller
e.g. from 20 °C to 25 °C
When the outside temperature is extremely low, the selected
room temperature is not achieved.
Select a steeper heating curve at the controller
e.g. from 1.0 to 1.2
36 3062555_201804
CGB-75/100
Outputsetting(parameterGB04orHG04)
TheoutputsettingcanbemodiedwithWolfcontrolaccessorieswitheBUScapability.
The heating output is determined by the gas fan speed. By reducing the gas fan speed in accordance with the table, the maximum
outputwillbematchedat80/60°CtonaturalgasE/H/LLandLPG.NaturalgasLLisnotapplicableforAustria/Switzerland.LNG
is not applicable for Switzerland.
21.Limitingthemaximumoutput
CGB-75
Heatingoutput (kW) 18 22 25 29 33 37 40 44 48 51 55 59 63 66 70
Display value (%) 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Table: Output settings
CGB-100
Heatingoutput (kW) 18 23 28 34 39 44 49 55 60 65 70 75 81 86 91
Display value (%) 25 30 36 41 46 52 57 63 68 73 79 84 89 95 100
Limitingthemaximumheatingoutputrelativetoaow/returntemperatureof80/60°C
SettingsforparameterGB04/HG04orwithWolfconnectionaccessorieswitheBUScapabilityin[%]
MaximumoutputinkW
373062555_201804
22.Testingthecombustionparameters
Testthecombustionparameterswiththeboilerclosed!
Testingtheintakeair
- Remove the screw from the l.h. test port
- Open the gas shut-off valve
- Insert the test probe
- Start the gas condensing boiler and turn the heating water
temperature selector to the emissions test symbol (illumi-
natedringofthestatusdisplayashesyellow)
- Measure the temperature and CO 2.
In the case of a concentric balanced ue, the ue is not
gas-tight if the CO 2contentis>0.2%.Theleakmustbe
rectied.
- After the test has been completed, switch the boiler off,
remove the test probe and close the test port. Ensure the
screws are tightly secured.
Fig.: Test ports
Test port
"Flue gas"
Test port
"Inlet air"
Testingtheuegasparameters
Whenthetestportisopen,uegascanes-
capeintotheinstallationroom.Thereisarisk
ofasphyxiation.
- Remove the screw from the r.h. test port
- Open the gas shut-off valve
- Start the gas condensing centre and turn the temperature
selector to the emissions test symbol (illuminated ring of
thestatusdisplayashesyellow)
- Insert the test probe
- Measuretheuegasvalues
- After the test has been completed, remove the test probe
and close the test port again. Ensure the screws are tight-
ly secured.
Fig.: Control unit overview
ON/OFF switch Temperature selector
38 3062555_201804
23. CO
2
adjustments
Settingthegas/airmixture
Carryouttheadjustmentsintheorderdescribedbelow.Thegascombinationvalvehasbeensetatthefactory
tothegastypespeciedonthetypeplate.Onlyadjustthegascombinationvalveafterthesystemhasbeen
changedtoadifferentgastypeorwhenservicing.
Iftoolittleheatisdrawnoff,opensomeradiatorvalves.
Note
A)CO2settingforupperload(emissionstestmode)
Release the casing cover with the l.h. and r.h. screw. Release
the bottom of the casing cover and unhook at the top.
- Remove the screw from the l.h. "Flue gas" test port.
- Insert the test probe of the CO
2testinstrumentintothe"ue
gas" test port (approx. 120 mm).
- Turn the temperature selector to "Emissions test"
.
 (illuminatedsignalringasstatusindicatorashesyellow.)
- Ensure that the boiler is not limited electronically.
- Check the CO2 content at full load, and compare the actual
values with those in the table below.
- Correct the CO
2adjustmentasrequiredusingthegasow
adjusting screw on the gas combination valve in accordance
with the table.
Gasowadjust-
ing screw
Fig.: Gas combination valve
- Terminate the emissions test mode by returning the temper-
ature selector to its original position.
- Turnclockwise-lowersCO2 content
- Turnanti-clockwise-raisesCO2 content
Fig.: Emission test with open appliance
Test port
"Flue gas"
Applianceopen
