Operating Instructions
3. Brief description
The signal isolator serves to electrically insulate SINEAX SI 815-5
the 4...20 mA input circuit of a two-wire transmitter. It performs two
tasks at the same time. Firstly it provides electrical insulation and
secondly it conducts the power supply needed for measurement to
the two-wire transmitter without injecting into the circuit itself. Thus
the isolator does not require an power supply connection itself.
Some versions of the SINEAX SI 815-5 are designed for FSK com-
munication. They are used in conjunction with “intelligent” two-wire
transmitter which are capable of dialogue and operation according
to the FSK principle and the HART or user-specifi c protocol.
The series also includes “intrinsically safe” versions [EEx ia] IIC with
an intrinsically safe measurement/supply circuit. These operate in
conjunction with intrinsically safe two-wire transmitters located in
explosion hazard areas.
O
T ZG
A
LR
X
mA E
2-wire
transducer
+
–
+
–
4...20 mA
W
Digital signal
Power supply
Analog signal
Power pack
Power
supply
Receiver
4...20 mA
Hand-held
terminal
FSK
Fig. 3. Block diagram.
4. Specifi cation and ordering information
Order Code 815 - 5 . 1 . .
1. Mechanical design
Housing N17 5
2. Version
Standard (non-Ex)
Output signal non-intrinsically safe 1
[EEx ia] IIC,
Output signal intrinsically safe 2
3. Number of isolation and
transmission channels
1 channel (interface) 1
4. Field communications protocol
Without FSK communication 0
With FSK communication 1
5. Climatic rating
Standard climatic rating 0
Improved climatic rating 1
The following symbols in the Operating Instructions indicate safety
precautions which must be strictly observed:
The instruments must only be disposed of in the
correct way!
Contents
1. Read fi rst and then … .............................................................1
2. Scope of supply .......................................................................1
3. Brief description .......................................................................1
4. Specifi cation and ordering information ....................................1
5. Technical data ..........................................................................2
6. Mounting ..................................................................................2
7. Electrical connections ..............................................................3
8. Commissioning and maintenance ...........................................4
9. Releasing the signal isolator ....................................................4
10. Dimensional drawings ..............................................................4
11. Declaration of conformity ........................................................4
1. Read fi rst and then …
The proper and safe operation of the device assumes
that the Operating Instructions are read carefully and
the safety warnings given in the sections
6. Mounting
7. Electrical connections
are .observed
The device should only be handled by appropriately
trained personnel who are familiar with it and author-
ised to work in electrical installations.
Unauthorized repair or alteration of the unit invalidates
the warranty.
2. Scope of supply
Signal isolator (Fig. 1)
1 Adapter (Fig. 1) for wall mounting
1 Operating Instructions (Fig. 2) in English, French, German
1 Ex approval (Fig. 2), only for Ex version devices
Fig. 1 Fig. 2
2
1 “Input” and “output” in this case refer to the direction of power supply
fl ow.
5. Technical data
Input signal E1
(Input circuit between signal isolator and power pack)
DC current signal IE: 4...20 mA
Voltage UE: 12…30 V DC
Overload capacity: ≤ 50 mA continuous
Output signal A1
(Input circuit between signal isolator and 2-wire transmitter)
DC current signal IA: 4...20 mA
Voltage UA (for IE = 20 mA and UE = 22 V):
> 19.3 V with standard (non-Ex) version,
not designed for communications protocol
> 18.5 V with standard (non-Ex) version,
designed for FSK communication
> 14.3 V with Ex versions,
not designed for communications protocol
> 13.3 V with Ex versions, designed for FSK communication
Voltage drop UV = UE – UA (at UE) 12…22 V:
< 2.7 V with standard (non-Ex) version,
not designed for communications protocol
< 3.5 V with standard (non-Ex) version,
designed for FSK communication
< 7.7 V with Ex versions,
not designed for communications protocol
< 8.7 V with Ex versions, designed for FSK communication
Residual ripple: < 20 mV ss (120 kHz)
Time constant: Approx. 5 ms
Accuracy data
Error: < ± 0.2%
(Reference value 20 mA of output signal,
including typical linearity error < ± 0.1%)
Ambient conditions
Climatic rating: Climate class 3Z acc. to VDI/VDE 3540
Operating temperature: – 25 to +55 °C
to +55 °C– 20
(for the Ex versions: output signals “intrinsi-
cally safe”)
Storage temperature: – 40 to +70 °C
Annual mean
relative humidity: ≤ 75% standard climatic rating
≤ 95% improved climatic rating
Seismic test: 5 g, < 200 Hz, 2 h in each of 3 directions
Shock test: , 10 shocks in each of 3 directions50 g
Altitude: 2000 m max.
Indoor use statement!
6. Mounting
The SINEAX SI 815-5 can be mounted either on a top-hat rail or
directly onto a wall or mounting plate using the adapter (standard
accessory).
