Kyoritsu KEW 8035 Manual de Usario
Kyoritsu
Equipo de medición
KEW 8035
Lee a continuación 📖 el manual en español para Kyoritsu KEW 8035 (1 páginas) en la categoría Equipo de medición. Esta guía fue útil para 2 personas y fue valorada con 4.5 estrellas en promedio por 2 usuarios
Página 1/1
2. Features
● This is a Phase indicator and can indicate a presence of live
line and phase sequence with the equipped LED and Buzzer
while clipping the 3-phase line over the jacket of a conductor.
● Brightness switch is equipped to make the indication visible
in dimly lit areas.
● A magnet on th e backside of the i nstrument c an f ix the
instrument onto the distribution board and enables safety and
easy measurements.
● Designed to International safety standard IEC 61010-1 (CAT
III 1000V/ CAT IV, 600V, Pollution degree 2)
3. Instrument layout
● Put insulated protective gears when there is a danger of
electrical shock hazard.
● The tip of clip is made of metal and it is not completely
insulated. Be especially careful about the possible shorting
where the measured object has exposed metal parts.
● Never attempt to use the instrument if it's surface or your
hand is wet.
Otherwise, electrical shock accident may occur.
● Ne ver open the Battery co m pa r tm e n t cover and the
instrument case when making a measurement.
● The instrument is to be used only in its intended applications
or conditions. Otherwise, safety functions equipped with the
instrument doesn’t work, and instrument damage or serious
personal injury may be caused.
● Only the qualified person can use the instrument at the
secondary side of high voltage power receiving equipments.
# WARNING
● Never attempt to make any measurement, if any abnormal
conditions are noted, such as broken case, and exposed
metal parts.
●
Do not install substitute parts or make any modification to the
instrument. Return the instrument to your local Kyoritsu distributor
for repair or re-calibration in case of suspected faulty operation.
● Always keep your fingers and hands behind the barrier on
the instrument to avoid the possible shock hazard.
● Do not t r y to re p lac e bat teri es if t he sur fac e of the
instrument is wet.
● Disconnect the clips from the measured conductors first
and power off the instrument before opening the Battery
compartment cover for a battery replacement.
● Stop using the test lead if the outer jacket is damaged and
the inner metal or color jacket is exposed.
# CAUTION
● Do not apply shocks, vibrations or excessive forces onto the
Measurement clips.
●
Never force to open the Measurement clips when they are frozen.
● This instrument can be operated with safe at temperatures
between -10ºC and 50ºC and altitude up to 2000m.
● Keep away from dust and water.
● Precise measurement cannot be made near a charged body
or equipment generating electromagnetic waves.
● Measurable c ondu ctor size is betwe en dia. 2.4mm and
30mm. Accurate measurements for conductors out of this
range cannot be made.
● Measured results are influenced by voltage wires on which
twice or more of the measured voltages exist near the point
to be clipped.
The clip point should be far from such voltage wires.
●
This instrument cannot identify wiring status correctly when an
earth line is connected between phases via delta connection.
Check the connection specification of the measured object.
● Incapable of measuring bus bars or shielded wires. Clip onto
a covered conductor and make a measurement.
●
All the clips should be clipped onto the covered wires and
make measurements. Otherwise, it may cause a malfunction.
1. Safety Warnings
This instrument has been designed, manufactured and tested
according to following standards and de livered in the best
condition after passing quality control tests.
● IEC61010-1 Me asureme nt C AT III 1000V/CAT IV 600V
Pollution degree 2
● IEC61010-031
This instruction manual contains warnings and safety rules which
have to be observed by the user to ensure safe operation of the
instrument and to maintain it in safe condition. Therefore, read
through these operating instructions before using the instrument.
# WARNING
● Read through and understand instructions contained in this
manual before using the instrument.
●
Keep the manual at hand to enable quick reference whenever
necessary.
●
The instrument is to be used only in its intended applications.
● Understand and follow all the safety instructions contained
in the manual.
It is essentia l that th e above instructions are adhered to.
Failure to follow the above instructions may cause injury and
or instrument damage.
Kyoritsu is by no means liable for any damage resulting from
the instrument in contradiction to this cautionary note.
The symbol # indicated on the instrument, means that the
user must refer to the related par ts in the manual for safe
operation of the instrument.
It is essential to read the instructions wherever the symbol
appears in the manual.
# DANGER is reserved for conditions and actions that are
likely to cause serious or fatal injury.
# WARNING is reserved for conditions and actions that can
cause serious or fatal Injury.
# CAUTION is reserved for conditions and actions that can
cause minor injury or instrument damage.
# DANGER
● Confirm a proper operation of the instrument with a well-
known power supply.
