Safety notes
The installation and commissioning should only be carried out by trained
personnel.
Check the following points before commissioning:
– that the maximum values for all the connections are not exceeded, see
the “Technical data” section,
– that the connection wires are not damaged, and that they are not live
during wiring,
– that the power fl ow direction, and the phase rotation are correct.
The instrument must be taken out of service if safe operation is no lon-
ger possible (e.g. visible damage). In this case, all the connections must
be switched off. The instrument must be returned to the factory or to an
authorized service dealer.
It is forbidden to open the housing and to make modifi cations to the instru-
ment. The instrument is not equipped with an integrated circuit breaker.
During installation check that a labeled switch is installed and that it can
easily be reached by the operators.
Unauthorized repair or alteration of the unit invalidates the warranty.
Contents Page
Brief description 2
Technical data 2
Commissioning 3
Electrical connections 3
Measured value display 5
Operation 9
Display window 10
Programming 13
Programming charts 20
Dimensional drawing 22
Camille Bauer LTD
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 21 21
info@camillebauer.com
www.camillebauer.com
The instruments must only be disposed of in the
correct way!
A 230 / A230s Be 154 807-10 03.13
Operating Instructions
Multifunctional Power
Monitor with System Analysis
SINEAX A 230 / A 230s
2
Brief description
Panel mounting instrument A230 with dimensions 144x144x46 mm
resp. A230s with dimensions 96 x 96 x 46 mm. Four-quadrant mea-
surement for power system and consumption analysis in single and
multi-phase AC systems. Three large LED displays with four digits
plus sign. The converter data are included for direct display and
further processing. Confi gurable display settings for user specifi c
presentation, integrated energy meters, impulse counters, and limit
value indication. Comprehensive average value and max./min. value
functions. Harmonic analysis and THD measurement. Determination
of the neutral wire current. Asymmetry factor and neutral point vol-
tage shift. Two switched outputs for the control of impulse counters,
or for signalling limit alarms.
Technical data
(for more detailed information please see datasheet, download under
www.camillebauer.com)
Measuring inputs
Nominal frequency: 50, 60 Hz
Nominal input voltage: Phase-phase: 500 V
Phase - N: 290 V
Nominal input current: 5 A or 1 A
Continuous thermal rating of inputs
10 A at 346 V in single-phase AC system
10 A at 600 V in three-phase system
Short-time thermal rating of inputs
Input variable Number of
inputs
Duration
of
overloads
Interval between
two overloads
577 V LN 10 1 s 10 s
100 A 10 1 s 100 s
100 A 5 3 s 5 min
Measuring ranges
U, I, S: ≤ 120% of nominal value
P, Q: ≤ ± 120% of nominal value
F: 45 to 65 Hz
cosϕ: ± 1
Display
The measurement display is 4 digit (frequency) and right justifi ed.
Energy values are displayed with 8 digits.
Zero value suppression
PF resp cos Display ---, if Sx < 0.2% Snennϕ:
Currents: Display 0, if Ix < 0.1% Inenn
unb. U: Display 0, if Ø U < 5% Unenn
Pulse/Limit value outputs
Depending on the function selected, the two digital outputs can
be used either as pulse outputs for actual and reactive energy or
as limit signals.
The outputs are passive, and are galvanically isolated from all the
other circuits by opto-couplers. They are suitable to drive tariff
devices (S0-standard DIN 43 864), or 24 V relais.
Uext ≤ 40 V DC (OFF: leakage current ≤ 0.1 mA)
IL ≤ 150 mA (ON: terminal voltage ≤ 1.2 V)
t
U
U
e.g. energy import
e.g. limit value output
R
L
R
L
SO2
SO1
20
21
22
U
ext
Limit value outputs
The measured values can be freely allocated.
Pulse outputs
Active and reactive energy pulses can be generated for the control
of electronic and electromechanical counters.
Power supply
DC-, AC power pack 50 to 400 Hz
100 to 230 V AC/DC ±15% or 24 to 60 V AC/DC ±15%
(UL) 85 bis 125 V DC
Power consumption: 3 VA (without extension module)
A marked and easily accessible current limiting
switch has to be arranged in the vicinity of the device
for turning off the power supply. Fusing should be
10 Amps or less and must be rated for the available
voltage and fault current.
Reference conditions
acc. to IEC 688 resp EN 60 688
Sine 50 - 60 Hz, 15 - 30°, application group II
Measurement accuracy (related to nominal value)
Current, voltage ± 0.2%
Power ± 0.5%
Power factor ± 0.5%
Energy ± 0.5%
Frequency ± 0.02 Hz (abs.)
