Radson 51052 - SLAVE RF 4 or 6 Zones Thermostaat Manual de Usario

Radson Thermostaat 51052 - SLAVE RF 4 or 6 Zones Thermostaat

Lee a continuación 📖 el manual en español para Radson 51052 - SLAVE RF 4 or 6 Zones Thermostaat (28 páginas) en la categoría Thermostaat. Esta guía fue útil para 13 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/28
USER GUIDE GB
UFH MASTER RF 6 Zones & SLAVE RF 4 or 6 Zones 3-6
GUIDE UTILISATEUR F
UFH MASTER RF 6 Zones & SLAVE RF 4 or 6 Zones 7-10
MONTAGE ANLEITUNG D
FUNK- SCHALTLEISTE MASTER 6 KANÄLE 11-14
HANDLEIDING Nl
UFH MASTER RF 6 Zones & UITBREIDING 4 of 6 Zones 15-18
INSTRUKCJA UŻYTKOWANIA Pl
UFH Listwa MASTER RF 6 Stref 19-22
MANUALUL UTILIZATORULUI Ro
UFH MASTER RF 6 Zone & SLAVE RF 4 sau 6 Zone 23-26
UFH MASTER RF 6 Zones
& SLAVE RF 4 or 6 Zones
2
3
1. USER GUIDE
UFH MASTER RF 6 Zones & SLAVE RF 4 or 6 Zones
Wireless (RF 868MHz) connecting boxes specially designed to control your Under Floor Heating managed by
Normally Closed actuators.
Possibility to extend easily the number of zones up to 12, with the slave modules.
Work in combination with our UFH-RF thermostat range (Digital and Basic)
2. TECHNICAL CHARACTERISTICS
Operating Temperature
0°C to 50°C
Regulation characteristics
Proportional Integral regulation with: 15 minutes cycle for 2°C.
Anti-short cycle: 3 minutes OFF, 2 minutes ON
Supply Voltage
230VAC +- 10% 50Hz
Outputs:
Pump or accessories
Actuators (Normally closed)
Relay => 5A / 250VAC (Free contact)
Relay => 5A / 230 VAC ( L, N)
For easy installation we recommend a maximum of 4 actuators by
zones.
Radio Frequency
868, 3 MHz, <10mW.
Range of approximately 180 meters in open space.
Range of approximately 50 meters in residential environment.
Certifications
EN 300220-1, -2
EN 301489-1, -3
Protection
IP 30
Combination
10 Zones => 1 Master 6 + 1 Slave 4 zones
12 Zones => 1 Master 6 + 1 Slave 6 zones
3. LED EXPLANATION
In normal working mode:
Green Flash:
RF signal reception from the thermostat assigned on this zone.
Red:
Heating demand indicator (Water circulation on this zone)
Red Blinking:
RF alarm, the communication between thermostat and the Master has been lost.
Check the thermostat batteries. (When batteries thermostat must be changed, always replace the 2 batteries)
* If all zones are Red blinking check the RF antenna connection before replacing of all thermostat batteries.
4. POSSIBLE COMBINATIONS WITH SLAVE MODULES
5.

Especificaciones del producto

Marca: Radson
Categoría: Thermostaat
Modelo: 51052 - SLAVE RF 4 or 6 Zones Thermostaat

¿Necesitas ayuda?

Si necesitas ayuda con Radson 51052 - SLAVE RF 4 or 6 Zones Thermostaat haz una pregunta a continuación y otros usuarios te responderán




Thermostaat Radson Manuales

Thermostaat Manuales

Últimos Thermostaat Manuales