● Warning LED might not light up at live status. (earth potential
70V or less). Never touch the wire.
● Voltages may exist when the Live LED is flashing (indicating
Earth phase). Never touch with the wires.
● Never make measurement on a circuit in which the earth
potential exceeds 1000V to avoid electrical shocks.
● Do not make measurement when thunder is rumbling. If the
instrument is in use, stop the measurement immediately and
remove the instrument from the measured object.
● Do not attempt to make measurement in the presence of
flammable gasses. Other wise, the use of the instrument
may cause sparking, which can lead to an explosion.
●
Keep your fingers and hands behind the Protective figerguard
on the instrument to avoid the possible shock hazard.
● Do not touch the Clips during measurements to get accurate
results.
● This instrument cannot find the missing line of the earth line.
●
Do not pull the cable when removing the Measurement clips
from the measured conductors. It may cause a break in cable.
● Power off the instrument after use. Remove the batteries
if the instrument is to be stored and will not be in use for a
long period.
● Do not expose the instr ument to dire ct su nlight, high-
temperature and humidity or dew.
● Dry and store the instrument if it is wet.
● Do not step on or pinch the cord to prevent the jacket of
cable from being damaged.
● Bending or pulling the cord may cause a break in a cord.
● Never give shocks, such as vibration or drop, which may
damage the instrument.
● Use a damp cloth and detergent for cleaning the instrument.
Do not use abrasives or solvents.
Safety Symbols
#Refer to the instructions in the manual to protect the
user and instrument.
Indicates instrument with double or reinforced insulation
AC
This instrument satisfies the marking requirement defined
in the WEEE Directive. This symbol indicates separate
collection for electrical and electronic equipment.
○ Measurement Category
To ensure safe operation of measuring instruments, IEC 61010
establishes safety standards for various electrical environ-
ments, categorized as O to CAT IV, and called measurement
categories. Higher-numbered categories correspond to electrical
environments with greater momentary energy, so a measuring
instrument designed for CAT III environments can endure greater
momentary energy than one designed for CAT II.
O : Circuits which are not directly connected to the mains
power supply.
CAT II : Electrical circuits of equipment connected to an AC
electrical outlet by a power cord.
CAT III : Primary electrical circuits of the equipment connected
directly to the distribution panel, and feeders from the
distribution panel to outlets.
CAT IV : The circuit from the service drop to the service
en t ran ce , a nd to t h e p o we r m ete r an d pr i mar y
overcurrent protection device (distribution panel).
4. Specification
Model KEW8035
Measurement
principle Static induction
Voltage range
3-phase AC70 to 1000V
(voltage to earth, continuous sine wave)
Frequency range
45 to 66Hz
Operating
temperature &
humidity range
-10 to 50ºC, relative humidity 80% or less
(no condensation)
Storage
temperature &
humidity range
-20 to 60ºC, relative humidity 80% or less
(no condensation) (*1)
Location for use
Altitude 2000m or less, Indoor use
Applicable
standards
IEC 61010-1
Measurement CAT III 1000V/CAT IV 600V
Pollution degree 2
IEC61010-031
IEC 61326-1,2-2 (EMC standard)
IEC 61557-1,7
Environmental
standards EU RoHS directive compliant
Dust-proof IP40 (IEC60529)
Withstand
voltage
AC6880V (rms 50/60Hz) for 5 sec
between the tip of Measurement clip and enclosure
Insulation
resistance
10MΩ or more/ 1000V
between the tip of Measurement clip and enclosure
Power source
DC6V
(size AA alkaline battery LR6 or equivalent
1.5V AA × 4pcs)
Auto-power-off 10 min after powering on the instrument
Low battery
warning Power LED flashes at 4.0±0.2V or less (*2)
Current
consumption 15mA (*3)
Continuous use
approx 200 hours (*4)
Conductor size External diameter of the covered conductor
Dia.2.4 to 30mm
Cable length approx 70cm
Dimension 112(L) × 61(W) × 36(D)mm
Weight approx 380g (batteries included)
Accessories
Instruction manual, battery, Soft case, Label for Clip(*5)
(*1) without batteries
(*2) powers off automatically at 3±0.2V or less
(*3) stand-by state (will be doubled (max) at measurement)
(*4) stand-by state (will be 0.5 times at measurement)
(*5) Labels for clip aren't supplied with KEW8035(EU).
5. Checks and Indications
5.1. Preliminary checks
5.1.1. Press the Power switch and power on the instrument.
Then all the LEDs flash in order for about 1 sec. Confirm
all the L EDs light up and flash. Only the Power LED
keeps lighted up in about 1 sec later.
5.1.2.