Environmental conditions
Operating temperature: -10 to +55 °C
Storage temperature: -25 to +70 °C
Humidity relative: ≤ 75%
Altitude: 2000 m max.
Indoor use statement
Safety
Protection class: II (voltage inputs with protection
impedances)
Measuring category: III
Pollution degree: 2
Measurement voltage: 300 V
Test voltage: Between current inputs, power
supply, digital outputs, terminals
of the plugged-in module: 3700 V /
50 Hz / 1 min.
On voltage inputs:
4.25 kV 1.2/50 μs
Module connections: The pin rail at the back is connected
to the voltage inputs via a protec-
tion impedance. Only the permitted
modules can be plugged-in!
Enclosure protection: IP 20
3
Commissioning
The multifunctional power monitor is made operational by switching
on the power supply. The following appears sequentially on the
display:
1. Segment tests: all the segments of the displays and all the LEDs
are lit for 2 s.
2. Version of the software : e.g. A 230 1.04
3. The 3 line voltages at switching on.
Loss of the power supply
All the values confi gured remain during a loss of the power sup-
ply.
On reconnecting the power supply, the last mode selected is dis-
played.
Note of maintenance
No maintenance is required.
Electrical connections
Safety Disconnects
The mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amp fuses are preferred.
WARNING
All mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amps are preferred.
The national provisions (e.g. in Germany VDE 0100
“Conditions concerning the erection of heavy current
facilities with rated voltages below 1000 V”) have to
be observed in the installation and material selection
of electric lines!
When using external PT’s or CT’s refer to the
manufacturer’s information for connections for volta-
ge and current monitoring.
The electrical connections are identical for the SINEAX A 230 and
A 230s.
U1
I1
U2
I2
U3
I3
N
Power supply
Pulse /
Limit value output
Measuring input, acc. to measuring mode
Jumper
1 2 +
No. 1
2022 21
1 2
SO
LOCK
Camille Bauer AG
Switzerland
14 15
11
N
9
I3
8
U3
7
I3
6
I2
5
U2
4
I2
3
I1
2
U1
1
I1
SINEAX A230s
UL: 3~300V 5A 50/60Hz CAT III
IEC: 3~500/290V 5A 50/60Hz CAT III
Ord: 010/123456/010/001
Man: 10/02
NLBxxxx
100-230V AC
85-125V DC
50-400Hz 3VA
230S-121200
Connecting modes
L1
N
k l
K L
2 11 31
Single phase
AC system
L1
N
v
V
u
U
k l
K L
2 11 31
System/
application Terminals
L1
L2
L3
5 182 3
L1
L2
L3
k l
K L
5 182 3
L1
L2
L3
u
U
v
V
v
V
u
U
k l
K L
5 182 3
3-wire
3-phase
symmetric
load
I: L1
Connect the voltage according to the following
table for current measurement in L2 or L3:
Current Terminals 2 5 8
transf.
L2 1 3 L2 L3 L1
L3 1 3 L3 L1 L2
L1
N
2 11 31
Symbol Meaning
Device may only be disposed of in a professional
manner!
Double insulation, device of protection class 2
CE conformity mark. The device fulfi lls the require-
ments of the applicable EC directives.
Products with this mark comply with both the
Canadian (CSA) and the American (UL) requirements
Caution! General hazard point. Read the operating
instructions.
General symbol: Input
General symbol: Output
General symbol: Power supply
CAT III Measurement category CAT III for current and vol-
tage inputs
Especificaciones del producto
Marca: | Camille Bauer |
Categoría: | Equipo de medición |
Modelo: | Sineax A230 |
¿Necesitas ayuda?