Make sure that the ambient temperature stays within the
permissible limits:
– 25 and + 55 °C for standard instruments
– 20 and + 55 °C for instruments in version!Ex
6.1 Top-hat rail mounting
Simply clip the device onto the top-hat rail (EN 50 022) (see Fig. 4).
Fig. 4. Mounting on top-hat rails 35 x 15 or 35 x 7.5 mm.
6.2 Wall mounting
Drill 2 holes in the wall or panel as shown in the drilling pattern
(Fig. 5). Now secure the adapter (standard accessory) to the wall or
panel using two 5 mm diameter screws (Fig. 6). Clip the device onto
the adapter (Fig. 7).
5.8
60
Fig. 5. Drilling pattern. Fig. 6. Adapter
mounted on wall.
Fig. 7. Mounting on the adapter.
3
7. Electrical connections
The electrical connections are made to screw terminals which are
easily accessible from the front of the signal isolator (see Fig. 9) and
can accommodate wire gauges up to 2,5 mm
2.
Make sure that the cables are not live when making
the connections!
In the case of explosionproof ver-“Intrinsically safe”
sion, the supplementary information given on the type
examination certifi cation, the EN 60 079-14 and also
local regulations applicable to electrical installations in
explosion hazard areas must be taken into account.
Note that, ...
... the required electrical insulation and transmission
data agree with the data on the nameplate of the
SINEAX SI 815-5 ( input signal and output
signal, see Fig. 8)!
... the input and output cables should be twisted
pairs and run as far as possible away from heavy
current cables!
Fig. 8. Example of a nameplate.
Connect the input E and output A leads and according to Fig. 9.
Signal isolator in housing N17 with one isolation and trans-
mission channel
Fig. 9. SINEAX SI 815-511..,
Standard (non-Ex) version
and
SINEAX SI 815-521..,
Ex version
(output signal A “intrinsically safe”).
3
–
–
1+
2
4
+
A
–
+
–
+
E
7.1 Connection of the hand-held-terminals HHT
The FSK transmission versions of the isolation transformers SINEAX
SI 815-5111 . and SI 815-5 .11. can relay a frequency modulated
digital signal in both directions in addition to the analog signal and
the auxiliary supply. Connect the hand-held terminal HHT as shown
in Figures 10 and 11.
The burden of the signalling circuit must be as least
250 Ω. The burden is represented in Figures 10 and 11
by the resistor RB.
4+
UM 12 V A
X
2-wire
transducer
Digital signal
Power pack
Power
supply
HHT
FSK
XSI 815
3–
2+
1–
E
UV < 3,5 V
Power supply
Analog signal
US 24 V
RB
Safe area
UM
minimum operating voltage
US supply voltage
Fig. 10. SINEAX SI 815-5111.
Standard (non-Ex) version,
designed for FSK communication, frequency 500 Hz … 35 kHz.
4+
UM12 V A
X
2-wire
transmitter
Digital signal
Power pack
Power
supply
HHT
FSK
XSI 815
3–
2+
1–
E
UV < 8,7 V
Power supply
Analog signal
US>26 V
RB
Safe areaHazardous area
UM
minimum operating voltage
US supply voltage
Fig. 11. SINEAX SI 815-5 .11.
Ex version, (output signal A “intrinsically safe”),
designed for FSK communication, frequency 500 Hz … 35 kHz.
Type: 815 – 51110
999295/1416280
Mat:
SINEAX SI 815
Passiver DC-Signaltrenner
Passive DC signal isolator
Camille Bauer AG
Aargauerstr. 7
CH-5610 Wohlen
Switzerland
Manufactured: 1998
Tamb 55°C
4…20 mA 12V/30V HART
4…20 mA
0,2 2,3
Especificaciones del producto
Marca: | Camille Bauer |
Categoría: | Equipo de medición |
Modelo: | Sineax Si815-5 |
¿Necesitas ayuda?