Apex of “▼” mark on the Measurement clip shall indicate
the center of the measured conductor. Connect each
Measurement clip to 3-phase line as follows: Red to L1,
Phase-U, White to L2, Phase-V, Blue to L3, Phase-W.
5.1.3. Measure a c overed condu ctor AC70V or m ore fir st
to c onf irm each live LED lig hts up. Do not use the
instrument when any of the LED doesn’t light up.
5.1.4. Prese n c e of live wir es a nd ph as e se q u e nce ar e
informed by LED indication and Buzzer sound as soon
as connecting the clips.
Note:
The label of KEW8035(EU) shows the harmonised and also
the pre-harmonised cable colours (UK):
KEW8035(EU)
KEW8035(EU) shows also other alphanumeric identifications on
the label as:
A B C, R S T and U V W.
5.2. Live wire check
# DANGER
● LEDs don’t light up when voltage to earth is 70V or less.
● Voltages may exist at Earth phase.
# CAUTION
● It is impossible to detect the missing phase of the earth line.
Earth line and phase sequence are indicated if the earth line
has a missing phase.
State Indication
Live Phase with flashing LED is
live state.
Missing line
or
Earth line
LED doesn’t light up for
missing line or earth line.
Earth line
(Delta
connection)
Phase with flashing LED is
an earth phase.
Positive
phase
When the green Rotation
LED flashes in the order of
the direction indicated by
the arrow mark (clockwise),
the circuit under test has a
positive phase.
The buzzer sounds
intermittently. (pi-pi-pi
)
Reversed
phase
When the red Rotation
LED flashes in the order
of the direction indicated
by the arrow mark
(counterclockwise), the
circuit under test has a
reversed phase. The buzzer
sounds continuously. (pi---)
5.3. Use the Brightness switch to make the LED indication
brighter.
Brightness of all the LEDs (except for the Power LED) is
increased while pressing down the switch.
6. Battery Replacement
# CAUTION
● Power off the instrument and remove the Measurement clips
from the measured object when replacing batteries to avoid
electrical shocks.
● Do not mix old and new batteries.
● Install batteries in correct polarity as indicated inside the
case.
●
Use the same model of batteries from the same manufacturer.
When the Power LED on the front side of the instrument is
flashing, battery voltage is low. Replace batteries with new
ones to continue further measurements.
Low battery voltage may not affect measurement accuracies.
The instrument is powered off automatically when batteries are
exhausted.
1) Loosen the screw fixing the Battery compartment cover.
2) Slide the Battery compartment cover downwards to remove
it.
3) Replace th e batteries w ith new on es. Four size AA LR6
alkaline or equivalent 1.5V AA type batteries should be used.
4) Install the Battery compartment cover and tighten the screw.
Instruction Manual
Non-Contact Safety Phase Indicator
KEW 8035
Incoming wire
O:Device which is
not directly
connected to the
mains power supply
Socket
Interior wiring
10-22 92-2009E
Protective fingerguard
It is a part providing protection
against electrical shock and
ensuring the minimum required
air and creepage distances.
Measurement clip
Test leads
Live LED (L1, Phase-U)
Live LED (L2, Phase-V)
Live LED (L3, Phase-W)
Phase sequence LED (positive)
Phase sequence LED (reversed)
Rotation LED (positive)
Rotation LED (reversed)
Power switch
Power LED
Brightness switch
Put the Label for clip,
if necessary.
(*5) Labels for clip aren't supplied
with KEW8035(EU).
Screw
Battery compartment
cover
DISTRIBUTOR
Kyoritsu reserves the rights to change specifications or designs
described in this manual without notice and without obligations.
Lines connecting the apexes of
“▼” marks should pass through
the center of the conductor.
Blue
or
Grey
White
or
Black
Red
or
Brown
Especificaciones del producto
Marca: | Kyoritsu |
Categoría: | Equipo de medición |
Modelo: | KEW 8035 |
¿Necesitas ayuda?