at loadupper
NaturalgasE/H/LL
8.6% ± 0.2%
LNG P
10.1% ± 0.2%
Screws
Fig.: Undoing screws
Aftercompletingservicing,closethefrontcasing
againandfastenthescrewstightly.Thereisa
riskofcarbonmonoxide poisoningiftheue
systemisfaulty.
393062555_201804
B)CO2settingforlowerload(softstart)
- Remove the protective screw over the zero point adjusting
screw with a Torx screwdriver.
- Restart the condensing boiler by pressing the "Reset button".
- Check and correct (if required) the CO2 content approx. 20 s
after the burner start with the CO
2tester,byneadjusting
the zero point adjusting screw with Torx in accordance with
the table. Make this adjustment within 180 s of the burner
start. If necessary, repeat the start phase for the setting
procedure by pressing the reset button.
- Duringthisadjustment,theremustbenoDHWoperation!
- Retighten the protective screw.
23. CO
2
adjustments
- Clockwiserotation–higherCO
2contentincreased!
- Anti-clockwiserotation–lowerCO2contentreduced!
Zero point
screw
Fig.: Gas combination valve
Protective
screw
Gas throughput
adjusting screw
D)Completingtheadjustments
- Shut down the boiler and close the test ports and hose
connection nipples again. Check the gas supply line and
hydraulics for tightness.
C)CheckingtheCO2setting
- Aftercompletingthework,retthecasingcoverandcheck
the CO2 values with the appliance closed.
Observe the CO emissions whilst making
CO2 settings. The gas combination valve is
incorrectly adjusted if the CO value is > 300
ppm when theCO2 value is correct. Takethe
followingsteps:
- Fully insert the zero point adjusting screw
- Open the zero point adjusting screw 1½ revolutions
- Repeat the adjusting process from section A)
- The condensing boiler is correctly adjusted if the CO
2 values
correspond to those in the adjacent table. Fig.: Emission test with closed appliance
Test port
"Flue gas"
Applianceopen
at loadlower
NaturalgasE/H/LL
8.5% ± 0.2%
LNG P
9.7% ± 0.2%
Applianceclosed
at loadupper
NaturalgasE/H/LL
8.8% ± 0.5%
LNG P
10.3% ± 0.5%
Applianceclosed
at loadlower
NaturalgasE/H/LL
8.7% ± 0.5%
LNG P
9.9% ± 0.5%
40 3062555_201804
24.Commissioningreport
Commissioning steps Testvaluesorconrmation
1.) Gas type
NaturalgasE/H
Natural gas LL
LNG
Wobbe Index
Operationalcaloricvalue
________________
________________
kWh/m³
kWh/m³
2.) Gas supply pressure checked?
3.) Gas tightness test carried out?
4.) Air/uesystemchecked?
5.) Water connections checked for tightness?
6.) Filling the trap
7.) Boiler and system vented?
8.) System pressure 1.5 - 2.5 bar?
9.) Systemushed?
10.) Water treatment carried out according to “Technical
information for water treatment”.
 pHvalueset
total hardness set
________________
________________
pHvalue
°dH
11.) No chemical additives (inhibitors; antifreeze) added?
12.) Gas type and heating output entered on label?
13.) Function test carried out?
14.) Flue gas test:
Flue gas temperature gross
Inlet air temperature
Flue gas temperature net
Carbon dioxide content (CO2) or oxygen content (O2)
Carbon monoxide content (CO)
________________
________________
________________
________________
________________
tA (°C)
tL (°C)
(t A
-tL)
(°C)
%
ppm
15.) Casingtted?
16.) System user instructed; documentation handed over?
17.) ________________Commissioningconrmed?
413062555_201804
25.Maintenanceanddesigndata
Hydraulicpressuredropintheboilerexcludingpump
Residualheadoftheheatingcircuitpump(accessory)
The pump modulates subject to burner load. The residual head can be obtained from the diagrams.
CGB-75/100residualhead
withpumpassembly(accessory)
Residual head [mbar]
Water volume [l/h]
CGB-75/100pressuredrop
Pressure drop [mbar]
Water volume [l/h]
0
20
40
60
80
10
0
12
0
14
0
16
0
18
0
20
0
22
0
24
0
26
0
28
0
30
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
