Eastron SDM54-M Manual de Usario

Lee a continuación 📖 el manual en español para Eastron SDM54-M (2 páginas) en la categoría Equipo de medición. Esta guía fue útil para 3 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios

Página 1/2
1. Introduction
The SDM54 measures and displays the characteristics
of single phase two wires (1p2w) and three phase four
wires(3p4w) supplies, including voltage, frequency, current,
power, power factor, active and reactive energy, imported
or exported.
Energy is measured in terms of kWh and kVArh. Maximum
demand on power and current can be measured over
preset periods of up to 60 minutes. SDM54 supports max.
100A direct loads per phase, with dual tariff management
availability. The meter is designed for DIN-rail mounting,
with IP51 front protection. The meter is optionally
equipped with pulse outputs, RS485 Modbus port or
M-bus port. Configuration can also be done via keypad,
which is password protected.
1.1 Unit Characteristics
The SDM54 Series are smart three phase energy meters,
covering 3 models with following features and differences:
SDM54 series
Smart Three Phase Energy Meter
Model Measurements Outputs Tariff
Control
SDM54--2T
kWh, kVarh,
W, Var, VA, PF,
Hz, V,
2x Pulse
outputs; RS485
Modbus
Double
tariffs
SDM54-M A, Max.dmd.
Etc.
2x Pulse
outputs; RS485
Modbus
Single
tariff
SDM54-DI
kWh, kVarh,
W, Var, VA, PF,
Hz, V,
2x Digital inputs;
RS485 Modbus
Single
tariff
SDM54-MB-2T A, Max.dmd.
Etc.
2x Pulse
outputs; M-Bus
Double
tariffs
SDM54-MB
kWh, kVarh,
W, Var, VA, PF,
Hz, V,
2x Pulse
outputs; M-Bus
Single
tariff
SDM54-P A, Max.dmd.
Etc.
2x Pulse
outputs
Single
tariff
1.2 RS485 Serial–Modbus RTU
The RS485 serial port with Modbus RTU protocol provides
a means of remotely monitoring and controlling the unit.
Set-up screens are provided for setting up the RS485
port. D/LT645 protocol is optionally available on request.
1.3 M-Bus
The M-Bus port complying with EN13757-3 protocol
provides a means of remotely monitoring and controlling
the meter. Set-up screens are provided for setting up the
M-Bus port.
1.4 Pulse outputs
Two pulse outputs that clock up the measured active and
reactive energy. The constant of pulse output 2 for active
energy is 400imp/kWh (unconfigurable), its width is fixed
at 100ms.
The default constant of configurable pulse output 1
is 400imp/kWh, default pulse width is 100ms. The
configurable pulse output 1 can be set from the set-up
menu.
1.5 Double Tariffs
The meter has double tariffs function for the cost allocation
management. There are two terminal to monitor voltage
input from external device. Once there are voltage
detected within 230V (80~120%), the energy will be
counted in another registers.
2. Start-up Screens
The interface performs
initial testing.
The second screen
indicates the software
version.
Meter serial number;
Modbus ID; Baudrate
info are provided.
After a short delay, the screen will display active energy
measurements.
3. Measurements
> Scroll the display for data-check.
> Change option at Set-up mode
> Exit the Set-up mode
> Set-up mode entry
> Confirmation
3.1 Buttons
There are two buttons on the front panel.
3.2 Measured parameters
Each successive pressing of the button shows
different parameters measured:
Total kWh
Import kWh
Export kWh
Total kVarh
Import kVarh
Export kVarh
(Available in SDM54-2T
only)
Tariff 1’s active energy
Total kWh
Import kWh
Export kWh
The “_” under T1 means
tariff 1 is running at the
moment.
(Available in SDM54-2T
only)
Tariff 1’s reactive energy
Total kVarh
Import kVarh
Export kVarh
(Available in SDM54-2T
only)
Tariff 2’s active energy
Total kWh
Import kWh
Export kWh