Si necesitas ayuda con Camille Bauer Sineax A230 haz una pregunta a continuación y otros usuarios te responderán
Equipo de medición Camille Bauer Manuales
13 Septiembre 2024
13 Septiembre 2024
13 Septiembre 2024
13 Septiembre 2024
11 Septiembre 2024
Equipo de medición Manuales
- Equipo de medición Bosch
- Equipo de medición Panasonic
- Equipo de medición DeWalt
- Equipo de medición Honeywell
- Equipo de medición Pioneer
- Equipo de medición Alecto
- Equipo de medición Amprobe
- Equipo de medición Silverline
- Equipo de medición Gude
- Equipo de medición Black And Decker
- Equipo de medición Beurer
- Equipo de medición Yato
- Equipo de medición Megasat
- Equipo de medición Meec Tools
- Equipo de medición Milwaukee
- Equipo de medición Extech
- Equipo de medición Victron Energy
- Equipo de medición ABB
- Equipo de medición Hazet
- Equipo de medición Metrix
- Equipo de medición Benning
- Equipo de medición Einhell
- Equipo de medición Voltcraft
- Equipo de medición Mitsubishi
- Equipo de medición Velleman
- Equipo de medición Vemer
- Equipo de medición Perel
- Equipo de medición Kyoritsu
- Equipo de medición IFM
- Equipo de medición Ideal
- Equipo de medición Flir
- Equipo de medición Grohe
- Equipo de medición Technoline
- Equipo de medición Soler And Palau
- Equipo de medición Continental Edison
- Equipo de medición Rossmax
- Equipo de medición Carrier
- Equipo de medición Testboy
- Equipo de medición Goclever
- Equipo de medición Danfoss
- Equipo de medición Hager
- Equipo de medición Bresser
- Equipo de medición TFA
- Equipo de medición Powerfix
- Equipo de medición Owon
- Equipo de medición Flex
- Equipo de medición Finder
- Equipo de medición Fluke
- Equipo de medición Fantini Cosmi
- Equipo de medición Eltako
- Equipo de medición Sekonic
- Equipo de medición EBERLE
- Equipo de medición Basetech
- Equipo de medición Be Cool
- Equipo de medición Laserliner
- Equipo de medición REV
- Equipo de medición Testo
- Equipo de medición Clean Air Optima
- Equipo de medición Bruder Mannesmann
- Equipo de medición Eastron
- Equipo de medición ORNO
- Equipo de medición RIDGID
- Equipo de medición Multimetrix
- Equipo de medición GW Instek
- Equipo de medición Logilink
- Equipo de medición SIIG
- Equipo de medición Reely
- Equipo de medición Muller
- Equipo de medición Werma
- Equipo de medición Greisinger
- Equipo de medición Beha-Amprobe
- Equipo de medición Kopp
- Equipo de medición Kern
- Equipo de medición Kogan
- Equipo de medición Kemo
- Equipo de medición Peak
- Equipo de medición Uni-T
- Equipo de medición H-Tronic
- Equipo de medición Elgato
- Equipo de medición Hikmicro
- Equipo de medición PeakTech
- Equipo de medición Sonel
- Equipo de medición Tru Components
- Equipo de medición Emko
- Equipo de medición Entes
- Equipo de medición KS Tools
- Equipo de medición Trumeter
- Equipo de medición Delta Ohm
- Equipo de medición Atmel
- Equipo de medición Qualita
- Equipo de medición MGL Avionics
- Equipo de medición Adwa
- Equipo de medición Chauvin Arnoux
- Equipo de medición Megger
- Equipo de medición AREXX
- Equipo de medición Gossen Metrawatt
- Equipo de medición PCE Instruments
- Equipo de medición CEM
- Equipo de medición SHX
- Equipo de medición Hameg
- Equipo de medición TDE Instruments
- Equipo de medición Joy-it
- Equipo de medición Circutor
- Equipo de medición Wachendorff
- Equipo de medición Klein Tools
- Equipo de medición Duro Pro
- Equipo de medición Aerospace Logic
- Equipo de medición GMW
- Equipo de medición Janitza
- Equipo de medición Sanwa
- Equipo de medición MSW
- Equipo de medición Weidmüller
- Equipo de medición Qubino
- Equipo de medición HT Instruments
- Equipo de medición P3 International
- Equipo de medición Beckmann & Egle
- Equipo de medición Seek Thermal
- Equipo de medición INFICON
- Equipo de medición Motrona
- Equipo de medición Tempo
- Equipo de medición Blebox
- Equipo de medición Seaward
- Equipo de medición HOZO Design
- Equipo de medición Corentium
- Equipo de medición GQ
- Equipo de medición Tektronix
- Equipo de medición Dostmann Electronic
- Equipo de medición Murideo
- Equipo de medición SecuTech
- Equipo de medición NetPeppers
- Equipo de medición SensoProtect
- Equipo de medición Water-i.d.
- Equipo de medición ZKETECH
- Equipo de medición LabNation
- Equipo de medición Electronics International
- Equipo de medición Cliff
- Equipo de medición ClimeMET
- Equipo de medición Fixpoint
- Equipo de medición Kübler
- Equipo de medición AkYtec
- Equipo de medición Stahlwille
- Equipo de medición MASIMO
- Equipo de medición Milesight
- Equipo de medición Enda
- Equipo de medición CSL
- Equipo de medición Ermenrich
- Equipo de medición PICO
- Equipo de medición Siglent
- Equipo de medición Noyafa
- Equipo de medición Stamos
Últimos Equipo de medición Manuales
26 Octubre 2024
25 Octubre 2024
25 Octubre 2024
24 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024