CGB-75
20° spread
CGB-100
20° spread
Maximum
Water volume
42 3062555_201804
25.Maintenanceanddesigndata
Sensorresistances
Resistance [Ohm]
Temperature [°C]
Temperature/resistance
0°C 16325 15°C 7857 30°C 4028 60°C 1244
5°C 12697 20°C 6247 40°C 2662 70°C 876
10°C 9952 25°C 5000 50°C 1800 80 °C 628
Max.spread A heat exchanger protective functionisintegratedintotheCGB-75/100. This prevents
stressesinthematerialbylimitingthemaximumtemperaturedifferentialbetweenow
and return. The output is restricted at 28 K and above. If 38 K is nevertheless reached, the
burnershutsdownbrieywithoutafaultmessage.Thischaracteristicmustbetakeninto
account when selecting the components (e.g. pumps, heat exchangers and cylinders).
Max.owrate Excessiveowvelocitiesmayleadtoerosion.
MaximumowrateatQmax: CGB-75/100 6000 l/h (100 l/min)
1)Mark"x"indicatesthatallcomponentsoftheuearesur-
rounded by combustion air and meet higher requirements
for gas tightness.
2) For type B23, B33 the combustion air is drawn from the
installationroom(openuegascombustionequipment).
3) In Switzerland, observe the G1 gas guidelines!
For type C, combustion air is drawn through a sealed system
from the outside (room sealed combustion equipment).
Connectiontypes
Device Type 1) Operating mode Can be connected to
Openue Balanced
ue
chimney
moisture resistant
Balanced
ue
chimney
Air/uegas
routing
Certied
balanced
ue
Moisture
resistantue
CGB-
75/100
B23, B33, C13x3),
C33x, C43x, C53,
C53x, C63, C83x,
C93x
X X B33, C53, C83x C43x C13x2),
C33x, C53x
C63x B23, C53x,
C83x, C93x
Category: Germany II2ELL3P, Austria II2H3P,Switzerland I2H
433062555_201804
26.Technicalinformationforwatertreatment
The system must be thoroughly cleaned / ushed before
commissioningandasludgelter/dirttrap(<5μm)e.g.Wolf
accessory installed in the return line. This must be in close
proximity to the boiler.
Thellandtop-upwatermustonlybetreatedwithadesalina-
tion process. The “Water treatment diagram” and the "Maxi-
mum permissible total hardness" table shows the degree to
which water treatment is required. The system water must not
fallbelowatotalhardnessofdH,whichcorrespondstocon-
ductivityof≈60μS/cm.Themax.permissibletotalhardness
andthecorrespondingmax.conductivityaresystem-specic
and must be calculated (see also "Maximum permissible
total hardness" table). The desalinated water (conductivity
<=30 μS/cm) must not be mixed with untreated DHW. The
addition of chemicals or de-scaling using single stage ion
exchangers is not permissible, as system damage with asso-
ciated water leaks may occur.
We recommend regular emptying of the sludge lter and
keeping of a system log.
Permissible methods:
- Desalination using mixed-bed cartridges. These are multi
stage ion exchangers. We recommend, for example, using
e.g.GrünbeckorJudocartridgesfortherstll,andlater
as and when required.
- Desalination via reverse osmosis
- Topping up with distilled water
TreatmentofheatingwaterinaccordancewithVDI2035:
WerecommendaheatingwaterpHvalueofbetween8.2and
8.5, also in mixed installations with various materials.
Request a water analysis from the water supply utility. This
mustverifythatthetotalhardnessissufcientlylow.
For a specic system volume V
A,specic >= 10l/kW the next
smaller limit must be used, for V
A,specic>=20l/kWthenext-
but-one limit and for V
A,specic >=40l/kW the smallestvalue
from the following table must be used.
Foraspecicsystemvolumeof>50l/kW,adjustthetotalhard-
nessto2-3°dHusingadesalinationprocess.Thiscorresponds
toconductivityof60-100μS/cm.
If the boiler is integrated in the system without a low loss
header,adjustthetotalhardnessto2-3°dH(Conductivity=
60-100μS/cm).
2
6
10
14
18
600 800200 400 1000 16001200 1400 1800 2000
CGB-75
CGB-100
Water treatment
required
No water treatment