(Available in SDM54-2T
only)
Tariff 2’s reactive energy
Total kVarh
Import kVarh
Export kVarh
L1-N Voltage
L2-N Voltage
L3-N Voltage
L1-2 Voltage
L2-3 Voltage
L3-1 Voltage
Frequency
L1 Current
L2 Current
L3 Current
Neutral Current
Total PF (Power Factor)
L1 PF
L2 PF
L3 PF
Total PF (Power Factor)
Max. Current Demand of
L1
L2
L3
Max. Active Power
Demand of
L1
L2
L3
Active Power
Reactive Power
Apparent Power
Active Power of
L1
L2
L3
Reactive Power of
L1
L2
L3
Apparent Power of
L1
L2
L3
4. Set-up
Password is needed
be checked before any
further operation.
The default password
is 1000.
The left screen shows
the set-up menu of the
meter, including main,
communication, time,
and pulse.
System type: the
network type where the
meter is installed and
working.
Options: 3P4W(default),
3P3W, 1P3W, 1P2W.
Password: allows user to
set a new password.
Reset: to reset the max.
Dmd / DI
DMD: information of
current and active power.
DI: digital input counts
Com.: configure
the communication
parameters
Addr: communication
MODBUS Address,
range from 001~247
Baud: communication
baudrate Options:
2400~38400bps;
Default: 9600bps
Parity: Communication
Parity Options: None,
Even, Odd Default: None
Stop: Stop bit of
communication Options:
1 or 2
Default: 1
Time information setting
Backlight: to set the
backlight duration time
after button operation.
Options: on, off, 5, 10,
15, 30, 60, 120 minutes.
Default: 60 minutes
Scroll: automatic screen
scroll time interval.
Options: off, 5,10,15,
30,60 seconds.
Default: off
DMD: demand interval
time Options: 0, 5, 8, 10,
15, 20, 30, 60 minutes.
Default: 60 minutes
Pulse output 1 parameter
setting
The meter pulse output 1
is configurable.
Note: Pulse output 2 is
fixed to
Type: the type of energy
that pulse output is
refer to.
Options: kWh; Imp-kWh;
Exp-kWh kVarh;
Imp-kVarh; Exp-kVarh
Default: Exp-kWh
Constant: Pulse output
constant Options: 1000;
100; 10; 1
Default: 400
Width: Pulse width
Options: 60,100,200mS
Default: 100mS
Keep pressing the button , the meter will get into
Set-up mode.
5. Specifications
5.1 Electrical specifications
• Power: self power supply
(via measured voltage)
• Consumption: <1W, 8VA
• Basic current: 10A
• Max. current : 100A
• Min. current: 0.5A
• Starting current : 0.02A
• Over-current: 30 x Imax for 0.01s
• L-N voltage: 100 to 289V a.c. (not for 3p3w
supplies)
• L-L Voltage: 173 to 500V a.c.
(3p supplies only)
• Frequency: 50Hz (MID version)
50/60Hz (non-MID version)
Accuracy
active energy Class 1(IEC62053-21)/Class
B(EN50470-3)
Reactive energy Class 2 (IEC62053-23)
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
5.2 Environmental specifications
• Operating temperature -25°C to +55°C
• Storage temperature -30°C to +80°C
• Relative humidity 0 to 90%, non-condensing
@40°C
• Altitude Up to 2000m
• Mechanical environment M2
• Electromagnetic environment E2
5.3 Output specifications
Three interfaces are available:
• Modbus RS485 port output ... (SDM54-M, SDM54-2T,
SDM54-DI)
• M-Bus port output ... (SDM54-MB, SDM54-MB-2T)
• two Pulse outputs
5.3.1 Modbus RS485 port output
Baud rate: 2400, 4800, 9600(default),
19200, 38400
Parity: none /odd/even
Stop bits: 1 or 2
RS485 address: 001 to 247
Response time: <80mS
Transmission distance: 1000m
5.3.2 M-Bus port output
Baud rate: 300, 600, 1200, 2400, 4800,
9600
Parity: even/odd
Stop bits: 1 or 2
M-Bus primary
address: 001 to 250
M-Bus Secondary
address: same as the serial number of the
meter.
5.3.3 Pulse Output
The unit provides two pulse outputs indicating real-time
measured energy. Pulse output 1 is configurable; Pulse
output 2 is fixed with constant 400imp/kWh.. Both pulse