Si necesitas ayuda con Camille Bauer Sineax Si815-5 haz una pregunta a continuación y otros usuarios te responderán
Equipo de medición Camille Bauer Manuales
13 Septiembre 2024
13 Septiembre 2024
13 Septiembre 2024
13 Septiembre 2024
11 Septiembre 2024
Equipo de medición Manuales
- Equipo de medición Bosch
- Equipo de medición Panasonic
- Equipo de medición DeWalt
- Equipo de medición Fysic
- Equipo de medición Honeywell
- Equipo de medición Pioneer
- Equipo de medición Alecto
- Equipo de medición Amprobe
- Equipo de medición Silverline
- Equipo de medición Gude
- Equipo de medición Black And Decker
- Equipo de medición Pyle
- Equipo de medición Beurer
- Equipo de medición Yato
- Equipo de medición Megasat
- Equipo de medición Meec Tools
- Equipo de medición Milwaukee
- Equipo de medición Extech
- Equipo de medición Victron Energy
- Equipo de medición ABB
- Equipo de medición Hazet
- Equipo de medición Metrix
- Equipo de medición Benning
- Equipo de medición Einhell
- Equipo de medición Voltcraft
- Equipo de medición Mitsubishi
- Equipo de medición Velleman
- Equipo de medición Vemer
- Equipo de medición Perel
- Equipo de medición Kyoritsu
- Equipo de medición IFM
- Equipo de medición Ideal
- Equipo de medición Flir
- Equipo de medición Grohe
- Equipo de medición Technoline
- Equipo de medición Soler And Palau
- Equipo de medición Continental Edison
- Equipo de medición Rossmax
- Equipo de medición Carrier
- Equipo de medición Testboy
- Equipo de medición Goclever
- Equipo de medición Danfoss
- Equipo de medición Hager
- Equipo de medición Bresser
- Equipo de medición TFA
- Equipo de medición Powerfix
- Equipo de medición Owon
- Equipo de medición Flex
- Equipo de medición Finder
- Equipo de medición Fluke
- Equipo de medición Fantini Cosmi
- Equipo de medición Eltako
- Equipo de medición Sekonic
- Equipo de medición EBERLE
- Equipo de medición Basetech
- Equipo de medición Stabila
- Equipo de medición Be Cool
- Equipo de medición Laserliner
- Equipo de medición REV
- Equipo de medición Testo
- Equipo de medición Clean Air Optima
- Equipo de medición Bruder Mannesmann
- Equipo de medición Eastron
- Equipo de medición ORNO
- Equipo de medición RIDGID
- Equipo de medición Monacor
- Equipo de medición Multimetrix
- Equipo de medición GW Instek
- Equipo de medición Logilink
- Equipo de medición SIIG
- Equipo de medición Reely
- Equipo de medición Muller
- Equipo de medición Werma
- Equipo de medición Greisinger
- Equipo de medición Beha-Amprobe
- Equipo de medición Kopp
- Equipo de medición Kern
- Equipo de medición Kogan
- Equipo de medición Kemo
- Equipo de medición Peak
- Equipo de medición Uni-T
- Equipo de medición H-Tronic
- Equipo de medición Elgato
- Equipo de medición Hikmicro
- Equipo de medición PeakTech
- Equipo de medición Sonel
- Equipo de medición Tru Components
- Equipo de medición Emko
- Equipo de medición Entes
- Equipo de medición KS Tools
- Equipo de medición Trumeter
- Equipo de medición Delta Ohm
- Equipo de medición Atmel
- Equipo de medición Qualita
- Equipo de medición MGL Avionics
- Equipo de medición Adwa
- Equipo de medición Chauvin Arnoux
- Equipo de medición Megger
- Equipo de medición AREXX
- Equipo de medición Gossen Metrawatt
- Equipo de medición PCE Instruments
- Equipo de medición CEM
- Equipo de medición SHX
- Equipo de medición Hameg
- Equipo de medición TDE Instruments
- Equipo de medición Joy-it
- Equipo de medición Circutor
- Equipo de medición Wachendorff
- Equipo de medición Klein Tools
- Equipo de medición Duro Pro
- Equipo de medición Aerospace Logic
- Equipo de medición GMW
- Equipo de medición Janitza
- Equipo de medición Sanwa
- Equipo de medición MSW
- Equipo de medición Weidmüller
- Equipo de medición Qubino
- Equipo de medición Lascar Electronics
- Equipo de medición HT Instruments
- Equipo de medición P3 International
- Equipo de medición Beckmann & Egle
- Equipo de medición Seek Thermal
- Equipo de medición INFICON
- Equipo de medición Motrona
- Equipo de medición Tempo
- Equipo de medición Blebox
- Equipo de medición Seaward
- Equipo de medición HOZO Design
- Equipo de medición Corentium
- Equipo de medición GQ
- Equipo de medición Tektronix
- Equipo de medición Dostmann Electronic
- Equipo de medición Murideo
- Equipo de medición SecuTech
- Equipo de medición NetPeppers
- Equipo de medición SensoProtect
- Equipo de medición Water-i.d.
- Equipo de medición ZKETECH
- Equipo de medición LabNation
- Equipo de medición Electronics International
- Equipo de medición Cliff
- Equipo de medición ClimeMET
- Equipo de medición Fixpoint
- Equipo de medición Kübler
- Equipo de medición AkYtec
- Equipo de medición Stahlwille
- Equipo de medición MASIMO
- Equipo de medición Milesight
- Equipo de medición Enda
- Equipo de medición CSL
- Equipo de medición Ermenrich
- Equipo de medición PICO
- Equipo de medición Siglent
- Equipo de medición Noyafa
- Equipo de medición Stamos
Últimos Equipo de medición Manuales
26 Octubre 2024
25 Octubre 2024
25 Octubre 2024
24 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024
23 Octubre 2024