required
System volume in l
Totalhardnessin°dH
Figure: Water treatment
LimitsinrelationtothespecicsystemvolumeVA
(VA=Systemvolume/maximumratedheatingpower
1))
Totalhardnessconversion:1mol/m³=5.6°dH=10°fH
Total
heating
output
VA ≤20l/kW VA >20l/kWand<50l/kW V
A ≥50l/kW
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
Total hardness/
total alkaline earths
Conductivity2)
at 25°C
[kW] [mol/m³] C [µS/cm] [mol/m³] C [µS/cm] [mol/m³] C [µS/cm][°dH] [°dH] [°dH]
1≤50 ≤16.8 ≤3.0 <800 ≤11.2 ≤2 <800 ≤0.11
3) ≤0.02 <800
2 50-200 ≤11.2 ≤2
<100
≤8.4 ≤1.5
<100
≤0.113) ≤0.02
<1003 200-600 ≤8.4 ≤1.5 ≤0.113) ≤0.02 ≤0.113) ≤0.02
4≤600 ≤0.113) ≤0.02 ≤0.11
3) ≤0.02 ≤0.113) ≤0.02
Thetotalamountofllandtop-upwateroverthelifecycleoftheboilermustnotexceedthreetimesthenominalvolumeofthe
heating system.
1) In systems with multiple boilers, the max. rated heating output of the smallest boiler must be used in accordance with VDI 2035
2) Highsalinity<800µS/cm
 Lowsalinity<100µS/cm
3) <0.1dHrecommendedstandard;permissibleuptolimitof<1°dH
Table 1
GradualincreaseinthedemandforthespecicSystemvolume(V
S
=systemvolume/lowestindividualoutput)andtotalheat-
ing output.
Thetotalamountofllwateroverthelifecycleoftheappliancemustnotexceedthreetimesthenominalvolumeoftheheating
system.
Please note: Thetotalhardnessmustnotfallbelow2°dH.
Heatingwaterqualityrequirementrelatingtotheentireheatingsystem
44 3062555_201804
Example:
 Systemoutput=170kW;
system volume VSystem=4000l;
Volume of top-up water
VTop-up =1000l
Total hardness of drinking water CDHW=18.5°dH;
Maximum permissible total hardness Cmax=8.4°dH
 Systemoutput=170kW;
system volume VSystem=4.000l;
Volume of top-up water VTop-up=1000l
VAspec=4000l/170kW=23.53l/kW
Total hardness of drinking water CDHW=18.5°dH;
Maximum permissible total hardness Cmax=8.4°dH
Proportionofllingwatertobetreated:
A=100%-[(8.4-0.1)/(18.5–0.1)]x100%=54.9%
54.9%ofthellingandtop-upwatermustbedesalinated.
VTreatment=54.9%x(4.000l+1.000l)=2.746l
 Whenllingthesystem,2,745lofdesalinatedwatermust
be added. The system can then be topped up to V max with
drinking water.
When topping up, it is important to check regularly that the
permissible total hardness is not exceeded.
26.Technicalinformationforwatertreatment
Example:
System with a 170 kW boiler;
system volume VSystem=4000l;
VA,specic=4000l/170kW=23.5l/kW
This is greater than 10 l/kW, therefore stage 3 must be se-
lectedinsteadofstage2.Thellandtop-upwatermustbe
in the range of .2 to 8.4 °dH
If the total hardness of the untreated drinking water is too high,
someofthellandtop-upwatermustbedesalinated.
A% desalinated water should be added:
A=100%–[(Cmax–0.1°dH)/(CDHW–0.1°dH)]x100%
Cmax maximumpermissibletotalhardnessin°dH
CDrinking water total hardness of the untreated drinking water
in°dH
We recommend allowing for the expected top-up water during
therstll.Untreateddrinkingwatercanthenbeaddedlater.
VTreatment=Ax(VSystem + VTop-up)
In large systems in stage 4, the top-up water should not be
takenintoaccountduringtherstll.
VTreatment=Ax(VSystem)
46 3062555_201804
Air/uegasrouting
28.Technicalinformation
B23
B33
C53 C93x C43x C83x
C53x
C33x
IIIIIIIIIIII IIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIIII IIIII IIIII IIIII IIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIII
IIIIIIIIIIIIIIIIIIIIIII
II
II
II
I
II
II
I
II
II
II
I
II
II
III
I
IIIII
IIII
II
I
I
II
II
I
II
II
C33x C43x
C83x C93x B33
C13x

Especificaciones del producto

Marca: Wolf
Categoría: Caldera de calefacción central
Modelo: CGB-2-75

¿Necesitas ayuda?

Si necesitas ayuda con Wolf CGB-2-75 haz una pregunta a continuación y otros usuarios te responderán




Caldera de calefacción central Wolf Manuales

Caldera de calefacción central Manuales

Últimos Caldera de calefacción central Manuales