outputs are passive type.
Pulse output 1 is configurable. Default setting is
exp-kWh; 100mS, constant 400imp/kWh
Pulse output 2 is non-configurable. It is fixed up with
active kWh. The constant is 400imp/kWh.
5.4 Safety and EMC
• Measurement category IEC 61010-1 CAT III
• Current input Direct connect
• Over-voltage category CAT III
• Dielectric withstand IEC 61010-1 double insulated
• Protective class II
• EMC IEC 61326-1:2013 ; IEC 61326-
2-3:2013
5.5 Mechanics specifications
• DIN rail dimensions 54x100x67.5mm(WxHxD)
• Mounting DIN Rail 35mm
• Ingress protection IP51 front panel (indoor)
• Material Self-extinguishing UL94 V-0
• Weight 265g
If you have any question, please feel free to contact our sales team. Tel: Fax: Email: +86-573-83698881 +86-573-83698883 sales@eastrongroup.com www.eastrongroup.com
Connection Data SDM54
Measurement connection Screw connection
Conductor cross section solid/
stranded/AWG 4-25mm2
Tightening torque 2.5Nm
Other connections (COM and Pulse) Screw connection
Conductor cross section solid/
stranded/AWG 0.5-1.5mm2
Tightening torque 0.4Nm
Warnings
Important Safety Information is contained in the
Maintenance section. Familiarize yourself with this
information before attempting installation or other
procedures. Symbols used in this document:
Risk of Danger: These instructions contain
important safety information. Read them before
starting installation or servicing of the equipment.
Caution: Risk of Electric Shock
User Manual
2022 V1.0
If you have any question, please feel free to contact our sales team. Tel: Fax: Email: +86-573-83698881 +86-573-83698883 sales@eastrongroup.com www.eastrongroup.com
6. Dimensions 7. Wiring diagram
• Three Phase Four Wires:
• Single Phase Two Wires:
• Other terminals
CONTACT US
If you have any question, please feel
free to contact our sales team. Zhejiang
Eastron Electronic Co., Ltd.
No.1369, Chengnan Rd. Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881
Fax: +86-573-83698883
Email: sales@eastrongroup.com
www.eastrongroup.com
EU Declaration of Conformity
We, Zhejiang Eastron Electronic Co LTD
No.1369,Chengnan Rd. Jiaxing, Zhejiang, 314001, China
Ensure and declare that electricity meter types:
SDM54-2T
SDM54M
SDM54-DI
SDM54-MB-2T
SDM54-MB
SDM54-P
with the measurement range
1. 3 x 230/400V 50Hz, 0.5-10(100)A 400imp/ kWh.
Are in conformity with the type as described in the EU-type examination certificate
0120/ SGS0533
The fulfillment of the essential requirements set out in Annex I and in the relevant
instrument spe cific Annexes has been demonstrated.
The electricity meter types described above are in conformity with the relevant Union
harmonization legislation and satisfy the appropriate requirements of the Directive
2014/32/EU with the following standards:
EN50470-1:2006, Electricity metering equipment (AC) part 1: General requirements,
tests and test conditions. Metering equipment (class indexes A, B and C)
EN50470-3:2006, Electricity metering equipment (AC) Part 3: Particular requirements-
Static meters for active energy (class indexes A, B and C)
This Declaration of Conformity is issued under the sole responsibility of the
manufacturer.
Signed on behalf of Zhejiang Eastron Electronic Co., LTD.
Signature:
Date: 2022-2-23
Position: General Manager
8. EU Declaration of Conformity
9. MID certificate

Especificaciones del producto

Marca: Eastron
Categoría: Equipo de medición
Modelo: SDM54-M

¿Necesitas ayuda?

Si necesitas ayuda con Eastron SDM54-M haz una pregunta a continuación y otros usuarios te responderán




Equipo de medición Eastron Manuales

Equipo de medición Manuales

Últimos Equipo de medición Manuales