Si necesitas ayuda con Kyoritsu KEW 8035 haz una pregunta a continuación y otros usuarios te responderán
Equipo de medición Kyoritsu Manuales
15 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
11 Septiembre 2024
10 Septiembre 2024
10 Septiembre 2024
10 Septiembre 2024
Equipo de medición Manuales
- Equipo de medición Bosch
- Equipo de medición Panasonic
- Equipo de medición DeWalt
- Equipo de medición Honeywell
- Equipo de medición Pioneer
- Equipo de medición Alecto
- Equipo de medición Amprobe
- Equipo de medición Silverline
- Equipo de medición Gude
- Equipo de medición Black And Decker
- Equipo de medición Beurer
- Equipo de medición Yato
- Equipo de medición Megasat
- Equipo de medición Milwaukee
- Equipo de medición Extech
- Equipo de medición Victron Energy
- Equipo de medición ABB
- Equipo de medición Hazet
- Equipo de medición Metrix
- Equipo de medición Benning
- Equipo de medición Einhell
- Equipo de medición Voltcraft
- Equipo de medición Mitsubishi
- Equipo de medición Velleman
- Equipo de medición Vemer
- Equipo de medición Perel
- Equipo de medición IFM
- Equipo de medición Ideal
- Equipo de medición Flir
- Equipo de medición Grohe
- Equipo de medición Technoline
- Equipo de medición Soler And Palau
- Equipo de medición Continental Edison
- Equipo de medición Rossmax
- Equipo de medición Carrier
- Equipo de medición Testboy
- Equipo de medición Goclever
- Equipo de medición Danfoss
- Equipo de medición Hager
- Equipo de medición Bresser
- Equipo de medición TFA
- Equipo de medición Powerfix
- Equipo de medición Owon
- Equipo de medición Flex
- Equipo de medición Finder
- Equipo de medición Fluke
- Equipo de medición Fantini Cosmi
- Equipo de medición Eltako
- Equipo de medición Sekonic
- Equipo de medición EBERLE
- Equipo de medición Basetech
- Equipo de medición Be Cool
- Equipo de medición Laserliner
- Equipo de medición REV
- Equipo de medición Testo
- Equipo de medición Clean Air Optima
- Equipo de medición Eastron
- Equipo de medición ORNO
- Equipo de medición RIDGID
- Equipo de medición Multimetrix
- Equipo de medición GW Instek
- Equipo de medición Logilink
- Equipo de medición SIIG
- Equipo de medición Reely
- Equipo de medición Muller
- Equipo de medición Werma
- Equipo de medición Greisinger
- Equipo de medición Beha-Amprobe
- Equipo de medición Kopp
- Equipo de medición Kern
- Equipo de medición Kogan
- Equipo de medición Kemo
- Equipo de medición Peak
- Equipo de medición Uni-T
- Equipo de medición H-Tronic
- Equipo de medición Elgato
- Equipo de medición Hikmicro
- Equipo de medición PeakTech
- Equipo de medición Sonel
- Equipo de medición Tru Components
- Equipo de medición Emko
- Equipo de medición Entes
- Equipo de medición KS Tools
- Equipo de medición Trumeter
- Equipo de medición Delta Ohm
- Equipo de medición Atmel
- Equipo de medición Qualita
- Equipo de medición MGL Avionics
- Equipo de medición Adwa
- Equipo de medición Chauvin Arnoux
- Equipo de medición Megger
- Equipo de medición AREXX
- Equipo de medición Gossen Metrawatt
- Equipo de medición PCE Instruments
- Equipo de medición CEM
- Equipo de medición SHX
- Equipo de medición Hameg
- Equipo de medición TDE Instruments
- Equipo de medición Joy-it
- Equipo de medición Circutor
- Equipo de medición Wachendorff
- Equipo de medición Klein Tools
- Equipo de medición Duro Pro
- Equipo de medición Aerospace Logic
- Equipo de medición GMW
- Equipo de medición Janitza
- Equipo de medición Sanwa
- Equipo de medición MSW
- Equipo de medición Weidmüller
- Equipo de medición Qubino
- Equipo de medición HT Instruments
- Equipo de medición P3 International
- Equipo de medición Beckmann & Egle
- Equipo de medición Seek Thermal
- Equipo de medición INFICON
- Equipo de medición Motrona
- Equipo de medición Tempo
- Equipo de medición Camille Bauer
- Equipo de medición Blebox
- Equipo de medición Seaward
- Equipo de medición HOZO Design
- Equipo de medición Corentium
- Equipo de medición GQ
- Equipo de medición Tektronix
- Equipo de medición Dostmann Electronic
- Equipo de medición Murideo
- Equipo de medición SecuTech
- Equipo de medición NetPeppers
- Equipo de medición SensoProtect
- Equipo de medición Water-i.d.
- Equipo de medición ZKETECH
- Equipo de medición LabNation
- Equipo de medición Electronics International
- Equipo de medición Cliff
- Equipo de medición ClimeMET
- Equipo de medición Fixpoint
- Equipo de medición Kübler
- Equipo de medición AkYtec
- Equipo de medición Stahlwille
- Equipo de medición MASIMO
- Equipo de medición Milesight
- Equipo de medición Enda
- Equipo de medición CSL
- Equipo de medición Ermenrich
- Equipo de medición PICO
- Equipo de medición Siglent
- Equipo de medición Noyafa
- Equipo de medición Stamos
Últimos Equipo de medición Manuales
26 Octubre 2024
25 Octubre 2024
25 Octubre 2024
24 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024