Klein Tools CL120KIT Manual de Usario

Lee a continuación 📖 el manual en español para Klein Tools CL120KIT (25 páginas) en la categoría Equipo de medición. Esta guía fue útil para 3 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/25
INSTRUCTION MANUAL
600V
400A
20M
Ω
FRANÇAIS pg. 33
ESPAÑOL pg. 17
400A AC Au
Digital Clam
NON-CONTACT
VOLTAGE TESTING
AUTO-RANGING
DATA HOLD
RANGE HOLD
AUDIBLE
CONTINUITY
ENGLISH
CL120KIT
2m
CAT III
600V
2
GENERAL SPECIFICATIONS
Klein Tools CL120 is an automatically ranging digital clamp-meter
that measures AC current via the clamp, and AC/DC voltage,
resistance and continuity via test-leads.
Operating Altitude: 6562 ft. (2000 m)
Relative Humidity: <95% non-condensing
Operating Temp: ° ° ° °32 to 122 F (0 to 50 C)
Storage Temp: ° ° ° °14 to 122 F (-10 to 50 C)
Accuracy: Values stated at 65° to 83°F (18° to 28°C)
Temp Coefcient: °0.1 x (Quoted Accuracy) per C above
28 C or below 18 C, corrections are required when ambient ° °
working temp is outside of Accuracy Temp range
Dimensions: 8.46" x 3.54" x 1.50" (215 x 90 x 38 mm)
Weight: 11.04 oz. (313 g) including batteries
Calibration: Accurate for one year
Auto Power-Off (APO): After approx. 10 minutes of inactivity
Standards: IEC EN 61010-1, 61010-2-032, 61010-2-033.
IEC EN 61326-1, 61326-2-2.
Conforms to UL STD.61010-1,
61010-2-032,61010-2-033;
Certified to CSA STD.C22.2 NO. 61010-1,
61010-2-032,61010-2-033.
Pollution degree: 2
Accuracy: ± (% of reading + # of least significant digits)
Drop Protection: 6.6 ft. (2m)
Safety Rating: CATIII 600V, Class 2, Double insulation
Electromagnetic Environment: IEC EN 61326-1. This
equipment meets requirements for use in basic and controlled
electromagnetic environments like residential properties,
business premises, and light-industrial locations.
Specifications subject to change.
ENGLISH
4
ENGLISH
WARNINGS - GENERAL
To ensure safe operation and service of the meter, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
Before each use verify meter operation by measuring a known voltage
or current.
Never use the meter on a circuit with voltages that exceed the category
based rating of this meter.
Do not use the meter during electrical storms or in wet weather.
Do not use the meter or test leads if they appear to be damaged.
Use only with CAT III or CAT IV rated test leads.
Ensure meter leads are fully seated, and keep fingers away from the
metal probe contacts when making measurements.
Do not open the meter to replace batteries while the probes are connected.
Use caution when working with voltages above 25V AC RMS or 60V DC.
Such voltages pose a shock hazard.
To avoid false readings that can lead to electrical shock, replace batteries
when a low battery indicator appears.
Do not attempt to measure resistance or continuity on a live circuit.
Always adhere to local and national safety codes. Use personal protective
equipment to prevent shock and arc blast injury where hazardous live
conductors are exposed.
WARNINGS - NCV FUNCTION
When NCV Function is initiated, a blinking or steady red glow and an audible
beep indicate voltage present. If no indication, voltage could still be present.
Before and after each use of the NCVT, verify operation by testing a known
working circuit that is within the rating of this unit.
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire
branch circuits may be energized when disconnected and must be retested
before handling.
The NCV tester WILL NOT detect voltage if:
The wire is shielded.
The
operator is not grounded or is otherwise isolated from an effective earth ground.
The voltage is DC.
The NCV tester MAY NOT detect voltage if:
The user is not holding the tester.
The user is insulated from the tester with a glove or other materials.
The wire is partially buried or in a grounded metal conduit.
The tester is at a distance from the voltage source.
The field created by the voltage source is blocked, dampened, or otherwise
interfered with.
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
The tester is outside of operation conditions (listed in Specifications section).
Operation may be affected by differences in socket design and insulation
thickness and type; tester may not be compatible with some types of standard
or tamper resistant (TR) electrical outlets.
Do not apply to uninsulated hazardous live conductors.
Detection above 50V is specified under “normal” conditions as specified below.
The tester may detect at a different threshold at different conditions, or may not
detect at all unless:
The
tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
The user is holding the body of the tester with his or her bare hand.
The user is standing on or connected to earth ground.
The air humidity is nominal (50% relative humidity).
The tester is held still.

Especificaciones del producto

Marca: Klein Tools
Categoría: Equipo de medición
Modelo: CL120KIT

¿Necesitas ayuda?

Si necesitas ayuda con Klein Tools CL120KIT haz una pregunta a continuación y otros usuarios te responderán




Equipo de medición Klein Tools Manuales

Equipo de medición Manuales

Últimos Equipo de medición Manuales